background image

Alarm system JA-65 MAESTRO 

- 13 - 

MFM53003 

actions' table 

no splitting 

split system 

no action 

no action 

arm all 

arm all 

2 disarm  disarm 

all 

partial arming

arm A 

partial arming

arm B 

5 disarm  disarm 

6 disarm  disarm 

Options:  

6 9 2 0

  

test 

disable

  

6 9 2 1

  

test 

enable

 

Factory default setting: test disabled

 

 

11.26 Audible panic alarm 

 

sequence:  693 x    

For special cases it is possible to set the audible panic alarm.      

Options:  

 

6 9 3 0

 

 audible panic alarm 

disabled

 

6 9 3 1

 

 audible panic alarm 

enabled

 

Factory default setting: disabled 

 

11.27. Next delay wireless detectors 

sequence:  694x 

 

All wireless detectors set to instant zone mode (see relevant 

detector manuals) can be programmed as next delay detectors 
which will not trigger the alarm during the exit and entry delays. 

 

Options: 

6 9 4 0  

Next delay

 disabled 

6 9 4 1 

Next delay

 enabled  

 

Factory default setting: Next delay disabled 

 

Notes:  

• 

This programming sequence concerns only wireless 
detectors. For hard-wired detectors’ setting see 11.2. 

• 

Next delay wireless detectors provide an exit/entrance 
delay only if at the moment of their triggering any one 
delayed detector has already been activated. If no 
delayed detector was triggered before the next delayed 
one, the triggering will cause an instant alarm. 

 

11.28. Communication loss alarm                                            

sequence:  696x  

  

If the regular communication check function is enabled (see 11.9) it 
is possible to determine if either an alarm will be triggered or a fault 
indication will be generated when communication with the detectors 
is lost and the control panel is armed. 

 

Options:  

6 9 6 1 

Communication loss causes

 an alarm    

6 9 6 0

 

Communication loss causes 

fault indication

  

 

Factory default setting: Communication loss causes an alarm   

 

Note:

 if the control panel is disarmed then in the case of lost 

communication the fault will be indicated regardless of this setting 

 

11.29. Entering the programming mode by SC+MC/UC 

sequence:  697 x    

If it is enabled then Master code or User code must follow the 

Service code in order to enter programming mode.  

Options:  

6 9 7 0

 

MC/UC must follow SC to open programming 
mode 

disabled

 

6 9 7 1

 

MC/UC must follow SC to open programming 
mode 

enabled

 

Example: If it is enabled then to enter the programming mode 

(SC 6060/ MC 1234) must be set: F0 6060 1234  

Factory default setting: disabled 

Note: it has no influence on the user mode entering (F0 MC) 

 

11.30. Addressing of wireless detectors to sections      

sequence:  61 nns 

If the control panel is split (see 11.23.) and is equipped with a 

65R module, the wireless detectors can be addressed to 
sections by entering: 

61 nns 

where:  

nn

 = wireless detector zone number: from 01 to 16 

s

 = section: 1 = A,  2 = B,  3 = C (common section - it is 

armed only when both A and B are armed). If the 
control panel is not split, and s=2 (or s=3) is 
selected, this detector will be bypassed while 
partial arming. 

Example: to address wireless detector zone number 3 to 
section A enter: 61 031 

Factory default setting: detectors 1 - 10 are addressed to A, 

detectors 11 - 16 are addressed to B 

 

11.31. Addressing of the user codes to sections 

sequence:  62 nns 

If the control panel is split (see 11.23.), the user codes can be 

addressed to sections A or B by entering: 

62 nns  

where:  

nn

  

user code number: from 01 to 14 

s

  

section: 1 = A, 2 = B

 

Notes: 

• 

If the control panel is not split, this setting has no effect.   

• 

Master code (MC) can not be addressed. If the system is 

split, the use of MC will arm all sections if no section is 
armed or it will disarm all sections if any is armed. If you 
want to operate only section A with master code, enter F1 
MC and F2 MC for section B.

   

 

Example: to address user code number 4 to section A enter: 62 04 1 

Factory default setting: all user codes (01 - 14) are addressed 
to section A  

 

11.32. Addressing of wireless controllers to sections 

sequence:  63 nns 

If the control panel is split (see 11.23.) and is equipped with a 

65R module, the wireless controllers (RC-40, RC-22 and 

 

JA-60D) can be addressed to A or B section by entering: 

63 nns 

where:  

nn

  

number of the enrolled controller from 01 to 08 (c1 
to c8) 

s

  

section: 1 = A, 2 = B  

 

Notes: 

• 

If the control panel is not split, this setting has no effect  

• 

For the JA-60F keypad this setting has no effect (its user 

codes are determined by 62nns setting) 

Example: to address controller number 5 to section A enter: 63 051 

Factory default setting:

 all wireless controllers are addressed 

to section A  

 

11.33. Automatic arming / disarming setting 

sequence:  64 nahhmm 

 
The control panel can 
automatically arm and 
disarm for a requested 
period of a day. Up to ten 
instructions (time & 
action) can be 
programmed in the 
period of one day by 
entering:  
64 nahhmm

 

Summary of Contents for MAESTRO JA-65

Page 1: ...JA 65 MAESTRO Alarm system installation manual...

Page 2: ......

Page 3: ...audible indication 12 11 19 Arming and disarming chirps with hard wired siren 12 11 20 Siren alarm in Disarm Partial arming 12 11 21 Wireless siren alarm 12 11 22 Indication of system problems when a...

Page 4: ...ireless output modules Hard wired input module JA 65H has 8 input loops with programmable triggering NC balanced or double balanced and programmable reactions Up to two JA 65H hard wired input modules...

Page 5: ...e should be connected to the metal case Instructions use flexible 2 core size from 0 75 to 1 5 mm 2 double insulated power cord The system should not share a fuse 10 A max with any other household ite...

Page 6: ...nal siren output In the normal mode it has the U terminal voltage In the alarm mode it has a GND terminal potential Connect an ordinary external siren to U and SIR terminals max load 0 7 A A back up s...

Page 7: ...ed backup period a 12V back up battery from 1 3Ah to 45Ah can be used instead A battery larger than 7Ah must be installed in an external case and the case must be equipped with tamper protection The c...

Page 8: ...module only No code requested effects F4 F8 F9 30x 301 YES 300 NO YES Partial Home arming enabled 31x 311 YES 310 NO YES Siren alarm enabled 32x 321 YES 320 NO YES Exit delay audible indication enabl...

Page 9: ...its enrollment signal The siren will send the signal only if it has no current communication with any other control panel This protects you from enrolling your neighbor s siren Enrollment is complete...

Page 10: ...ice message and telephone numbers of the built in dialer If the changes are enabled then programming sequences for number programming voice message recording and dialer testing are accessible in the U...

Page 11: ...panel was enrolled to position c3 scroll to this position in the enrolling mode and holding key 2 will erase the master control panel as a controller 11 12 Enrollment of the control panel to a UC 2xx...

Page 12: ...s after arming if any component of the system is not ready for arming Cause of the problem for example permanently triggered detector lost communication etc will remain displayed on the keypad If the...

Page 13: ...en to enter the programming mode SC 6060 MC 1234 must be set F0 6060 1234 Factory default setting disabled Note it has no influence on the user mode entering F0 MC 11 30 Addressing of wireless detecto...

Page 14: ...ed wireless controller or siren signal receiving will be similarly indicated Some detectors JA 60P JA 60N JA 60B etc have an extra testing mode which is usually activated for 5 minutes after the detec...

Page 15: ...amples There is a comprehensive help file in the Comlink program virtual control panel access complete events list item testing window RF signal oscilloscope programming dialogs map of the system show...

Page 16: ...distributor for advice local hot line number 17 Possibilities to extend the system The JA 65 alarm system is a kit which can be tailor configured according to the size of the house or the needs of th...

Page 17: ...e outputs PgX PgY Chime Fire Arm Panic Alarm Door Home AC failure Phone siren output 12 V 0 7 A Wireless outputs module 65R transmits signals for siren and PgX PgY data for UC 2xx receivers Events mem...

Reviews: