Alarm system JA-65 MAESTRO 

- 10 - 

MFM53003 

 

11.4. Entrance delay   

sequence:  2 1 x 

To change duration of the entrance delay enter: 

21x 

 (where 

x

 

represents time in seconds x10). The delay can be selected 
from 10 to 90 seconds. 

Example: To select entrance delay duration of 40 seconds, enter 
214  

Factory default setting: 30 seconds 

 

11.5. Alarm duration 

sequence:  2 2 x 

The alarm duration can be selected from 1 to 8 minutes (or 10 
seconds or 15 minutes) entering 

22x

 (where 

x

 represents time in 

minutes, for x=0 the duration will be 10 seconds, for x=9 the 
duration will be 15 minutes). 

Example: to select an alarm duration of 5 minutes, enter 225 

Factory default setting: 4 minutes 

 

 

11.6. PgX and PgY output functions   

sequences:  2 3 x  &   2 4 x 

The control panel outputs 
PgX and PgY can have 
different functions, 
depending on parameter 

x

 

in the corresponding 
sequence: 

2 3 x

 – determines 

triggering of  

PgX

 

2 4 x

 – determines 

triggering of  

PgY 

where x

  represents the following functions (non split 

system): 

0 Chime

 – triggered during the entrance delay (pre-

alarm output) 

1 Fire

 – triggered by a fire alarm (by a smoke or a 

gas detector)  

2 Arm

 – activated when the control panel is armed 

(complete & partial arming) 

3 Panic

 – activated when a silent panic alarm is 

triggered  

4 Alarm

 – triggered by any audible alarm (except 

panic alarm)  

5 Door 

– activated for 5sec. after 

 (F3)  

entering (electric door lock opening) 

6 Home 

– activated when the control panel is 

partially armed (Home arming)  

No AC 

– triggered by an AC power failure  

Phone/F8 

– output can be operated 

remotely by phone

 or 

by SMS (if this feature is supported by installed 
communicator) or locally 

from the keypad

 by F81 

(ON) and F80 (OFF).  If a code is requested to 
operate the system  then the F8x instruction 
should be followed by a valid user code. 

Example: the PgX will work as a Panic output when 233 

is entered, PgY as Door output when 245 is entered. 

Factory default setting: PgX=Chime, PgY=Arm 

Note: the control panel also wirelessly transmits the PgX and 
PgY signals. Wireless output modules UC-216 and UC-222 can 
be used to receive the signals (see 11.12). The function of the 
UC module output relays is determined by the 23x and 24x 
setting. 

 

11.7. Recorded message and phone number editing in 
the user mode      

 

sequence:  2 5 x 

The 

U

ser mode, which is accessible with F 0 “Master Code”, is for 

bypass setting, system testing and battery replacement. This 
setting enables the user to change the voice message and 
telephone numbers of the built in dialer. If the changes are 
enabled, then programming sequences for number programming, 
voice message recording and dialer testing are accessible in the 

U

ser mode. These settings have effect only when the control 

panel has a 65X communicator module.  

options: 

2 5 1

 changes 

enabled

 

2 5 0

 changes 

disabled

 (no dialer programming in the 

U

ser mode) 

Factory default setting: changes disabled 

 

11.8. Radio signal jamming testing 

 

sequence:  2 6 x 

When this function is enabled, the control panel will indicate 
trouble if the working band is jammed for more than 30 seconds. 
Jamming will trigger an alarm when the control panel is armed. 
Do not enable this testing, if the control panel does not have a 
65R radio module. 

options: 

2 6 1

 testing 

enabled

 

2 6 0

 testing 

disabled 

 

Factory default setting: disabled 

Note: in some locations the system can be repeatedly jammed 
for some period of time (near radar, TV or radio station etc.). In 
these cases the control panel can work without any problems 
because all important data is repeated, but the jamming test 
should not be enabled. The level of the signals and interference 
can be observed using the Comlink software  (see 14.) 

 

11.9. Regular communication checking 

 

sequence:  2 7 x 

The control panel will check communication regularly with all 
enrolled items (detectors, keypads, siren etc.) when this function is 
enabled. If communication is lost with any item, the control panel will 
indicate the fault of this item (when armed reaction of the system 
depends on setting 696x, see 11.28). Do not enable this checking, if 
the control panel does not have the 65R radio module. 

options: 

2 7 1

 checking 

enabled 

2 7 0

 checking 

disabled  

Factory default setting: checking disabled 

Note: in some locations with a strong radio interference (near radar, 
TV or radio station etc.) the communication can be jammed 
periodically. The control panel can detect such a strong interference 
as a temporary loss of communication with an item. Even in this 
case, the system is usually able to work without any problems, 
because all important data is repeated, but the communication 
check should not be used.  

 

11.10.  Reset enabled   

sequence:  2 8 x 

The factory default reset (see 13) can be disabled. This way no 
unauthorized future programming of the control panel will be 
possible.  

options: 

2 8 1

 reset 

enabled 

2 8 0

 reset 

disabled 

Factory default setting: reset enabled 

If the system is split: 

23x (PgX)  24x (PgY) 

Alarm A 

Alarm A 

Alarm B 

Alarm B 

Chime A 

Chime A 

Chime B 

Chime B 

Arm A 

Arm B 

Door A 

Door B 

Panic A 

Panic B 

7 FIRE 

NoAC 

8 Phone  Phone 

Summary of Contents for MAESTRO JA-65

Page 1: ...JA 65 MAESTRO Alarm system installation manual...

Page 2: ......

Page 3: ...audible indication 12 11 19 Arming and disarming chirps with hard wired siren 12 11 20 Siren alarm in Disarm Partial arming 12 11 21 Wireless siren alarm 12 11 22 Indication of system problems when a...

Page 4: ...ireless output modules Hard wired input module JA 65H has 8 input loops with programmable triggering NC balanced or double balanced and programmable reactions Up to two JA 65H hard wired input modules...

Page 5: ...e should be connected to the metal case Instructions use flexible 2 core size from 0 75 to 1 5 mm 2 double insulated power cord The system should not share a fuse 10 A max with any other household ite...

Page 6: ...nal siren output In the normal mode it has the U terminal voltage In the alarm mode it has a GND terminal potential Connect an ordinary external siren to U and SIR terminals max load 0 7 A A back up s...

Page 7: ...ed backup period a 12V back up battery from 1 3Ah to 45Ah can be used instead A battery larger than 7Ah must be installed in an external case and the case must be equipped with tamper protection The c...

Page 8: ...module only No code requested effects F4 F8 F9 30x 301 YES 300 NO YES Partial Home arming enabled 31x 311 YES 310 NO YES Siren alarm enabled 32x 321 YES 320 NO YES Exit delay audible indication enabl...

Page 9: ...its enrollment signal The siren will send the signal only if it has no current communication with any other control panel This protects you from enrolling your neighbor s siren Enrollment is complete...

Page 10: ...ice message and telephone numbers of the built in dialer If the changes are enabled then programming sequences for number programming voice message recording and dialer testing are accessible in the U...

Page 11: ...panel was enrolled to position c3 scroll to this position in the enrolling mode and holding key 2 will erase the master control panel as a controller 11 12 Enrollment of the control panel to a UC 2xx...

Page 12: ...s after arming if any component of the system is not ready for arming Cause of the problem for example permanently triggered detector lost communication etc will remain displayed on the keypad If the...

Page 13: ...en to enter the programming mode SC 6060 MC 1234 must be set F0 6060 1234 Factory default setting disabled Note it has no influence on the user mode entering F0 MC 11 30 Addressing of wireless detecto...

Page 14: ...ed wireless controller or siren signal receiving will be similarly indicated Some detectors JA 60P JA 60N JA 60B etc have an extra testing mode which is usually activated for 5 minutes after the detec...

Page 15: ...amples There is a comprehensive help file in the Comlink program virtual control panel access complete events list item testing window RF signal oscilloscope programming dialogs map of the system show...

Page 16: ...distributor for advice local hot line number 17 Possibilities to extend the system The JA 65 alarm system is a kit which can be tailor configured according to the size of the house or the needs of th...

Page 17: ...e outputs PgX PgY Chime Fire Arm Panic Alarm Door Home AC failure Phone siren output 12 V 0 7 A Wireless outputs module 65R transmits signals for siren and PgX PgY data for UC 2xx receivers Events mem...

Reviews: