Installation manual: OASiS security system JA-82KRC-US
16 / 21
MKH51400
6 9 3 1 audible
panic alarm
Note:
If the sequence 370 is used, panic alarms are silent if any section
of the system is unset.
Factory default setting:
silent panic alarm
12.36. Higher control-panel receiver-sensitivity
If enabled, this feature can extend the communication range
between the control panel and its wireless devices if there is no
radio frequency interference in the premises.
6 9 4 0
standard
control panel sensitivity
6 9 4 1 higher
control panel sensitivity
Note:
The sensitivity of the control panel receiver should only be
increased if there is no RF interference as the radio range would only be
reduced if interference was present.
Factory default setting:
standard control panel sensitivity
12.37. Access by code plus card
This
feature
increases
security
against
unauthorised
setting/unsetting (arming/disarming):
6950
system access by code or card
6951
system only accessed by code and card if both
are assigned to the same user position
Notes:
•
The system has up to 50 user positions (01 to 50) each capable of
having an access code and an access card assigned to it. If both a
code and a card are assigned to a user then the above sequences
(6950 and 6951) determine whether the user can use a code or a
card or whether he must present both a card and a code to gain
control over the system. If both a card and a code have to be
presented, the order in which they are done is unimportant.
•
If only a card or only a code is assigned to a user, then the above
settings have no effect on users like
this.
Factory default setting
: system operated by code or card
12.38. Audible 24 hour intruder alarm
The 24-hour intruder alarm which can be triggered whether the
system is set or not, and can also be silent or audible (IW and
EW) according to the following sequences:
6 9 6 0
silent
24-hour intruder alarm
6 9 6 1 audible
24-hour intruder alarm
Note:
If sequence 370 is programmed, the intruder alarm will be silent if
any section in the system is unset.
Factory default setting:
audible 24 hour intruder alarm
12.39. Service mode only with service code and
master code
To prevent the installer from accessing Service Mode without a
user’s permission, this feature (if enabled) makes it compulsory
for the master code (or any valid user code) to be entered
directly after entering the service code to access Service mode.
Service Mode can then be entered by keying in
∗
0 service-code
master-code(or user-code).
6 9 7 0
Only service code needed.
6 9 7 1
Service code and master code (or user code)
needed.
Factory default setting:
Only service code needed.
12.40. Device reactions and section assignment
The following sequence programs the characteristics of system
devices :
61 nn r s
where
nn
is the device address from 01 to 50 (01 to 04 or
01 to 14 can either be the hard-wired input
terminals in the control panel or enrolled wireless
devices)
r
is the reaction index from 0 to 9 – see
Table 2
s
is the section 1 = A, 2 = B, 3 = C (only has an
effect if partial setting or system splitting is used
– except for PG output control)
Guidance on assignment to sections:
Assigning keyfobs with natural reactions to sections
s
button
Unsplit
system
Partial
setting
Split
system
(or
)
set
set A
set A
1
(or
)
unset
set AB
unset A
(or
)
set
set A
set B
2
(or
)
unset
set AB
unset B
(or
)
set
set ABC
set ABC
3
(or
)
unset
unset ABC
unset ABC
•
If partial setting is programmed then detectors can be
assigned to sections: A (s=1), B (s=2) a C (s=3). The three
possible setting (arming) options are as follows:
o
A
(using the A key on the keypad, e.g. setting (arming) the
garage in the afternoon),
o
AB
(using the B key on the keypad, e.g. setting (arming)
the garage and the ground floor during the night)
o
ABC
(using the ABC key on the keypad, e.g. to set the
entire system when leaving the house).
•
In a split system, detectors can be assigned to sections: A
(s=1), B (s=2) a C (s=3). Sections A and B can be set
independently and section C is a common section which only
sets when A and B are set.
•
Partially setting and splitting a system only have an effect on
intruder detectors with instant, delayed or next-delayed
reactions. Detectors with fire, tamper, panic, and 24-hour
reactions are continuously ready to trigger an alarm no matter
which section they are assigned to or whether their section is
set or not.
•
If the selected
reaction is PG output
control then the s
parameter defines which PG output is controlled:
s=1 PGX,
s=2 PGY, s=3 PGX and PGY
.
Guidance on programming reactions:
•
The reaction selected in a detector by its internal DIP
switches is only obeyed by the control panel if the reaction
programmed in the detector’s address is a natural one (r=1).
•
Keyfobs
always enroll a pair of buttons (
+
) or (
+
).
The natural reaction of such a pair of buttons is shown in the
above table. If any other reaction is selected for a keyfob, this
reaction will only apply to the first button of the pair, i.e.
or
, or to double buttons
+
or
+
. The
(
)
button has no effect (can still be used for controlling UC/AC
receivers).
Factory default setting:
All addresses from 01 to 50 have a
natural reaction (r=1) and are assigned to section C (s=3).
Table 2 Control panel reactions
R Reaction
Notes
0
Disabled
For temporarily disabling codes or devices
including tamper sensors
1
Natur
al
For detectors
= instant, delayed or fire
(selectable in detectors by DIP switch)
For hard-wired inputs
of the control panel or
keypad
=
delayed
Keyfobs
(or
) =set,
(or
) =unset,
both buttons = panic
Code
= set/unset (see reaction r=9)
2
Panic
Triggers a panic alarm (audible or silent, see
12.35)
3
Fire
Triggers a fire alarm
4
24 hours
Triggers an intruder alarm even if the system is
unset (audible or silent – see 12.38)
5
Next delay
Always provides an exit delay. An entrance
delay is only provided if it is triggered shortly
after a delayed detector.
6
Instant
If activated in a set (armed) section, it triggers
an intruder alarm instantly