Issue: 01.06.2023
Page 12
•
Note
: The Fan Motors are pre-lubricated, and factory
sealed so no maintenance is necessary.
3.
Condenser & Evaporator Coils
–
Clean and inspect at
regular intervals.
•
Check and remove the dirt and debris between the fins
using a soft brush and/or a suitable chemical coil cleaner
then rinse with clean water.
•
Check and remove any obstacles that may hinder the
airflow through the coils.
•
Repair any damage to fins and ensure any guards are
fitted correctly.
•
Do not use high pressure washers on coils
–
They
damage the fins.
4.
Controls
•
Check controller settings and operation.
•
Check calibration of temperature probe reading.
5.
Power Supply
–
Inspect at regular intervals.
•
Check the running current and voltage for the units.
•
Check the electrical wiring and tighten the if necessary.
6.
Refrigerant Charge
•
Check the refrigerant charge by ensuring that the system
is operating correctly, and the system pressures are as
expected.
•
Carry out a full leak test.
7.
Unit decommissioning and disposal
•
At the end of the system’s useful life, a suitably qualified
engineer should decommission it. The refrigerant and
compressor oil are classed as hazardous waste and as
such must be reclaimed and disposed of in the correct
manner, including completion of waste transfer
paperwork. The system components must be disposed of
or recycled as appropriate in the correct manner.
8.
Component replacement (connections tightening
torque value)
•
Refer
Table 11
for the recommended torque tightening
of all the components in outdoor unit.
Table 11: Torque Tightening
9.
Warranty
•
The warranty as provided by J & E Hall on its products
is subject to correct application, siting, and installation
procedures together with subsequent recorded
maintenance/servicing carried out in accordance with
our recommendations. Failure to do so could result in the
withdrawal of our warranty. Please go to our website
for our detailed warranty terms and conditions:
F-Gas Requirement
The equipment covered in this Technical Manual relies on
fluorinated greenhouse gases
R448A (GWP: 1387)
and
R449A (GWP: 1397)
for their functioning.
All unit models come from the factory pressurized with OFN
(Oxygen Free Nitrogen) only.
F-Gas Regulation EU 517/2014 requires leak testing is
based on the charge size in tonnes of CO
2
equivalent
specified in below table. Starting 1st January 2017, the
requirement for leak detection and maintaining system logs
changes from 3kg HFC to 5 tonnes CO2 equivalent.
Table 12: Leak Inspection Frequency
System Charge
(Tonnes CO
₂
Equivalent)
Leak Inspection Frequency
3.6 to 36 kg R448A
3.6 to 35.8 kg R449A
•
At least once every year.
(5 to < 50 TCO
2
eq)
•
At least once every 2 years if
a fixed leak detection system
is fitted.
•
𝑇𝑜 𝑐𝑎𝑙𝑐𝑢𝑙𝑎𝑡𝑒 𝑇𝐶𝑂
2
𝐸𝑞 𝑣𝑎𝑙𝑢𝑒 =
𝑅𝑒𝑓𝑟𝑖𝑔𝑒𝑟𝑎𝑛𝑡 𝐶ℎ𝑎𝑟𝑔𝑒 (𝑘𝑔𝑠) × 𝑅𝑒𝑓𝑟𝑖𝑔𝑒𝑟𝑎𝑛𝑡 𝐺𝑊𝑃
1000
A refrigerant charge label is supplied with each unit (inside
the electrical box). The total refrigerant charge for the
system and the TCO
2
Eq value must be entered on the label
with indelible ink and must be adhered in the proximity of
the product charging port. The label supplied will represent
the refrigerants approved for use with that unit.
Suction
Liquid
BSCU-30-M1
BSCU-30-M3
BSCU-35-M1
BSCU-35-M3
BSCU-40-M1
BSCU-40-M4
Graphic
Presentation
N/A
Model
Tightening Torque (Nm)
Service Valve (Cap)
Liquid Receiver
Schrader Valve;
Charging Port
M33*1.5mm
(42-47Nm)
M18*1.0mm
(25-30Nm)
M16*1.0mm
(20-25Nm)
Brazed
Connection
Plug 3/8"NPT
(18-22Nm)
7/16" - 20UNF
(14-16 Nm)
M25*1.0mm
(42-47Nm)
Summary of Contents for CellarPlus 70-S1/S3
Page 26: ...Issue 01 06 2023 Page 23 Figure 30 Declaration of Conformity Outdoor ...
Page 27: ...Issue 01 06 2023 Page 24 Figure 31 Declaration of Incorporation Indoor ...
Page 28: ...Issue 01 06 2023 Page 25 Figure 32 Declaration of Incorporation Outdoor ...
Page 29: ...Issue 01 06 2023 Page 26 Figure 33 EU Declaration of Conformity Outdoor ...
Page 30: ...Issue 01 06 2023 Page 27 Figure 34 EU Declaration of Incorporation Indoor ...
Page 31: ...Issue 01 06 2023 Page 28 Figure 35 EU Declaration of Incorporation Outdoor ...