background image

Installation manual: OASiS security system JA-82KRC-US   

20 / 21 

MKH51400

 

 

13.3.  Setting  and  unsetting  (arming/disarming) 

the system 

The system can be set and unset from a keypad, a keyfob or 

remotely  by  phone  or  the  Internet  or  from  a  PC  running  OLink 
software. 

 

To set the system from a keypad: 

  Press key ABC, A or B,  

  Enter a code (or present a card) 

  If the system is partially set (section A is set), and you wish to 

extend the proportion of the system which is set, press the B 
or ABC key. If you extend the proportion of the system which 
is  set,  then  all  delayed  or  next-delayed  detectors  in  the 
section(s) going to be set and in the section currently set, will 
provide  an  exit  delay  which  means  that  if  a  user  has  his 
system partially set (e.g. night setting) and wishes to exit the 
house by walking through the sections that are still set, he will 
not need to unset the whole system before leaving the house 
and setting the whole system. The route used by the user to 
leave the house must be covered by delayed or next-delayed 
detectors  to  make  this  possible  and  must  be  considered  at 
the system design stage. 

 

To unset the system from a keypad: 

  Enter a valid access code (or present a card). 

 

Operating the system from an outdoor keypad: 

If  the  system  is  equipped  with  a  JA-80H  outdoor  keypad  or  a 

JA-80N  external  card  reader  then  the  outdoor  device  could 
either work the same way as an indoor keypad unit or it could be 
programmed only to operate an electric door lock (known as an 
outdoor-bypass  feature),  i.e.  an  indoor  keypad  would  then  be 
used to control the alarm system. If the outdoor-bypass feature 
is enabled then: 

  Setting and unsetting the alarm system is only possible using 

a JA-80F or JA-80E indoor keypad or a keyfob. 

  Entering a valid access code or presenting a valid card to the 

outdoor  keypad  or  card  reader  will  always  only  open  the 
electric door lock. 

  If  the  system  is  set,  and  the  door  is  opened  via  the  outdoor 

keypad  or  reader,  an  entrance  delay  will  begin.  During  this 
delay the system has to be unset using an indoor keypad unit 
(or keyfob). 

 

13.4.  Maintenance Mode 

Maintenance  mode  can  be  entered  using  a  master  code  or 

master card by entering: 

0 MC 

where  MC = master code (card) – factory default 1234 

In maintenance mode it is possible to: 

  Test devices (an alarm cannot be triggered). 

  Display which code/card positions are currently occupied. 

  Bypass  individual  devices  (for  one  setting/unsetting  cycle  or 

indefinitely)  - see 13.4.2. 

  Program the real-time system clock – see 12.46. 

  Program  the  automatic  setting/unsetting  schedule  –  see 

12.43. 

  Program telephone numbers for event reports to the end user 

(see 12.6). 

 

Exit maintenance mode by pressing the

 

# key.

 

 

13.4.1. 

Displaying which user/card positions are occupied 

Which positions in the range 01 to 50 are occupied by codes or 

cards can be displayed in maintenance mode as follows: 

1.  The control panel must be in maintenance mode – if not then 

enter 

0 master code or card (factory default: 1234) while the 

system is totally unset. 

2.  Press key 

5

 (the display indicates “Codes 01: Code”), 

3.  Using  the  arrow  keys  all  user  positions  (01  to  50)  can  be 

scrolled through, with the A indicator showing whether a code 

is programmed or not, and the B indicator showing whether a 
card is programmed or not. 

4.  To exit this code/card display mode press the  

key. 

5.  To exit maintenance mode press the 

key

.

 

 

To change access codes and cards use sequence 

6 MC nn NC 

(see 13.2). 
The most convenient way to administer codes is by using a PC 
running OLink software. 

13.4.2. 

Bypassing devices 

In  maintenance  mode  it  is  possible  to  bypass  (disable) 

individual  system  devices  (permanently  or  only  for  one 
setting/unsetting cycle): 

1.  The control panel must be in maintenance mode – if it is not, 

then  enter 

0  master  code  (factory  default:  1234)  while  the 

system is totally unset. 

2. 

Press key 1, 

to display the control panel’s 

bypass menu

3.  Using  the  arrow  keys  you  can  scroll  through  all  the  devices 

able to trigger alarms

  

4. 

To bypass 

a device use key:  

2

 

to  bypass  the  device  for  one  setting/unsetting 

cycle (the 

 indicator will start flashing) 

3

 

to  permanently  bypass  a  device

 

(the 

 

indicator will light continuously) 

To cancel the bypassing of a device 

use the same button 

as was originally used for bypassing (

2

 or 

3

). Using key 

4

 will 

cancel all device bypasses in the system. 

5.  All  the  desired  bypasses  can  be  programmed  by  repeating 

step 3 and 4. 

6.  Press  the 

key  to  exit  the  bypass  menu.  Pressing 

again

 

exits maintenance mode

.

 

 

If a system with bypasses programmed is being set, then bypass 
text will be displayed on the keypad unit. 

 

13.4.3. 

Protecting a car near the system 

The  Oasis  system  can  also  protect  a  car  (cars)  parked  in  the 

proximity of the house.  

1.  If  the car has  a  built-in car alarm  then  an  RC-85 transmitter 

unit  can  be  connected  to  the  car  alarm  output  and  the 
transmitter unit can be enrolled to a free address in the Oasis 
control panel. An alarm triggered in the car can be indicated 
as an Oasis panic alarm 24 hours a day whether the system 
is set or not. Note: if the car alarm confirms setting (arming) 
by  siren  chirps  appearing  on  the  alarm  output,  then  these 
should be disabled to avoid false alarms. 

2. 

If the car has no built-in car alarm 

then JA-85P or JA-85B 

detectors  can  be  installed  in  the  car.  The  car  detectors  can 
be  assigned  to  their  own  dedicated  section  in  the  system, 
e.g.  a  split  system  where  section  A  could  be  for  the  car 
detectors,  and  section  B  for  the  house  detectors,  with  no 
detectors  assigned  to  section  C,  and  the  entry  codes/cards 
assigned to section C to access the whole system. So when 
the user enters the house he can set section A to protect the 
car, and unset section B to be able to enter the house. Radio 
communication  supervision  should  be  disabled  for  the  car 
detectors  to  avoid  fault  notifications  when  the  car  is  driven 
away from the house. 

 

14.  Operating  and  programming  the  system 

by PC 

The  Oasis  system  can  be  operated  and  programmed  locally 

using a PC running OLink software. To connect the control panel 
to  the  PC  use  a  JA-80T  interface  or  a  JA80-BT  wireless 
Bluetooth interface.  

OLink  software  can  be  used  by  installers  and  end  users.  The 

software  only  allows  access  to  features  allowed  by  the  access 
code (service or user). 

If  the  control  panel  is  equipped  with  a  suitable  communicator 

such  as  the  JA-80Y  (GSM/GPRS)  or  JA-80V  (LAN/Telephone 
line)  then  the  system  can  also  be  accessed  from  a  PC 

Summary of Contents for JA-82KRC-US

Page 1: ...OASiS security system JA 82KRC US 1 21 MKH51400 JA 82KRC US OASiS Control panel installation manual This manual is valid for control panel JA 82KRC US The control panel can be configured by a PC runn...

Page 2: ...ible alarms 13 12 21 Wireless siren alarm enabled IW and EW 13 12 22 Auto bypass user approval via the key 13 12 23 Final door detectors 13 12 24 Partial setting arming or system splitting 14 12 25 Au...

Page 3: ...01 to 50 for wireless inputs o The control panel does not allow for the simultaneous connection of both a wired and a wireless input to the same address Connecting to a wired input automatically disab...

Page 4: ...r Maintenance modes 1 2 Optional system configurations In the European Union region follow the valid standards and rules especially series EN 501 xx The Oasis control panel complies with grade 2 The c...

Page 5: ...allel resistors see the diagram below o For wiring examples see the below diagram TAMPER SIREN ACTIVATION TAMPER ACTIVATION TAMPER ACTIVATION TAMPER ACTIVATION ACTIVATION DOOR 1 DOOR 2 DETECTOR 1 DETE...

Page 6: ...control panel for 1 second e g using a screwdriver This will enter enrollment mode on the control panel 4 Install batteries into the keypad not far from the control panel 5 The keypad generates a bee...

Page 7: ...nection to the control panel possibly due to excessive distance or it could be too close to the control panel closer than 2 meters is not permitted To re enroll a device first disconnect its battery T...

Page 8: ...multiple control panels in one UC or AC receiver 12 Control panel programming The most convenient way to program the system is to use a PC running OLink software The system can however also be progra...

Page 9: ...g Entrance delay beeps 35x 351 YES 350 NO YES Setting arming confirmation by wired siren chirp 36x 361 YES 360 NO NO IW terminal only Siren always sounds during audible alarms 37x 371 YES 370 NO YES N...

Page 10: ...the effect or SET A or SET AB C has the effect or SET ABC or UNSET ABC In a split system a keyfob button pair assigned to section A SET UNSET A B SET UNSET B C SET UNSET ABC 61 nn r s Code card react...

Page 11: ...alarm PG on excluding Panic Panic A PGX on Panic B PGY on 6 AC dropout PG on Fire PGX on dropout PGY on 7 ON OFF 8 2 seconds pulse The ON OFF and 2 second pulse functions can be controlled from the ke...

Page 12: ...ter code has no effect on other codes and cards Resets are recorded in the control panel memory and sent to the ARC if used Alarm Receiving Centre previously called a central monitoring station 12 12...

Page 13: ...Wireless siren alarm enabled IW and EW This setting is for enabling and disabling wireless sirens in the system 3 8 1 wireless sirens enabled 3 8 0 wireless sirens disabled Note This setting has no e...

Page 14: ...nset immediately after the user sets unsets the system Assigning wireless devices access codes and keyfobs to various sections of the system has no effect in this mode Partial setting is especially su...

Page 15: ...r or a JA 80V version XA64005 or higher is installed 12 32 Annual check notification This sequence enables the user and installer to be notified of the necessary time for an annual technical check 690...

Page 16: ...hard wired input terminals in the control panel or enrolled wireless devices r is the reaction index from 0 to 9 see Table 2 s is the section 1 A 2 B 3 C only has an effect if partial setting or syst...

Page 17: ...rd has a natural reaction i e r 1 then its reaction is set unset set etc the same as reaction r 9 in table 2 A code card can also have an alarm reaction designated to it similar to detectors Factory d...

Page 18: ...is stored in the non volatile memory of keypads so power disconnection will not erase any stored text Convenient text editing is possible using a PC running OLink software Besides device names keypad...

Page 19: ...codes and cards from 01 to 50 are erased If a user has both a code and a card then it is possible to program whether both a code and card must be presented to the system for system access or whether o...

Page 20: ...can be scrolled through with the A indicator showing whether a code is programmed or not and the B indicator showing whether a card is programmed or not 4 To exit this code card display mode press th...

Page 21: ...st wake it up Install an ordinary magnetic sensor to the entrance door wiring it to the keypad input so that opening the door wakes up the keypad and reports to the control panel Alternatively power t...

Reviews: