64
RCM 202-AB
NOTE
A cable length of 10 m between the transformer and the measurement de-
vice may not be exceeded. Observe the maximum cable resistance of 2
Ohm. Recommendations:
- Single wires (0.75 to 1.5 mm²):
up to 1 m
- Twisted single wires (0.75 to 1.5 mm²)
up to 10 m
- Shielded cable (0.75 to 1.5 mm²)
up to 10 m
The following current measurement transformers can be connected to the RCM
202-AB:
Transformer type Inner win-
dow mm
Sepa-
rable
Transformation
ratio
Max. primary cur-
rent
mA
DACT20
20 - 600:1
18000
CT-AC RCM 35N
35
-
700:1
20000
CT-AC RCM 80N
80
-
700:1
20000
CT-AC RCM 110N
110
-
700:1
20000
CT-AC RCM 140N
140
-
700:1
20000
CT-AC RCM 210N
210
-
700:1
20000
CT-AC RCM
A110N
110
• 700:1
20000
CT-AC RCM
A150N
150
•
700:1
20000
CT-AC RCM
A310N
310
• 700:1
20000
KBU 23D
20 x 30
•
600:1
18000
KBU 58D
50 x 80
•
600:1
18000
KBU 812D
80 x 120
•
600:1
18000
Tab. 5:
Current measurement transformer for RCM 202-AB