background image

Installation manual: OASiS security system JA-82KRC-US   

5 / 21 

MKH51400

 

Radio module
connector

Memory socket

Digital bus conn.

Wired input conn.

Wiring plug

1A fuse for +U

Input balancing
switches

Terminals for
transformer output

 

4.  Control panel connectors and terminals 

 

Wireless-input  module  connector 

–  connects  the  JA-82R 

wireless module. 

Wired-input module connector

 – connects the JA-82C wired-

input extender. 

Digital bus connector 

– for connecting a JA-80E keypad or a 

PC running OLink software with a JA-80T interface cable. The 
same digital bus connector is present on the bottom right hand 
corner  of  the  plastic  housing.  Additionally,  the  same 
connections are available on the GND, A, B, +U terminals. 

Communicator  connector

  –  allows  the  connection  of  an 

optional communicator to the main board. 

Internal wiring connector 

– connects the internal wiring in the 

control panel housing. 

Reset

 

link

  (normally  open)  –  Used  to  reset  the  control  panel 

by  shorting  the  link  only  while  powering  up  the  control  panel. 
This  link  can  also  be  used  to  enter  control  panel  enrollment 
mode  by  briefly  shorting  the  link  while  the  control  panel  is 
powered. 

 

Terminals: 

AC 20V

  – the transformer output is connected here. 

01 

to 

04 

and 

COM 

are hard-wired inputs for the control panel

.  

  The  reactions  to  triggering  inputs  01  to  04  are  determined 

by  the  settings  of  addresses  01  to  04.  The  factory-set 
natural  reaction  for  these  hard-wired  inputs  is  a  delayed 
alarm in section C.  

  Terminals  01  to  04  use  resistors  in  connected  double 

balanced  loops  to  sense  loop  stand-by,  activation  or 
tampering as follows:  

o

  Connected  to  GND  via  a 

1  k

  resistor  = untriggered

 

input  

o

  Connected to GND via 

2 to 6 k

 = triggered input

,  

o

  Connected to GND via 

less then 700

 or more then 6 

k

 =

 tamper signal

  

o

  Stand-by  (untriggered)  input  zone  (if  any)  must  have  1

 

k

o

  Up  to  five normally-closed  door/window  contacts can be 

connected in series to enable one hard-wired input to be 
used  for  multiple  contacts  with  each  contact  having  a 
1k

 resistor in parallel (see the diagram below). 

o

  Multiple  normally-closed  tamper  contacts  should  be 

connected  in  series  without  any  parallel  resistors.  The 
number  of    tamper  contacts  is  unlimited  and  can  be 
combined  with  trigger  contacts  having  parallel  resistors 
(see the diagram below). 

o

  For wiring examples, see the below diagram. 

 

TAMPER

SIREN

ACTIVATION

TAMPER ACTIVATION

TAMPER ACTIVATION

TAMPER ACTIVATION

ACTIVATION

DOOR 1

DOOR 2

DETECTOR 1

DETECTOR 2

DETECTOR 3

Maximum of 5 detectors in one loop

 

 

  If  you  enroll  a  wireless  device  to  address  01  to  04,  the 

corresponding input terminal will be disabled. 

o

  The same applies to input terminals 05 to 14 on the JA-

80C wired-input extension module. 

  If you do not use an input terminal and you do not enroll a 

wireless  device  to  its  address,  then  the  terminal  must  be 
connected  to  the 

GND 

terminal  via  a  1

  k

 

  resistor  (the 

same is valid for the JA-80C module). 

EW

  –  external  warning  output  (max.  0.5A).  This  output  is 

grounded during an alarm. The control panel also transmits the 
external warning relay signal via radio for wireless sirens.   

IW 

–  internal  warning  (siren)  output.  This  output  is  grounded 

during  an  alarm.  A  standard  siren  can  be  wired  between 
terU and IW (

max. 0.5A

).

 

The IW output status is also 

transmitted by radio for the IW siren. 

The main difference between internal and external warning is during 
the  entrance  delay  period.  If  any  instant  detectors  are  triggered 
during the entrance delay period, e.g. a child running straight to the 
living  room,  only  an  internal  warning  will  be  triggered  and  an 
external  warning  will  only  follow  if  the  entrance  delay  has  been 
exceeded.   

PGX,  PGY 

–  are  a  pair  of  terminals  providing  programmable 

outputs.  If  an  output  is  activated  it  switches  to  GND  with  a 
maximum load of 0.1A/12V. The factory-default setting of PGX 
is  the  function  ON/OFF  which  can  be  operated  from  the 
keypad  by  the instruction 

81  / 

80  or  using  keys 

 

).  The 

factory-default function of PGY is that it will be activated if any 
section of the system is set.  The status of PG outputs is also 
transmitted by radio for AC and UC output modules. 

GND

 – common ground connection 

A,B

 – digital bus data 

+U

  –  back-up  power  supply  (10  to  14V),  1A  fuse.  Max. 

continuous  load  0.4  A  (max.  intermittent  load  1  A,  for  15 
minutes,  once  an  hour).  If  the  1A  fuse  is  blown,  the  control 
panel will indicate power supply fault. 

5.  Wired keypad connection  

The control panel can be operated and programmed by a JA-

80E  hard-wired  keypad.  It  can  be  connected  to  the  control 
panel  either  by  flat  telephone  cable  (max.  length  10  metres) 
using RJ connectors, or via twisted-pair cable (max. length 100 
metres) connected to the digital bus terminals (GND, A, B, +U). 

Summary of Contents for JA-82KRC-US

Page 1: ...OASiS security system JA 82KRC US 1 21 MKH51400 JA 82KRC US OASiS Control panel installation manual This manual is valid for control panel JA 82KRC US The control panel can be configured by a PC runn...

Page 2: ...ible alarms 13 12 21 Wireless siren alarm enabled IW and EW 13 12 22 Auto bypass user approval via the key 13 12 23 Final door detectors 13 12 24 Partial setting arming or system splitting 14 12 25 Au...

Page 3: ...01 to 50 for wireless inputs o The control panel does not allow for the simultaneous connection of both a wired and a wireless input to the same address Connecting to a wired input automatically disab...

Page 4: ...r Maintenance modes 1 2 Optional system configurations In the European Union region follow the valid standards and rules especially series EN 501 xx The Oasis control panel complies with grade 2 The c...

Page 5: ...allel resistors see the diagram below o For wiring examples see the below diagram TAMPER SIREN ACTIVATION TAMPER ACTIVATION TAMPER ACTIVATION TAMPER ACTIVATION ACTIVATION DOOR 1 DOOR 2 DETECTOR 1 DETE...

Page 6: ...control panel for 1 second e g using a screwdriver This will enter enrollment mode on the control panel 4 Install batteries into the keypad not far from the control panel 5 The keypad generates a bee...

Page 7: ...nection to the control panel possibly due to excessive distance or it could be too close to the control panel closer than 2 meters is not permitted To re enroll a device first disconnect its battery T...

Page 8: ...multiple control panels in one UC or AC receiver 12 Control panel programming The most convenient way to program the system is to use a PC running OLink software The system can however also be progra...

Page 9: ...g Entrance delay beeps 35x 351 YES 350 NO YES Setting arming confirmation by wired siren chirp 36x 361 YES 360 NO NO IW terminal only Siren always sounds during audible alarms 37x 371 YES 370 NO YES N...

Page 10: ...the effect or SET A or SET AB C has the effect or SET ABC or UNSET ABC In a split system a keyfob button pair assigned to section A SET UNSET A B SET UNSET B C SET UNSET ABC 61 nn r s Code card react...

Page 11: ...alarm PG on excluding Panic Panic A PGX on Panic B PGY on 6 AC dropout PG on Fire PGX on dropout PGY on 7 ON OFF 8 2 seconds pulse The ON OFF and 2 second pulse functions can be controlled from the ke...

Page 12: ...ter code has no effect on other codes and cards Resets are recorded in the control panel memory and sent to the ARC if used Alarm Receiving Centre previously called a central monitoring station 12 12...

Page 13: ...Wireless siren alarm enabled IW and EW This setting is for enabling and disabling wireless sirens in the system 3 8 1 wireless sirens enabled 3 8 0 wireless sirens disabled Note This setting has no e...

Page 14: ...nset immediately after the user sets unsets the system Assigning wireless devices access codes and keyfobs to various sections of the system has no effect in this mode Partial setting is especially su...

Page 15: ...r or a JA 80V version XA64005 or higher is installed 12 32 Annual check notification This sequence enables the user and installer to be notified of the necessary time for an annual technical check 690...

Page 16: ...hard wired input terminals in the control panel or enrolled wireless devices r is the reaction index from 0 to 9 see Table 2 s is the section 1 A 2 B 3 C only has an effect if partial setting or syst...

Page 17: ...rd has a natural reaction i e r 1 then its reaction is set unset set etc the same as reaction r 9 in table 2 A code card can also have an alarm reaction designated to it similar to detectors Factory d...

Page 18: ...is stored in the non volatile memory of keypads so power disconnection will not erase any stored text Convenient text editing is possible using a PC running OLink software Besides device names keypad...

Page 19: ...codes and cards from 01 to 50 are erased If a user has both a code and a card then it is possible to program whether both a code and card must be presented to the system for system access or whether o...

Page 20: ...can be scrolled through with the A indicator showing whether a code is programmed or not and the B indicator showing whether a card is programmed or not 4 To exit this code card display mode press th...

Page 21: ...st wake it up Install an ordinary magnetic sensor to the entrance door wiring it to the keypad input so that opening the door wakes up the keypad and reports to the control panel Alternatively power t...

Reviews: