Page 90
These specifications presuppose a yearly calibration and a warm up time of 10 minutes.
Used abbreviations:
rng
= of measuring range
rdg
= of measured value
1)
Measuring range with scale factor = 1, (Current transformer = 5/5A, 1/1A)
2)
Accuracy class according to DIN EN62052-11:2003, IEC62052:2003
3)
In the range of -10..18°C and 28..55°C an additional error of +-0,5‰ rng per K must be respected.
4)
The maximum indication range of real and
reactive energy depends on the transformer
ratio v = vi * vu.
vi = Currrent transformer ratio.
vu = Voltage transformer ratio.
Example:
200/5A -> vi = 40
1000/100V -> vu = 10
v = vi * vu
v = 40 *10
v = 400
1
10 100 400 v
999.999.999
210.000.000
21.000.000,0
2.100.000,00
/kvarh /kWh
Transformer ratio
Indication range
Indication range and accuracy
Quantity
Indication range
Meas. range
1)
Accuracy
3)
Voltage L-N
300V Standard version
0 .. 34kV
50 .. 300V
+-0,5% rng
150V Special version
0 .. 17kV
25 .. 150V
+-0,5% rng
Voltage L-L
300V Standard version
0 .. 60kV
87 .. 520V
+-1,0% rng
150V Special version
0 .. 30kV
40 .. 260V
+-1,0% rng
Current
0,01 .. 60,0kA
0,01 .. 6A
+-0,5% rng
Current in N
0,01 .. 180,0kA
0,01 .. 18A
+-1,5% rng
Real power, per phase
0,1W .. 99,9MW
0,1W .. 1,8kW
+-1,0% rng
Apparent power, per phase
0,1VA .. 99,9MVA
0,1VA .. 1,8kVA
+-1,0% rng
Reactive power, (Q0) per phase 0,1var .. 99,9Mvar
0,1var .. 1,8kvar
+-1,0% rng
Real power, Sum
1W .. 99,9MW
1W .. 5,4kW
+-1,0% rng
Apparent power, Sum
1VA .. 99,9MVA
1VA .. 5,4kVA
+-1,0% rng
Reactive power (Q0), Sum
1var .. 99,9Mvar
1var .. 5,4kvar
+-1,0% rng
Harmonics U, 1-15
0 .. 34kV
0,1V .. 300,0V
+-2,0% rng
Harmonics I, 1-15
0,01 .. 60,0kA
1mA .. 6000mA
+-2,0% rng
THD U , I
0,1% .. 100,0%
+-2,0% rng
cos(phi)
0,00i .. 1.00 .. 0,00k
0,00i ..1.00.. 0,00k
+- 1degree
Frequency (of voltage)
45,0 .. 65,0Hz
45,0 .. 65,0Hz
+-0,1% rdg
Reactive energy Wq, inductive
0 .. 999.999.999kvarh
4)
Class 1
2)
(../5A)
Class 2
2)
(../1A)
Real energy Wp, supply
0 .. 999.999.999kWh
4)
Class 1
2)
(../5A)
Class 2
2)
(../1A)
Operating hours counter
0 .. 999 999 999h
+-2Minutes/day
Summary of Contents for UMG 96S