07610-003-61-42-U
14
STEP
ACTION
RESULT
1.
Apply power (120, 208, or 240 VAC) to the A1 & A2
terminals.
Idle state.
2.
Make control signal connection at B1. No control
signal is applied.
Remains in idle state.
3.
Apply control signal (logic high).
Relay closes (ports 15-18).
4.
Remove control signal (logic low).
Relay remains closed for 2.5 minutes.
NOTE: In Step 4, if control signal is reapplied while the relay is still closed, Step 3 will restart.
TESTING EXHAUST FAN TIMER