Issue: 01.06.2023
Page 6
•
Suction pipework should slope gently back towards the
unit to assist oil return to the compressor. A fall of
approximately 2cm per meter of pipework is
acceptable.
•
The maximum recommended pipe length is 50m.
•
Additional oil may be required if piping length
exceeds 20m or multiple oil traps are fitted. Check the
oil level closely during commissioning and add oil, as
necessary. Add oil in small amounts.
Do not overfill
the compressor!
•
It is recommended to install Pressure Relief Valve on
the liquid receiver if there is a risk of fire incidence.
Increasing temperature will lead to pressure increase in
receiver.
•
No valves and detachable joints shall be in areas
accessible to the public except when they comply with
EN 16084.
Figure 6 Piping Layout for Outdoor Above
Indoor
Figure 7: Piping Layout for Outdoor Below
Indoor
One of the main factors affecting equipment
reliability and compressor service life is
refrigeration circuit contamination.
During installation, circuit contamination could cause by:
•
Brazing and Welding Oxides
•
Filings and Particles from de-burring pipework
•
Brazing Flux
•
Moisture & Air
Pipe Sizing
When refer
Table 6
for selecting the connecting pipe size, the total equivalent length must include elbows and other components
that would increase the equivalent length.
Table 6: Total Equivalent Length
Notes:
(1)
The pipe sizes indicated in bold are from condensing unit to ‘T’ piece.
(2)
The pipe sizes indicated in brackets
are from ‘T’ piece to each evaporator.
(3)
Pipework should be selected on the total equivalent length of run between units.
(4)
For pipe sizing on runs longer than 30m, please contact J & E Hall.
INDOOR
UNIT
OUTDOOR
UNIT
MAX. 4m
MAX. 4m
8 TO 12 m/s
U-TRAP AS SHORT AS POSSIBLE
2cm/m SLOPE,
4m/s OR MORE
SUCTION LINE
LIQUID LINE
2cm/m SLOPE, 4m/s OR MORE
MAX. TOTAL HEIGHT <10M
BULB LOCATION
U-TRAP AS
SHORT AS
POSSIBLE
INVERTED P-TRAP
OUTDOOR
UNIT
INDOOR
UNIT
INVERTED P-TRAP
SUCTION LINE
LIQUID LINE
MAX. RISE 6M
2cm/m SLOPE, 4m/s OR MORE
BULB LOCATION
Liquid
Suction
Liquid
Suction
Liquid
Suction
3/8"
3/4"
3/8"
7/8"
3/8"
7/8"
(2x 3/8")
(2x 5/8")
(2x 3/8")
(2x 5/8")
(2x 3/8")
(2x 5/8")
1/2"
7/8"
1/2"
7/8"
1/2"
7/8"
(2x 3/8")
(2x 5/8")
(2x 3/8")
(2x 5/8")
(2x 3/8")
(2x 5/8")
1/2"
7/8"
1/2"
7/8"
1/2"
1 1/8"
(2x 3/8")
(2x 3/4")
(2x 3/8")
(2x 3/4")
(2x 3/8")
(2x 3/4")
- The pipe sizes indicated in brackets are from the ' T ' piece to each evaporator.
- Pipework should be selected on the total equivalent length of run between all units.
Condensing Unit
Model
Evaporator
Models
1x JCC2-80EV
1x JCC2-80EV
2x JCC2-60EV
BSCU-40-M1/M3
10m
20m
30m
CellarPlus 90-T1/T3
BSCU-30-M1/M3
BSCU-35-M1/M3
BSCU-30-M1/M3
BSCU-35-M1/M3
CellarPlus 70-S1/S3
3/8"
7/8"
CellarPlus 70-T1/T3
2x JCC2-40EV
3/8"
7/8"
CellarPlus 80-S1/S3
1/2"
7/8"
1/2"
System
- The pipe sizes indicated in
bold
are from condensing unit to ' T ' piece.
CellarPlus 80-T1/T3
7/8"
3/4"
3/8"
7/8"
2x JCC2-50EV
Pipe Sizing: 10ºC Cellar R448A/R449A
1/2"
1x TE2-03
1x TE2-04
TEV Model
2x TE2-02
2x TE2-02
2x TE2-02
Summary of Contents for CellarPlus 70-S1/S3
Page 26: ...Issue 01 06 2023 Page 23 Figure 30 Declaration of Conformity Outdoor ...
Page 27: ...Issue 01 06 2023 Page 24 Figure 31 Declaration of Incorporation Indoor ...
Page 28: ...Issue 01 06 2023 Page 25 Figure 32 Declaration of Incorporation Outdoor ...
Page 29: ...Issue 01 06 2023 Page 26 Figure 33 EU Declaration of Conformity Outdoor ...
Page 30: ...Issue 01 06 2023 Page 27 Figure 34 EU Declaration of Incorporation Indoor ...
Page 31: ...Issue 01 06 2023 Page 28 Figure 35 EU Declaration of Incorporation Outdoor ...