background image

Issue: 01.06.2023 

 

 

Page 10  

 

Ensure that the power supply corresponds to the unit and 
that the power supply is stable. 

 

Connect power supply according to the present norm 
and legal requirement. Ensure that the unit is properly 
connected to the ground.  

 

Access to the electrical terminals and components on the 
indoor unit is via the removable cover plate on the front 
of the unit. Removal of the cover plate gives access to 
the contactor, the terminal block as well as the electronic 
controller and rocker switch connections. 

 

To gain access to the electrical box on the outdoor unit, 
remove  the  screws  of  the  panel  located  on  the  right-
hand  side  of  the  unit  and  remove  the  panel.  The 
electrical box is located behind the panel.  

 

3phase scroll compressor: 

incoming

 

live wires need 

correctly terminated at 

condensing unit’s terminal 

block

 for the compressor to rotate in correct direction 

(compression).  

 

The outdoor unit is equipped with an overload relay to 
protect compressor from overheating. It was preset from 
factory and never set value higher than set current on 
wiring diagram.  
 
 

 

Commissioning 

 
To gain access to the electrical box on the indoor and 
outdoor unit, isolate the power supply to the outdoor unit 
and indoor unit by turning the remote motor rated circuit 
breaker to the OFF position.  
 
To access the electrical box on the outdoor unit: Loosen the 
screws from the right-side panel.   
 
To access electrical box on the indoor unit: Loosen the 
screws from the L shaped window panel.   
 

Pre startup checks 
 

Before starting the system, the following checks should be 
carried out as a minimum: 

 

Check electrical supply is correct and all connections 
are sound. 

 

All moving parts are free, and guards are fitted. 

 

Compressor oil level satisfactory. 

 

Initial settings for safety switches. 

 

Overload set correctly.  

 

All valves are in correct operating position. 

 

Initial refrigerant charge. 

 

Gauge manifold connected to both low and high sides 
of system. 

 

Before starting the system, ensure that all 
electrical connections are correctly made and 
tight, service ports are in the correct position 
and all covers and guards are fitted. 

 
 
Unit startup 
 

 

Switch on the power of the main isolator and then 
switch on the rocker switch on the front of the indoor 
unit.  

 

Set the required room temperature on the electronic 
controller (Lead controller on Twin Systems) and check 
the system parameters in the controller as required (the 

controllers are pre-programmed in the factory to the 
suggested settings). 

 

Run the system to the required temperature and  check 
system  pressures  and  temperatures,  gas  charge  and 
running currents of motors to ensure correct operation. 

 

Check  compressor  suction  superheat.  This  should  be 
between 10~20K at normal operating conditions. 

 

Final adjustment of safety switch settings. 

 

Allow  the  system  to  run  for  3 

  4  hours.  Check 

compressor oil level and top up with the correct oil type 
as  required  (RL32-3MAF).  Recheck  the  compressor  oil 
level again after 24 hours operation. 

 

Carry  out  final  leak  test  and ensure  all  panels/covers 
are fitted and screws tightened. 

 

Log  all  information  along  with  the  system  model  and 
serial numbers for future reference. 

 

Ensure that the customer / responsible person is 
provided with basic operating instructions and where 
electrical isolators are situated in case of emergency. 
 

An anti-short cycle timer is built into the 
indoor controller to prevent the compressor 
from stop/starting too quickly, which can 
result in the compressor tripping on its 
internal overload. If the overload trips, 

please allow time for it to cool down and auto reset 
before restarting. 
 

 

Compressor Operation 

 

Scroll  compressor  motors  are  designed  to  run  only  in  one 
direction.

 This is not an issue with single phase compressors as 

they  will  always  run  in  the  correct  direction.  The  correct 
rotation of a three-phase compressor motor depends on the 
connection of the three incoming phases to the unit. Correct 
rotation can be determined by a drop in suction pressure and 
a  rise  in  discharge  pressure  when  the  compressor  is 
energized. Running the compressor for a short period of time 
in  reverse  direction  will  have  no  negative  impact  but 
prolonged running in reverse direction may cause premature 
failure. 

To  reverse  the  rotation  of  a  three-phase  scroll 

compressor,  shut  off  the  incoming  power  supply  to  the  unit, 
swap connection of any two of the three incoming phases at the 
unit

’s terminal block

, reapply power to the unit and following 

compressor restart, recheck operating pressures. 
 

The condensing unit does not include phase protector. Thus, 
it is necessary to ensure correct scroll compressor rotation 
and incoming line voltage variance /-2% during 
commissioning.   

 

 

 

3 phase scroll compressors require proper phase 
sequence to secure right rotation and therefore 
compression.   

 

 

Do not use a megohmmeter nor apply power to the 
compressor while the system under vacuum as this 
may cause internal damage to the compressor.  

 

 

Never  start  the  compressor  under  vacuum  (do  not 
operate the compressor with the low-pressure cut-out 
bypassing),  as

 

this  will  cause  the  rotating  part  to 

overheat very quickly causing premature failure.  

 

Summary of Contents for CellarPlus 70-S1/S3

Page 1: ...CELLAR PLUS CELLAR COOLER RANGE ISSUE 01 06 2023 CELLAR COOLER RANGE TECHNICAL MANUAL R448A R449A ...

Page 2: ...ese individuals possess independent training that will enable them to perform their assigned tasks properly and safely It is essential that prior to performing any task on this equipment this individual shall have read and understood this document and any referenced mate rials This individual shall also be familiar with and comply with all applicable governmental standards and regulations pertaini...

Page 3: ...RESSOR OPERATION 10 DUAL PRESSURE SWITCH 11 Figure 14 Adjustment on Danfoss KP17WB 11 Figure 15 KP17WB High Pressure Reset Option 11 Table 9 Dual Pressure Switch Manufacturer Setting 11 PRESSURE SWITCH SETTINGS 11 Table 10 Working Pressure R448A R449A 11 SERVICE MAINTENANCE 11 Table 11 Torque Tightening 12 F GAS REQUIREMENT 12 Table 12 Leak Inspection Frequency 12 APPENDIX 13 Table 13 Trouble Shoo...

Page 4: ... Single or three phase scroll compressor AC axial fan with run capacitor Al Cu condenser with inner groove 10mm Adjustable dual pressure switch Filter drier and liquid sight glass Basic module control box Service valves with braze connection Acoustic panel insulation Product Range Single Evaporator Systems Cellar Plus 70 S1 S3 Cellar Plus 80 S1 S3 Twin Evaporator Systems Cellar Plus 70 T1 T3 Cella...

Page 5: ...ties are nominal duties 10 C DB 8 C WB and 32 C ambient 2 Noise levels are sound pressure levels 10m free field 3 Indoor unit air throw distance is based on final air velocity of 0 4m s For applications where Back to back installation at least 3meter pipe run with loop to damp vibration is required to avoid sound of outdoor unit transferred to indoor unit via connecting pipe Suction Liquid Inlet O...

Page 6: ...ons are suitable and provide adequate support for the weight of the units Offloading and Lifting Unit Model W x D x H mm Fixing Ctrs mm Weight kgs Unit Model W x D x H mm Fixing Ctrs Top mm Fixing Ctrs Rear mm Weight kgs BSCU 30 M1 77 BSCU 30 M3 76 BSCU 35 M1 97 BSCU 35 M3 96 BSCU 30 M1 77 BSCU 30 M3 76 BSCU 35 M1 97 BSCU 35 M3 96 BSCU 40 M1 107 BSCU 40 M3 107 CellarPlus 90 T1 T3 1351 x 530 x 864 ...

Page 7: ...onnecting the electrical supply The electrical covers and fan guards must remain always fitted Use of the units outside of the design conditions and the application for which the units were intended may be unsafe and be detrimental to the units regardless of short or long term operation Installation Unit location and Fixing Both indoor and outdoor units must be level in all directions Outdoor The ...

Page 8: ... alloys containing phosphorus such as BCuP 7 without flux for joining copper tubes Run braze without over filling to ensure there is no leakage into the tube To prevent oxidation blow oxygen free nitrogen through pipework when brazing Protect the casing of the unit when brazing connections To prevent condensation on pipe surface install insulation with a minimum wall thickness 1 2 on all suction l...

Page 9: ...ipe sizes indicated in bold are from condensing unit to T piece 2 The pipe sizes indicated in brackets are from T piece to each evaporator 3 Pipework should be selected on the total equivalent length of run between units 4 For pipe sizing on runs longer than 30m please contact J E Hall INDOOR UNIT OUTDOOR UNIT MAX 4m MAX 4m 8 TO 12 m s U TRAP AS SHORT AS POSSIBLE 2cm m SLOPE 4m s OR MORE SUCTION L...

Page 10: ...abel which is in green color fastened around the capillary of expansion valve indicates the pre fit orifice size Example Figure 8 indicates orifice size 04 Figure 8 Capillary Tube Label Refer Table 6 to change the orifice size in JCC2 80EV to match the coupled condensing unit Follow Figure 9 to install the orifice Installer is recommended to change the capillary tube label accordingly if orifice h...

Page 11: ...ng the system is safe inform relevant personnel and fit warning signs indicating high pressure testing Also use correct Personal Protection Equipment PPE as required Always pressurize the system slowly preferably in stages up to the maximum required pressure Never exceed maximum test pressures shown in Table 8 Failure to obey the limit will cause premature failure on the pressure safety device Tab...

Page 12: ...ared face of the fitting and the drip tray if so desired The accessories bag is tied to the indoor unit s fan guard and consists of instruction manual 1pcs aluminum alloy drain fitting 1 14UNF male thread 1pcs hexagon locknut and 1pcs aluminium washer To install the drain fitting firstly unscrew the drain pan from the indoor unit Locate the drain fitting into drain pan insert washer and followed w...

Page 13: ... settings Run the system to the required temperature and check system pressures and temperatures gas charge and running currents of motors to ensure correct operation Check compressor suction superheat This should be between 10 20K at normal operating conditions Final adjustment of safety switch settings Allow the system to run for 3 4 hours Check compressor oil level and top up with the correct o...

Page 14: ...exceed the compressor s high side operating pressure The high pressure switch can be set to lower values depending on the application and ambient conditions Low pressure protection The low pressure protection cut out switch protects the compressor against deep vacuum operation a potential cause of failure due to internal arcing and operating outside the compressor limits The low pressure protectio...

Page 15: ...rect application siting and installation procedures together with subsequent recorded maintenance servicing carried out in accordance with our recommendations Failure to do so could result in the withdrawal of our warranty Please go to our website for our detailed warranty terms and conditions www jehall co uk F Gas Requirement The equipment covered in this Technical Manual relies on fluorinated g...

Page 16: ...s and rectify cause Faulty compressor run capacitor Check visual condition of capacitor and check uF reading with capacitor meter Replace capacitor as required Motor windings faulty Check resistances of windings Windings that show open circuit could be due to internal overload trip Wait for reset and recheck If continually open circuit motor faulty Replace compressor Compressor seized Does compres...

Page 17: ...pressor starting too frequently Refer section above Compressor starts and stops too quickly Refer section above Compressor starts and stops too quickly Discharge gas bleeding into suction side Does suction pressure rise abnormally quickly when compressor stops Compressor valves may be damaged replace compressor CONDENSER FAN Condenser fan not running Power supply See compressor will not start sect...

Page 18: ...an as necessary Evaporator coil iced up Switch off unit and allow to defrost Checks required to determine cause of icing SYSTEM Insufficient cooling Lack of refrigerant Is sight glass flashing continuously Leak test system and top up with refrigerant Condenser coil dirty Visual check of coil condition Clean condenser coil Lack of ventilation to unit Any obstructions around unit Clear same to ensur...

Page 19: ...ure 18 Drawing Outline JCC2 80EV 505 372 489 220 425 220 745 70 865 505 745 122 MODEL JCC2 40EV DWG NR RJ7001010008691 504 370 240 504 122 546 425 240 70 826 826 904 MODEL JCC2 50 60EV DWG NR RJ7001010008692 1437 557 192 425 175 425 219 505 406 310 71 1173 505 1173 324 340 MODEL JCC2 80EV DWG NR RJ7001010013639 ...

Page 20: ...CU 35 M1 M3 Figure 21 Drawing Outline BSCU 40 M1 M3 1108 710 478 403 448 1048 649 25 DWG NR RJ7001010008693 MODEL BSCU 30 M1 3 4 Ø10 500 530 946 460 1334 1272 4 Ø10 864 38 DWG NR RJ7001010008694 MODEL BSCU 35 M1 3 864 39 1272 1351 460 500 530 946 4 Ø10 MODEL BSCU 40 M1 3 DWG NR RJ7001010013637 ...

Page 21: ...T BREAKER C1 FAN CAPACITOR M1F EVAPORATOR FAN S1S ON OFF SWITCH SFR SUGGESTED FUSE RATING Y1S SOLENOID VALVE NOTE 1 LINK WITH SOLENOID VALVE FOR PUMP DOWN MODEL C1 uF SFR A JCC2 40 50 60EV 6 0 6 0 C1 M1F 1 M CL L N CN P1 BLU BRN C L N P2 BLK E P3 5 2 4 1 C L N ROOM 1 2 3 4 6 7 8 9 BLK HOT KEY XR02CX S1S BRN BRN BLU BLU 240V PLATE WINDOW CASING Y1S INCOMING SUPPLY 220 240V 50Hz SUPPLY 2 1 GRN YLW B...

Page 22: ...Figure 25 Wiring Diagram BSCU 30 M1 BSCU 35 M1 Figure 26 Wiring Diagram BSCU 40 M1 CL L N CN P1 P2 P3 PLATE WINDOW CASING Y1S INCOMING SUPPLY 220 240V 50Hz L N PE CL L N CN P1 P2 P3 LEAD UNIT PLATE WINDOW CASING LAG UNIT TWIN CELLAR SYSTEM INDOOR UNITS WIRING CONNECTION ...

Page 23: ...Issue 01 06 2023 Page 20 Figure 27 Wiring Diagram BSCU 30 M3 BSCU 35 M3 Figure 28 Wiring Diagram BSCU 40 M3 ...

Page 24: ...eter To exit the programming mode press the SET and buttons together or wait 15 seconds without pressing a button To enter the hidden parameter menu full parameter list Enter the programming mode by pressing the SET and buttons together for 3 seconds C or F LED starts blinking Release the buttons and then press the SET and buttons for more than 7 seconds L2 will be displayed followed by the first ...

Page 25: ... the external alarm condition and its signalling With iF do it represents the delay to activate the door open alarm 0 99 minutes 5 5 LS Minimum Set Point 55 C 67 F 55 C 55 F 4 C US Maximum Set Point 99 C 210 F 99 C 99 F 16 C od Output activation delay at startup 0 99 minutes 0 0 Cy Compressor on time faulty probe Cy 0 compressor always OFF 0 99 minutes 15 5 Cn Compressor off time faulty probe Cn 0...

Page 26: ...Issue 01 06 2023 Page 23 Figure 30 Declaration of Conformity Outdoor ...

Page 27: ...Issue 01 06 2023 Page 24 Figure 31 Declaration of Incorporation Indoor ...

Page 28: ...Issue 01 06 2023 Page 25 Figure 32 Declaration of Incorporation Outdoor ...

Page 29: ...Issue 01 06 2023 Page 26 Figure 33 EU Declaration of Conformity Outdoor ...

Page 30: ...Issue 01 06 2023 Page 27 Figure 34 EU Declaration of Incorporation Indoor ...

Page 31: ...Issue 01 06 2023 Page 28 Figure 35 EU Declaration of Incorporation Outdoor ...

Page 32: ...Issue 01 06 2023 RJ0110030011426 J E Hall Limited Hansard Gate West Meadows Derby DE21 6JN England Tel 44 0 1332 253400 Fax 44 0 1332 371061 Email helpline jehall co uk www jehall com ...

Reviews: