Issue: 01.06.2023
Page 3
Table 3: Unit Dimensions and Weights
Table 4: Electrical Data and Requirements
Notes:
(1)
RRC: Rated Run Current (RRC) and power consumption of outdoor unit, rated at 10°C DB / 8°C WB and 32°C ambient.
(2)
MCC: Maximum Continuous Current; LRA: Locked Rotor Amps. Both values are for the unit compressor only.
(3)
SFR: Suggested Fuse Rating (Motor Rated for Outdoor Unit)
Table 5: Outdoor Unit Sound Spectrums
Model
1/1 Octave Sound Pressure Levels
@ 1 meter from front of the unit
Noise Levels
(10m)
Frequency
125 Hz
250 Hz
500 Hz
1 kHz
2 kHz
4 kHz
8 kHz
A (dBA)
A (dBA)
BSCU-30-M1/M3
62.1
56.7
51.3
48.2
43.1
38.3
31.3
54.1
34
BSCU-35-M1/M3
63.5
62.7
53.1
48.6
43.9
38.8
32.4
56.3
36
BSCU-40-M1/M3
61.4
61.7
58.6
55.2
51.7
48.3
43.1
60.7
41
Health and Safety
Only a qualified refrigeration engineer, who
is familiar with refrigeration systems and
components including all controls, should
perform the installation and start-up of the
system. To avoid potential injury, use care
when working around coil surfaces or sharp edges of
metal cabinets. All piping and electrical wiring should be
installed in accordance with all applicable codes,
ordinances, and local by-laws.
General Information
Before Installation
•
Ensure the units received are the correct models for the
intended application.
•
Ensure the refrigerant, voltage and maximum working
pressure are all suitable for the proposed application.
•
Check there is no damage to the units. Any damage
should be reported to the supplier immediately.
•
Check that the proposed equipment locations are
suitable and provide adequate support for the weight
of the units.
Offloading and Lifting
Unit Model
W x D x H
(mm)
Fixing Ctrs.
(mm)
Weight
(kgs)
Unit Model
W x D x H
(mm)
Fixing Ctrs.
Top (mm)
Fixing Ctrs.
Rear (mm)
Weight
(kgs)
BSCU-30-M1
77
BSCU-30-M3
76
BSCU-35-M1
97
BSCU-35-M3
96
BSCU-30-M1
77
BSCU-30-M3
76
BSCU-35-M1
97
BSCU-35-M3
96
BSCU-40-M1
107
BSCU-40-M3
107
CellarPlus 90-T1/T3
1351 x 530 x 864
946 x 500
2x JCC2-60EV 904 x 504 x 546
1108 x 478 x 649
703 x 448
745
(2x)
33
CellarPlus 80-T1/T3
1334 x 530 x 864
946 x 500
2x JCC2-50EV 904 x 504 x 546
1173 x 310
CellarPlus 70-S1/S3
1108 x 478 x 649
703 x 448
1x JCC2-80EV
1437 x 505 x 557 1173 x 324
System
Outdoor Units
Indoor Units
1437 x 505 x 557 1173 x 324 1173 x 310
63
63
2x JCC2-40EV 865 x 505 x 489
745 x 122
CellarPlus 70-T1/T3
CellarPlus 80-S1/S3
1334 x 530 x 864
946 x 500
1x JCC2-80EV
826 x 122
826
(2x)
36
826 x 122
826
(2x)
38
Unit Model
Power Supply
(V/ph/Hz)
Power
(kW)
MCC
(2)
(A)
LRA
(2)
(A)
RRC
(1)
(A)
SFR
(3)
(A)
Unit Model
Power Supply
(V/ph/Hz)
Power
(kW)
RRC
(1)
(A)
SFR
(3)
(A)
BSCU-30-M1
230/1/50
21.5
82.0
12.2
25
BSCU-30-M3
400/3/50
10.3
40.0
5.1
16
BSCU-35-M1
230/1/50
25.0
97.0
14.0
32
BSCU-35-M3
400/3/50
9.0
46.0
5.7
20
BSCU-30-M1
230/1/50
21.5
82.0
13.3
25
BSCU-30-M3
400/3/50
10.3
40.0
5.4
16
BSCU-35-M1
230/1/50
25.0
97.0
14.3
32
BSCU-35-M3
400/3/50
9.0
46.0
5.8
20
BSCU-40-M1
230/1/50
28.0
114.0
17.4
40
BSCU-40-M3
400/3/50
11.0
50.0
6.8
20
1.9
6
2x JCC2-50EV
2x JCC2-60EV
230/1/50
230/1/50
1x JCC2-80EV
1x JCC2-80EV
2x JCC2-40EV
230/1/50
2.0
6
2.0
6
2.0
6
230/1/50
Outdoor Units
Indoor Units
0.44
System
CellarPlus 70-S1/S3
CellarPlus 80-S1/S3
CellarPlus 70-T1/T3
CellarPlus 80-T1/T3
CellarPlus 90-T1/T3
2.90
3.17
3.65
0.43
0.43
0.45
0.44
2.70
3.08
230/1/50
1.9
6
Summary of Contents for CellarPlus 70-S1/S3
Page 26: ...Issue 01 06 2023 Page 23 Figure 30 Declaration of Conformity Outdoor ...
Page 27: ...Issue 01 06 2023 Page 24 Figure 31 Declaration of Incorporation Indoor ...
Page 28: ...Issue 01 06 2023 Page 25 Figure 32 Declaration of Incorporation Outdoor ...
Page 29: ...Issue 01 06 2023 Page 26 Figure 33 EU Declaration of Conformity Outdoor ...
Page 30: ...Issue 01 06 2023 Page 27 Figure 34 EU Declaration of Incorporation Indoor ...
Page 31: ...Issue 01 06 2023 Page 28 Figure 35 EU Declaration of Incorporation Outdoor ...