12.2.5 Menu items: Alarm th. I to alarm th. I AC50
NOTE
The response values for the alarm thresholds must be set higher than the
response values for the warning thresholds.
Setting option:
Threshold values for the triggering of alarm messages
A message appears if the set value is exceeded (display, Modbus, if parameterized:
digital output 1 and/or 2).
Shown on the dis-
play
Set values/control com-
mands
Remark
Alarm th.
I
=
5.00
A
0.03
…
0.99 (steps of 0.01)
1.00
…
4.90 (steps of 0.1)
5.00
…
20.00 (steps of 1)
Total current with frequen-
cies up to 20
kHz (residual
current type B+)
Alarm
th.
I
DC
=
5.00
A
Direct current
Alarm
th.
I
AC2k
=
5.00
A
Alternating current with fre-
quencies up to 2
kHz (re-
sidual current type A)
Alarm
th.
I
AC20k
=
5.00
A
Alternating current with fre-
quencies up to 20 kHz
Alarm
th.
I
AC50
=
5.00
A
Fundamental oscillation
Alarm th.
I
2k
=
5.00
A
Total current with frequen-
cies up to 2
kHz (residual
current type B)