Page 70
Analog output
The UMG96S with the additional PCB 1 con-
tains 2 analogue outputs. Each analogue output
can provide a current of 4-20mA. For the
operation, an external power supply 24VDC is
mandatory.
Four parameters must be programmed for one
analogue output.
Input/Output (Addr. 002,003)
Switches the analogue output to the terminals
of the UMG96S.
Measured value (Addr. 047, 052)
Indicates the measured value, which shall be
transmitted by the analogue output.
Scale starting value (Addr. 050, 054)
The scale starting value corresponds to the
measured value, for which the minimum current
of 4mA should flow.
Scale end value (Addr. 048, 053)
The scale end value corresponds to the meas-
ured value, for which the maximum current of 20
mA should flow.
UMG96S
12
13
11
R
J
1
1
S
le
e
v
e
14
15
TXD
GND
RXD
A
B
Input/Output 2 (003)
Pulse output Wp (003 =0)
Digital output
(003 = 1)
Analog output (003 = 2)
Digital input
(003 = 3,5)
Profibus-Remote (003 = 4)
Input/Output 1 (002)
Pulse output Wp (002 =0)
Digital output
(002 = 1)
Analog output (002 = 2)
Digital input
(002 = 3,5)
Profibus-Remote (002 = 4)
Clock with battery
Data memory
Additional PCB 1
C
o
m
p
a
ra
to
r
g
ro
u
p
1
C
o
m
p
a
ra
to
r
g
ro
u
p
2
Basic PCB
RS485 (MODBUS RTU)
Interface
RS232 (MODBUS RTU)
Interface
S
e
ri
a
l
in
te
rf
a
c
e
Analog output 2
Measured value (052)
Scale start. val., 4mA (054)
Scale end val., 20mA (053)
Analog output 1
Measured value (047)
Scale start. val., 4mA (050)
Scale end val., 20mA (048)
Summary of Contents for UMG 96S
Page 17: ...Page 17...