6 Functions
6.1
Basic functionality
The main functions of the RCM 202-AB are:
Residual current measurement via a connected current measurement trans-
former (max. 2 current measurement transformers)
Transformer connection monitoring for wire breaks or short circuit per channel
Effective value measurement (true RMS)
Parallel measured value recording
Evaluation of fault currents (residual currents) type A and B according to IEC
62020
Detection of sinusoidal residual fault currents with frequencies up to 20
kHz
(type B+)
Measured value and extreme value storage with time stamp
Parameterizable alarm threshold for alarm message per channel
Parameterizable warning threshold (e.g. prewarning) for warning message per
channel
Parameterizable delay times:
Delay time for warning and alarm messages
Reset delay time for warning and alarm messages
Operating and error messages shown on the display
Communication via Modbus (RS485 interface/Modbus RTU)
Evaluation possibility with the help of the GridVis
®
monitoring system or a dis-
play and evaluation device
6.1.1 Residual current monitoring principle
The fault currents (residual currents) flowing to ground or other paths are recorded
via the connected current measurement transformers.
For example:
Outflow-related residual currents (consumers and systems)
Stray currents in TN-S systems (PEN and N conductors)