In  addition  to  controlling  the  PG  outputs  using  keys 

8  and 

9,  PG 

outputs  can  also  be  controlled  by  access  codes,  access  cards, 
keyfobs and detector signals (see 12.40 and 12.41 for details). 

 

If  a  PG  output  should  only  be  operated  by  a  valid  access  code  or 
card, then control by 

8 and 

9 should be disabled and the codes and 

cards should be programmed to control the PG outputs instead (see 
12.41). 

 

Factory default setting:

 control enabled 

 

12.28.  Permanent  alarm  status  display  for  a  set 

system 

The  below  sequence  enables  the  permanent  display  of  alarm 

status on the keypad unit, even if the system is set.  

6831

 

permanent status display enabled 

6830

 

display  time  a  maximum  of  3  minutes  if  any 
section is set (armed) 

Notes:  

 

European  legislation  requires  status  displaying  to  be  suppressed 
within  three  minutes  of  setting  (arming)  the  system,  no  matter  how 
much or little of the system is set. This feature can be used to ignore 
this requirement if appropriate. 

 

The wireless keypad can continuously display  the status if powered 
by  an  external  power  supply.  If  powered  by  internal  batteries  the 
keypad will turn off its display after 20 seconds of not being used ( in 
Service Mode the display turns off after 15 minutes of no use by the 
installer). 

 

Factory default setting:

 only 3 minutes of display time 

 

12.29.  Tamper alarm if unset 

According to EU legislation an unset (disarmed) system should 

not  audibly  sound  a  tamper  alarm  if  tampering  occurs.  If  the 
audible indication of tamper alarms is required while the system 
is  unset  (disarmed)  then  this  can  be  enabled  by  the  following 
sequence: 

6841

 

audible tamper alarm even for an unset system 

6840

 

silent tamper alarm for an unset system  

Notes:  

 

Even if tamper alarms are silent, they are still recorded in the control 
panel memory and reported to the end user by SMS, and also to the 
ARC if used. 

 

If the sequence 370 has been programmed, then tamper alarms will 
be silent if the system is unset or partially set. 

 

Factory  default  setting:

  silent  tamper  alarms  for  an  unset 

system 

12.30.  Recording PG output activation to memory 

The activation of PGX and PGY outputs can be recorded in the 

control panel’s memory (for example if the outputs are used for 
access control). This can be enabled by the following sequence:    

6851

 

enabled 

6850

 

disabled  

Factory default setting:

 recording enabled 

 

12.31.  Engineer reset 

This  is  a  special  function  requested  by  the  DD243:2004 

standard.  It  can  only  be  used  when  the  alarm  system  is 
connected  to  an  alarm-receiving  centre.  When  a  confirmed 
alarm  is  activated  the  control  panel  is  completely  blocked  –  it 
cannot be operated by any user, master or service code until an 
engineering reset is performed by an ARC code. 

6861

 

Engineer reset enabled 

6860

 

Engineer reset disabled 

 

Factory default setting:

 Engineer reset disabled 

 

Notes:  

 

To enable the confirmation of intruder alarms (requires two detectors 
to  be  triggered  in  different  zones  within  a  definite  period)  –  use 
sequence 3 2 1  

 

Reporting to ARCs must be locked by a digital code. 

 

The  keypad shows  the  text  “Eng.  reset  req’d”  and  the  system  stays 
blocked  until  the  ARC  code  is  used  via  the  communicator  (see 
manual). 

 

The feature is supported when a JA-80Y version XA61008 or higher, 
or a JA-80V version XA64005 or higher is installed. 

 

12.32.  Annual check notification 

This  sequence enables  the user  and  installer  to  be  notified  of 

the necessary time for an annual technical check: 

6900

 

notification 

disabled

 

6901

 

notification 

enabled

 

Notes:  

 

An annual technical inspection notification is displayed as text on the 
keypad  display  and  can  also  be  sent  as  an  SMS  to  the  end  user 
and/or installer and/or as a report code to an ARC, if used. 

 

Annual  technical  inspection  notification  text  disappears  on  entering 
Service Mode. 

 

When  this  notification  is  enabled,  exiting  Service  Mode  will  cause  a 
notification to occur in the next year on the first day of the month in which 
it  was  set.  (e.g.  if  you  set  the  annual  check  notification  on  the  15th 
October 2007, the notification is displayed on the 1st October 2008.) 

 

When  this  notification  is  enabled,  exiting  Service  Mode  will  cause  a 
notification  to  occur  every  twelve  months  later  (the  same  day  and 
month). 

 

If you wish to receive a notification earlier than a year later, change 
the    internal  clock  settings  to  the  day  and  month  you  prefer  before 
exiting  Service  Mode  by  entering  4hhmmDDMMYY,  and  then  re-
adjust the clock to the correct time in maintenance mode. By tricking 
the  system  this  way,  you  can  be  notified  on  the  desired  date.  (see 
12.45, entering and exiting maintenance mode does not change the 
notification date). 

 

Example

: If the date is 10 January 2007 and you wish to receive a 

notification  6  months  later  on  10  July  2007,  while  still  in  Service 
Mode    change  the  system  clock  to  10  July  2007,  i.e.  the  day  and 
month  of the  desired  notification date. Then  exit Service Mode and 
re-adjust the clock to the correct time in maintenance mode. 

 

Factory default setting:

 Annual inspection notification disabled. 

 

12.33.  Only single alarm indication    

If this function is enabled, then only one intruder alarm may be 

indicated  at  a  time.  Once  an  intruder  alarm  has  been  triggered 
and  has  still  not  ended,  then  no  more  alarms  can  be  indicated 
no  matter  how  many  more  times  triggering  occurs.  After  the 
alarm has ended, the system is then ready  to indicate the next 
single intruder alarm. 

This  is  to  limit  the  number  of  SMS  reports  sent  if  hard-wired 

PIR detectors capable of being frequently triggered are installed 
in  the  system  and  the  system  is  not  unset  (disarmed)  properly 
when someone enters the building. 

6 9 1 0

   multiple simultaneous intruder alarms allowed   

6 9 1 1

   single intruder alarm allowed only 

 

 

Note: 

Apart  from  this  limitation  in  the  number  of  simultaneous 

intruder alarms, the system also checks to see if any detector is 
triggering multiple alarms during the period in which the alarm is 
set.  Any  such  undesirable  detector  is  then 

automatically 

bypassed

 every time the system is set, if it has caused at least  

four alarms in a row

 

Factory  default  setting:

  multiple  simultaneous  intruder  alarms 

allowed 

 

Note:  A  panic  alarm  can  always  be  triggered  with  no  limits 
(except when in service and maintenance modes).

 

 

12.34.  Setting (arming) by service code 

    

Using this sequence, the installer can be authorized to set and 

unset the system by means of a valid service code. This feature 
should  only  be  enabled  with  the  explicit approval  of  the  master 
code holder (system administrator):   

 

6 9 2 0

    disabled 

6 9 2 1

    enabled

 

 

Factory default setting:

 disabled 

 

12.35.  Audible panic alarm   

If  enabled,  panic  alarms  can  be  indicated  by  internal  and 

external warning devices (sirens on IW and EW):     

6 9 3 0

   

silent 

panic alarm  

Summary of Contents for JA-82KRC-US

Page 1: ...OASiS security system JA 82KRC US 1 21 MKH51400 JA 82KRC US OASiS Control panel installation manual This manual is valid for control panel JA 82KRC US The control panel can be configured by a PC runn...

Page 2: ...ible alarms 13 12 21 Wireless siren alarm enabled IW and EW 13 12 22 Auto bypass user approval via the key 13 12 23 Final door detectors 13 12 24 Partial setting arming or system splitting 14 12 25 Au...

Page 3: ...01 to 50 for wireless inputs o The control panel does not allow for the simultaneous connection of both a wired and a wireless input to the same address Connecting to a wired input automatically disab...

Page 4: ...r Maintenance modes 1 2 Optional system configurations In the European Union region follow the valid standards and rules especially series EN 501 xx The Oasis control panel complies with grade 2 The c...

Page 5: ...allel resistors see the diagram below o For wiring examples see the below diagram TAMPER SIREN ACTIVATION TAMPER ACTIVATION TAMPER ACTIVATION TAMPER ACTIVATION ACTIVATION DOOR 1 DOOR 2 DETECTOR 1 DETE...

Page 6: ...control panel for 1 second e g using a screwdriver This will enter enrollment mode on the control panel 4 Install batteries into the keypad not far from the control panel 5 The keypad generates a bee...

Page 7: ...nection to the control panel possibly due to excessive distance or it could be too close to the control panel closer than 2 meters is not permitted To re enroll a device first disconnect its battery T...

Page 8: ...multiple control panels in one UC or AC receiver 12 Control panel programming The most convenient way to program the system is to use a PC running OLink software The system can however also be progra...

Page 9: ...g Entrance delay beeps 35x 351 YES 350 NO YES Setting arming confirmation by wired siren chirp 36x 361 YES 360 NO NO IW terminal only Siren always sounds during audible alarms 37x 371 YES 370 NO YES N...

Page 10: ...the effect or SET A or SET AB C has the effect or SET ABC or UNSET ABC In a split system a keyfob button pair assigned to section A SET UNSET A B SET UNSET B C SET UNSET ABC 61 nn r s Code card react...

Page 11: ...alarm PG on excluding Panic Panic A PGX on Panic B PGY on 6 AC dropout PG on Fire PGX on dropout PGY on 7 ON OFF 8 2 seconds pulse The ON OFF and 2 second pulse functions can be controlled from the ke...

Page 12: ...ter code has no effect on other codes and cards Resets are recorded in the control panel memory and sent to the ARC if used Alarm Receiving Centre previously called a central monitoring station 12 12...

Page 13: ...Wireless siren alarm enabled IW and EW This setting is for enabling and disabling wireless sirens in the system 3 8 1 wireless sirens enabled 3 8 0 wireless sirens disabled Note This setting has no e...

Page 14: ...nset immediately after the user sets unsets the system Assigning wireless devices access codes and keyfobs to various sections of the system has no effect in this mode Partial setting is especially su...

Page 15: ...r or a JA 80V version XA64005 or higher is installed 12 32 Annual check notification This sequence enables the user and installer to be notified of the necessary time for an annual technical check 690...

Page 16: ...hard wired input terminals in the control panel or enrolled wireless devices r is the reaction index from 0 to 9 see Table 2 s is the section 1 A 2 B 3 C only has an effect if partial setting or syst...

Page 17: ...rd has a natural reaction i e r 1 then its reaction is set unset set etc the same as reaction r 9 in table 2 A code card can also have an alarm reaction designated to it similar to detectors Factory d...

Page 18: ...is stored in the non volatile memory of keypads so power disconnection will not erase any stored text Convenient text editing is possible using a PC running OLink software Besides device names keypad...

Page 19: ...codes and cards from 01 to 50 are erased If a user has both a code and a card then it is possible to program whether both a code and card must be presented to the system for system access or whether o...

Page 20: ...can be scrolled through with the A indicator showing whether a code is programmed or not and the B indicator showing whether a card is programmed or not 4 To exit this code card display mode press th...

Page 21: ...st wake it up Install an ordinary magnetic sensor to the entrance door wiring it to the keypad input so that opening the door wakes up the keypad and reports to the control panel Alternatively power t...

Reviews: