Page 60
Inputs and outputs
The terminals 12 and 13 at UMG96S can be
assigned to the following functions:
0 = Pulse output,
1 = Digital output,
2 = Analog output,
3 = Digital input,
4 = Profibus-Remote output (Option),
5 = HT/NT changeover via digital input ,
6 = Synchronization of storage of profile 1
via digital input.
The desired function (0..6) is written into ad-
dress 002 related to the terminal 12 or address
003 related to terminal 13.
R
S
4
8
5
Current measurement
1
5
1
4
1
3
1
2
1
1
1
0
8
7
9
1
3
2
4
6
5
I / O
Measuring and
operating
voltage
Input/Output 2 (003)
Pulse output Wp (003 =0)
Digital output
(003= 1)
Analog output (003 = 2)
Digital input
(003 = 3,5)
Profibus-Remote (003 = 4)
Input/Output 1 (002)
Pulse output Wp (002 =0)
Digital output
(002 = 1)
Analog output (002 = 2)
Digital input
(002 = 3,5)
Profibus-Remote (002 = 4)
12
13
11
UMG96S
+
A simultaneous use of the various functions on
one terminal is not possible. The simultaneous
use of the functions on different terminals is
possible. Please note, that the common refer-
ence for the terminals 12 and 13 is on terminal
11(+).
combination possibilities of the inputs and out-
puts:
a) 2 Digital outputs,
b) 2 Digital inputs,
c) 2 Analog outputs,
d) 1 Digital output and 1 Analog output,
e) 1 Digital output and 1 Digital input.