Page 57
Profibus profile No.2
Value
Bytes
Uln L1
2
Uln L2
2
Uln L3
2
UL1-L2
2
UL2-L3
2
UL1-L3
2
IL1
2
IL2
2
IL3
2
P1
2
P2
2
P3
2
Cos-phi L1
2
Cos-phi L2
2
Cos-phi L3
2
Frequency
2
P_sum
2
Q_sum
2
S_sum
2
Cos_phi_sum
2
I_sum in N
2
Real ener.
(Adr.416)
4
Reactive energy
4
thd_u_L1
2
thd_u_L2
2
thd_u_L3
2
tdh_i_L1
2
thd_i_L2
2
thd_i_L3
2
Sum
62Bytes
Profibus profile No.3
Value Bytes
eeprom_timer
4
Comp_timer_1
4
Comp_timer_2
4
Comp_timer_3
4
Comp_timer_4
4
Comp_timer_5
4
Comp_timer_6
4
Sum
28Bytes
Profibus profile No.4
Value
Bytes
I_mean_L1
2
I_mean_L2
2
I_mean_L3
2
P_mean_L1
2
P_mean_L2
2
P_mean_L3
2
Q_mean_L1
2
Q_mean_L2
2
Q_mean_L3
2
S_mean_L1
2
S_mean_L2
2
S_mean_L3
2
P_sum_mean
2
Q_sum_mean
2
I_sum_mean
2
S_sum_mean
2
phi_sum_mean
2
Sum
34Bytes
Profibus profile No.5
Values Bytes
P_sum
2
Q_sum
2
S_sum
2
Cos_phi_sum
2
I_sum in N
2
Real ener.
(Adr.422)
4
Real ener.
(Adr.424)
4
React.enrg.
(Adr.418)
4
Real enr.
2)(Adr.416)
4
Scheinarbeit
1)
4
Sum
30 Bytes
Profibus profile No.6
Value Bytes
ct_prim
2
ct_sec
2
vt_prim
2
vt_sec
2
Field rotation
2
eeprom_timer
4
Comp_timer_1
4
Comp_timer_2
4
Comp_timer_3
4
Comp_timer_4
4
Comp_timer_5
4
Comp_timer_6
4
Sum
38Bytes
Profibus profile No.7
Values Bytes
Real ener.
(Adr.422)
4
Real ener.
(Adr.424)
4
React.enrg.
(Adr.418)
4
eeprom_timer
4
Real enr.
2)
(Adr.416)
4
Scheinarbeit
1)
4
Sum
24Bytes
Lists "Profibus profiles", integer size
Profibus profile No.1
Value
Bytes
Q1
2
Q2
2
Q3
2
S1
2
S2
2
S3
2
Frequency
2
Uln L1
2
Uln L2
2
Uln L3
2
UL1-L2
2
UL2-L3
2
UL1-L3
2
IL1
2
IL2
2
IL3
2
P1
2
P2
2
P3
2
Cos-phi L1
2
Cos-phi L2
2
Cos-phi L3
2
thd_u_L1
2
thd_u_L2
2
thd_u_L3
2
tdh_i_L1
2
thd_i_L2
2
thd_i_L3
2
Sum
56
Bytes
Format
Integer
Float
resolution
unit
resolution
unit
Messwert
Phase
Sum
Phase
Sum
Current
1
1
mA
0,01
0,01
A
Voltage
0,1
V
0,1
V
Real power
0,1
1
W
0,1
1(x10)
W
Apperent power
0,1
1
VA
0,1
1(x10)
VA
Reactive power
0,1
1
var
0,1
1(x10)
var
Energie
1
Wh/varh
0,01(x10) kWh/kvarh
CosPhi
0,01
0,01
-kap/+ind
0,01
0,01
-kap/+ind
THD I
0,1
0,1
%
0,1
0,1
%
THD U
0,1
0,1
%
0,1
0,1
%
Frequency
0,01
0,01
Hz
0,1
0,1
Hz
1) Ab Firmeware Rel.1.09
2)
Wirkarbeit ohne Rücklaufsperre.
m
Measured values in integer format do not respect the transformer ratio. Measured
values in floating point format contain the transformer ratio. (value in the UMG 96S
display = transformer ratio PLC x solution)
In the Profibus profiles no. 33, 35, 36, 38, 43 and 47, the measured values real energy,
reactive energy, Psum, Qsum and Ssum are given reduced by a factor 10. No specific
profiles can be assembled.