Limit supervision
For limit supervision, two comparator groups
with 3 comparators each are available. The re-
sults of the comparators A, B and C can be com-
bined with AND or OR and the result can be
inverted optionally. The total combination result
of comparator group 1 can be assigned to dig-
ital output 1 and the combination result of com-
parator 2 can be assigned to digital output 2.
Diagr. Limit supervision with digital output 1.
Measured value (Addr.015)
Limit (Addr.013)
Minimum time (Addr.016)
Run up time (Addr. 064)
Operator ">=", "<" (Addr.017)
Tafel
Comparator A
Measured value (Addr.025)
Limit (Addr.023)
Minimum time (Addr.026)
Run up time (Addr. 066)
Operator ">=", "<" (Addr.027)
Comparator C
Measured value(Addr.020)
Limit (Addr.018)
Minimum time (Addr.021)
Run up time (Addr. 065)
Operator ">=", "<" (Addr.022)
Comparator B
Comparator group 1
- Combine results of the comparators A, B and C AND or OR (Addr.043).
- Invert result (Addr.044).
Combine results of the comparators A, B and C
Total combination result (Addr.389)
Digital output 1 (Addr.002 = 1)
11
12
Data memory
(Addr.500)
Data memory
(Addr.500)
Data memory
(Addr.500)
Total run time
(Addr.396)
Total run time
(Addr.400)
Total run time
(Addr.398)
Comparator result (Addr.386)
Comparator result (Addr.388)
Comparator result (Addr.387)
Attention!
At UMG96S only the first three digits of a
parameter can be set.
With GridVis, all digits of a parameter can
be set.
Because of the measuring accuracy of
the UMG96S, only the first three digits of
a parameter are relevant.