Issue: 01.06.2023
Page 14
FAULT
POSSIBLE CAUSE
CHECK
SOLUTION
Loose / broken wiring
connection
Make sure all electrical connections are
sound
Compressor is
noisy
Vibration
Rubber feet mountings worn or
bolts are loose/missing
Replace mountings and tighten/replace
bolts as necessary
Liquid refrigerant
Does compressor 'knock' when
starting up or running? Liquid
refrigerant may be present in
oil and compression chambers
Identify cause of liquid return to
compressor and rectify
Overloaded
Are suction and discharge
pressures too high? There may
be too much load on the
compressor.
Identify cause of increased load and
rectify
High discharge pressure
Blocked condenser / faulty
condenser fan
Check and rectify
Refrigerant overcharge
Check and rectify
Non-condensable in system
Reclaim refrigerant, evacuate &
recharge
Internal wear / damage
Noise is always present even if
all operating conditions are
OK?
Replace compressor
Compressor
body too hot
System load too high
Are suction and discharge
pressures high?
Reduce load at evaporator
High discharge pressure
Blocked condenser / faulty
condenser fan / airflow around
unit restricted
Check and rectify
Lack of compressor
cooling
Suction superheat too high
Check refrigerant charge is correct
Too much heat load at evaporator -
reduce
Are refrigerant lines correctly
insulated?
Compressor starting too
frequently
Refer section above '
Compressor starts and stops
too quickly'
Refer section above ' Compressor starts
and stops too quickly'
Discharge gas bleeding
into suction side
Does suction pressure rise
abnormally quickly when
compressor stops
Compressor valves may be damaged -
replace compressor
CONDENSER FAN
Condenser fan
not running
Power supply
See compressor will not start
section
See compressor will not start section
Compressor contactor not
pulled in
See compressor will not start
section
See compressor will not start section
Compressor contactor
pulled in
Is voltage being switched
across contactor? (Terminals L1
& T1)
If yes - check voltage to fan motor. If
correct voltage present at motor - fan
faulty. Replace fan motor
If no. Replace faulty contactor
Fan being controlled by
Fan Speed Controller (if
fitted)
Is system operating pressure
below FSC setting?
If yes - all OK (check fan operates
when pressure rises)
Fan capacitor fault
Check visual condition of
capacitor and check uF reading
with capacitor meter.
Replace capacitor as required
Motor fault
If FSC fitted - bypass FSC to
test motor. If motor still does
not run - motor is faulty
Replace fan motor
Condenser fan
runs but only
slowly
Fan capacitor or motor
fault
See above
See above
Is fan being controlled
by a FSC?
Adjust FSC setting - does fan
speed up?
If yes - all OK
FSC faulty
If fan runs slowly even after
adjusting FSC with head
pressure rising - FSC may be
faulty
Replace FSC
INDOOR UNIT
Power supply
Is power switched on?
If not - switch on
Summary of Contents for CellarPlus 70-S1/S3
Page 26: ...Issue 01 06 2023 Page 23 Figure 30 Declaration of Conformity Outdoor ...
Page 27: ...Issue 01 06 2023 Page 24 Figure 31 Declaration of Incorporation Indoor ...
Page 28: ...Issue 01 06 2023 Page 25 Figure 32 Declaration of Incorporation Outdoor ...
Page 29: ...Issue 01 06 2023 Page 26 Figure 33 EU Declaration of Conformity Outdoor ...
Page 30: ...Issue 01 06 2023 Page 27 Figure 34 EU Declaration of Incorporation Indoor ...
Page 31: ...Issue 01 06 2023 Page 28 Figure 35 EU Declaration of Incorporation Outdoor ...