background image

7. Wiring of the JA-60 keypad(s)  

 

The system can be programmed and operated by JA-60E 
keypad(s). As a maximum, 5 keypads can be wired to the 
control panel. The keypads can either be wired by cables 
equipped with modular jacks to connectors K4 and K5 or by 
standard cables to terminals 1,2,3 & 4 on the main control panel 
board. The same numbered terminals (pins in the connectors) 
must be linked together. It is possible to combine arbitrary 
wiring with modular connectors and ordinary cables - see 
diagram. 

When a control panel has a JA-65R 

radio communicating 

module installed, it can also be operated and programmed via 
JA-60F wireless keypad(s) asunder this situation, a minimum of 
one JA-60E keypad should be connected to the control panel. 
With a 65R module,  the system can also be operated by 
remote controls RC-40, RC-22 & RC-60,  as well as  by a  
JA-60D wireless keypad. The control panel can have up to 8 
wireless controllers. 

It is also possible to operate and program the JA-65 system via 
a connected PC with SW ComLink. The PC can be connected 
locally with a  PC-60A or PC-60B interface cable or remotely, 
using a JA-60U modem if JA-65 module is installed. 

 

 

 

 

8. Installation of wireless items 

 

If the control panel is equipped with a JA-65R module, it can 
work with all types of JA-60 wireless items and wireless UC 
output modules (see brief overview of items in enclosed 
catalogue). 

• 

Detectors

 - one wireless JA-60 detector can be enrolled to 

each control panel zone (i.e. up to 16 detectors) 

• 

Keypads and remote controls

 - up to 8 wireless 

controllers can be enrolled to the control panel (JA-60F and 
JA-60D keypads,  RC-40, RC-22 and RC-60remote 
controls) 

• 

JA-60A

 

Wireless siren 

- only one can be enrolled to a 

control panel – position A (next JA-60A can be enrolled to 
detectors positions) 

• 

wireless output modules UC-216 and UC-222

 have 

relays, which copy the status of the control panel’s 
programmable outputs PgX and PgY. An unlimited number 
of the UC modules can be used with each system. 

 

Follow the particular wireless item manual when installing. After 
you install the item to desired location, leave it un powered and 
without its cover. The method of enrollment is described in 
section 11.1. 

 

9.   Back up battery installation 

 

there is a space for size 12V, 7Ah battery. According to the 
desired backup period a 12V back up battery from 1.3Ah to 
45Ah can be used instead. A battery larger than 7Ah must be 
installed in an external case and the case must be equipped 
with  tamper protection. 
 

The control panel 

recharges and checks the 
condition of the back up 
battery. If the system is 
powered from the battery 
for a long time and the 
battery is nearly 

 

discharged, the control 
panel will first trigger a 
technical alarm  and  it will then disconnect the battery to 
prevent damage. After the main power is on again, the battery 
will be re-connected and will automatically re-charge.  

• 

insert the battery into the control panel 

• 

connect the battery cables (red +, black - ) 

 

Warning - do not make any short connection of the battery 
terminals! 

 

 

10. First powering of the control panel 

 

• 

Check that all cables are connected correctly  

• 

Switch on the AC power  

• 

The JA-60E keypad will display a "P", confirming that 
the system is in the programming mode (for system 
setting, enrollment of wireless items and for testing). 

• 

If the JA-60F keypad is used, see 11.1 how to enroll it 

 

Note:  if „P“ is not displayed, the control panel is not in the factory 
default setting. Perform a Factory default reset. (See section  13). 

 

11. Control panel programming 

 

Functions of the system can be customized. The most 
convenient programming method is via a connected PC using  
the Comlink software (see 14). Programming can also be 
performed by entering  programming sequences from the 
system keypad while in the programming mode:  

• 

If the control panel is not in the programming mode, 
open it (entering 

F 0 SC

 - SC = Service Code, factory 

default SC=6060) – The programming mode will be 
indicated by a „P“ on the LED display. This mode can 
only be entered when the panel is disarmed. In this 
mode, no alarm can be triggered. Detectors and other 
accessories can be enrolled, the system parameters 
can be set up and  the system can be tested.  

• 

The parameters of the control panel can be set by 
entering programming sequences from the keypad. Any 
unfinished programming sequence can be terminated 
by pressing the 

N

 key. 

• 

To exit the programming mode, press the N 

key („P“ 

will turn off). If any fault is indicated when you try to exit 
the programming mode, the control panel will inform 
you of the problem (see programming sequence 39x for 
more details). 

 

For battery back up time calculation 
use the following stand-by 
consumption rates:  

module JA-65R 

20mA 

module JA-65X 

12mA 

module JA-65H 

15mA 

main b. JA-65K 

10mA 

keypad JA-60E 

25mA 

Module JA-60GSM 

50 mA

Summary of Contents for MAESTRO JA-65

Page 1: ...JA 65 MAESTRO Alarm system installation manual...

Page 2: ......

Page 3: ...audible indication 12 11 19 Arming and disarming chirps with hard wired siren 12 11 20 Siren alarm in Disarm Partial arming 12 11 21 Wireless siren alarm 12 11 22 Indication of system problems when a...

Page 4: ...ireless output modules Hard wired input module JA 65H has 8 input loops with programmable triggering NC balanced or double balanced and programmable reactions Up to two JA 65H hard wired input modules...

Page 5: ...e should be connected to the metal case Instructions use flexible 2 core size from 0 75 to 1 5 mm 2 double insulated power cord The system should not share a fuse 10 A max with any other household ite...

Page 6: ...nal siren output In the normal mode it has the U terminal voltage In the alarm mode it has a GND terminal potential Connect an ordinary external siren to U and SIR terminals max load 0 7 A A back up s...

Page 7: ...ed backup period a 12V back up battery from 1 3Ah to 45Ah can be used instead A battery larger than 7Ah must be installed in an external case and the case must be equipped with tamper protection The c...

Page 8: ...module only No code requested effects F4 F8 F9 30x 301 YES 300 NO YES Partial Home arming enabled 31x 311 YES 310 NO YES Siren alarm enabled 32x 321 YES 320 NO YES Exit delay audible indication enabl...

Page 9: ...its enrollment signal The siren will send the signal only if it has no current communication with any other control panel This protects you from enrolling your neighbor s siren Enrollment is complete...

Page 10: ...ice message and telephone numbers of the built in dialer If the changes are enabled then programming sequences for number programming voice message recording and dialer testing are accessible in the U...

Page 11: ...panel was enrolled to position c3 scroll to this position in the enrolling mode and holding key 2 will erase the master control panel as a controller 11 12 Enrollment of the control panel to a UC 2xx...

Page 12: ...s after arming if any component of the system is not ready for arming Cause of the problem for example permanently triggered detector lost communication etc will remain displayed on the keypad If the...

Page 13: ...en to enter the programming mode SC 6060 MC 1234 must be set F0 6060 1234 Factory default setting disabled Note it has no influence on the user mode entering F0 MC 11 30 Addressing of wireless detecto...

Page 14: ...ed wireless controller or siren signal receiving will be similarly indicated Some detectors JA 60P JA 60N JA 60B etc have an extra testing mode which is usually activated for 5 minutes after the detec...

Page 15: ...amples There is a comprehensive help file in the Comlink program virtual control panel access complete events list item testing window RF signal oscilloscope programming dialogs map of the system show...

Page 16: ...distributor for advice local hot line number 17 Possibilities to extend the system The JA 65 alarm system is a kit which can be tailor configured according to the size of the house or the needs of th...

Page 17: ...e outputs PgX PgY Chime Fire Arm Panic Alarm Door Home AC failure Phone siren output 12 V 0 7 A Wireless outputs module 65R transmits signals for siren and PgX PgY data for UC 2xx receivers Events mem...

Reviews: