background image

Alarm system JA-65 MAESTRO 

- 14 - 

MFM53003 

where:  

n

 

instruction number from 0 to 9  

a

  

action (see the actions' table) 

hh

  

hours (from 00 to 23) 

mm

  

minutes (from 00 to 59) 

 

Notes: 

• 

If any automatic action is selected, it will be preformed 

everyday in the programmed time, following the internal 
control panel clock (see 11.36.). 

• 

The automatic arming and disarming can be overridden 

manually anytime (by an user code or a remote control) 

• 

If the control panel is in the requested arming mode before 

the action time, performance of the programmed action will 
not change the arming 

 

Example: to program an automatic complete arming of the 
system at 21:15 everyday enter: 64 0 1 21 15  

Factory default setting: all instructions are set for no action 

 

11.34. New service code setting 

 

sequence:  5 nSC nSC 

The Service Code can be used to enter the programming mode. 
A new Service Code must be entered twice in the sequence to 
avoid an error. To change the code enter: 

5 nSC nSC 

where  

nSC

  

is your new Service Code (four digits) 

Example: to change service code to 1276 enter: 5 1276 1276 

Factory default setting:

 service code is 6060 

 

 

11.35. User Mode entering  

 

Sequence:  6 9 9 9 

 

This sequence is used to switch from the Service Mode to the User 
Mode, where you can set zones´ bypass (see User´s manual). You 
can exit the User Mode by pressing the “N” button. The bypassed 
zones will remain active after the leaving the User Mode.

  

 

11.36. Real time and date setting 

 

sequence:  4 hh mm dd MM YY 

The control panel has a built in real time clock. All events are 
stored to the event memory including the time of the event. The 
clock should be set after the installation is completed. Time 
Setting: 

4 hh mm dd MM YY 

 

where 

hh = hours 

(24 hr. cycle)

 

 

mm = minutes 

 

dd = day 

 

MM = month 

 

YY = year 

Example: on Jun. 30 2005 at 17:15 enter: 4 17 15 30 06 05 

After the control panel is powered, its internal clock’s default 
setting is:  00 00 01 01 00 

Note: detail control panel event history can be viewed with a 
connected PC using Comlink software. 

 

12. System testing 

 

For testing, the control panel should be in the programming mode 

- "P" indicated on the keypad (see part 11. how to enter 
programming). No alarm can be triggered in the programming mode 
and any triggering of a detector (wireless or  wired) will make a 
beep (press F to select for a loud beep by siren) and the LED 
display will show for a while which zone was triggered. An enrolled 
wireless controller or siren signal receiving will be similarly indicated.  

 

 

• 

Some detectors (JA-60P, JA-60N, JA-60B

 etc.) have an 

extra testing mode, which is usually activated for 5 minutes 
after the detector’s cover is attached (see manuals of the 
particular detectors). If the detector is in testing mode, it will 
indicate triggering locally, and it will also indicate the 
triggering on the control panel keypad. Note, that the JA-60P 
motion detector in normal mode (after 5 minutes testing 
mode) is ready to send information about next triggering 5 
minutes  after the previous triggering (this period can be 
shortened to 1 minute - see setting of the JA-60P detector). 

• 

Triggering of a detector wired

 to the H module is indicated 

at the control panel keypad for about 2 seconds after the 
triggering. It means, that if a detector is permanently triggered 
for a longer period, it will not be indicated. If a double 
balanced input loop (2x 10k) is used, then the control panel 
distinguishes triggering of the detector from its tampering. 

• 

The best way of testing

 is via a connected PC using  the 

Comlink software (see section 14). In the service events 
window you will get a chronological record of all performed 
tests, including zones setting, quality of communication etc.  

 

The system can also be tested by a user in the user mode 
(confirmed by a “U”). The user mode is accessible with the 
Master code. To open the user mode enter F 0 MC (= Master 
Code) when the control panel is disarmed.  

 

13. Control panel factory default reset 

 

If you forgot the control panel codes or you have a control panel 
which is currently not under factory default setting, perform the 
following procedure: 

 

• 

disconnect the power and the backup battery of the 
control panel and wait for 10 sec. 

• 

connect the RESET jumper N. K11 on the main board  

• 

control panel TAMPER must be open 

• 

reconnect the power, "-" will be displayed on the 
keypad 

• 

within 1 minute disconnect the RESET jumper 

• 

Disconnect the jumper (if you haven’t done it before) 

• 

reset is confirmed with "P" (panel is in programming 
mode) 

Note:

 this procedure resets the factory default settings (see part 

11.). The Master code will be 1234, Service code 6060 and all 
user codes, wireless detectors & controllers will be forgotten. All 
telephone numbers for voice message and Pager dialing will be 
erased in the 65X communicator. The reset will not erase event 
memory and information about the reset will be recorded there. 

Warning:

 if the Master code is forgotten when reset is disabled 

(with sequence 280), the control panel reset will be possible only 
by the manufacturer.

 

Summary of Contents for MAESTRO JA-65

Page 1: ...JA 65 MAESTRO Alarm system installation manual...

Page 2: ......

Page 3: ...audible indication 12 11 19 Arming and disarming chirps with hard wired siren 12 11 20 Siren alarm in Disarm Partial arming 12 11 21 Wireless siren alarm 12 11 22 Indication of system problems when a...

Page 4: ...ireless output modules Hard wired input module JA 65H has 8 input loops with programmable triggering NC balanced or double balanced and programmable reactions Up to two JA 65H hard wired input modules...

Page 5: ...e should be connected to the metal case Instructions use flexible 2 core size from 0 75 to 1 5 mm 2 double insulated power cord The system should not share a fuse 10 A max with any other household ite...

Page 6: ...nal siren output In the normal mode it has the U terminal voltage In the alarm mode it has a GND terminal potential Connect an ordinary external siren to U and SIR terminals max load 0 7 A A back up s...

Page 7: ...ed backup period a 12V back up battery from 1 3Ah to 45Ah can be used instead A battery larger than 7Ah must be installed in an external case and the case must be equipped with tamper protection The c...

Page 8: ...module only No code requested effects F4 F8 F9 30x 301 YES 300 NO YES Partial Home arming enabled 31x 311 YES 310 NO YES Siren alarm enabled 32x 321 YES 320 NO YES Exit delay audible indication enabl...

Page 9: ...its enrollment signal The siren will send the signal only if it has no current communication with any other control panel This protects you from enrolling your neighbor s siren Enrollment is complete...

Page 10: ...ice message and telephone numbers of the built in dialer If the changes are enabled then programming sequences for number programming voice message recording and dialer testing are accessible in the U...

Page 11: ...panel was enrolled to position c3 scroll to this position in the enrolling mode and holding key 2 will erase the master control panel as a controller 11 12 Enrollment of the control panel to a UC 2xx...

Page 12: ...s after arming if any component of the system is not ready for arming Cause of the problem for example permanently triggered detector lost communication etc will remain displayed on the keypad If the...

Page 13: ...en to enter the programming mode SC 6060 MC 1234 must be set F0 6060 1234 Factory default setting disabled Note it has no influence on the user mode entering F0 MC 11 30 Addressing of wireless detecto...

Page 14: ...ed wireless controller or siren signal receiving will be similarly indicated Some detectors JA 60P JA 60N JA 60B etc have an extra testing mode which is usually activated for 5 minutes after the detec...

Page 15: ...amples There is a comprehensive help file in the Comlink program virtual control panel access complete events list item testing window RF signal oscilloscope programming dialogs map of the system show...

Page 16: ...distributor for advice local hot line number 17 Possibilities to extend the system The JA 65 alarm system is a kit which can be tailor configured according to the size of the house or the needs of th...

Page 17: ...e outputs PgX PgY Chime Fire Arm Panic Alarm Door Home AC failure Phone siren output 12 V 0 7 A Wireless outputs module 65R transmits signals for siren and PgX PgY data for UC 2xx receivers Events mem...

Reviews: