29
www.janitza.de
RCM 202-AB
RCM 202-AB
29
10.2 Meaning of the status LED
Condition of LED
Meaning
Off
No power supply
Green
RCM 202-AB ready for operation.
Flashing green
RCM 202-AB is started.
Yellow
Response values are exceeded, error detected
Red or flashing red
Error, RCM 202-AB faulty.
10.3 Key functions
Key
Image
Function
Up/test
Normal operation:
Actuation
≥
3
s:
Generation of an internal test sig-
nal; the monitoring function of
RCM 202-AB is checked and
messages are generated.
Actuation
≥
3
s: no function
Menu:
Navigation in the submenus and
between the menu items
Parameterization mode: Setting the values
Down
Normal operation:
No function
Menu:
Navigation in the submenus and
between the menu items
Parameterization mode: Setting the values
Enter
Normal operation:
Calls up the menu
Menu:
Calls up the submenu and menu
items
Parameterization mode: Value transfer
10.4 Menu release
Symbol Menus release status
“Protected”
The values in the menus “1.Service”, “4.Measured value memory”“,
“9.Information” and “10.Restart” can be viewed, changed and saved.
“Released”
The values in the configuration menu can be viewed, changed and
saved.
Summary of Contents for RCM 202-AB
Page 2: ...2 RCM 202 AB www janitza de...
Page 6: ...6 RCM 202 AB www janitza de...
Page 66: ...66 RCM 202 AB www janitza de...
Page 67: ...67 www janitza de RCM 202 AB...