background image

Installation manual: OASiS security system JA-82KRC-US   

17 / 21 

MKH51400

 

Set 

Sets its own section of the system 

PG 
output 
control 

The value of the s parameter determines which 
PG output is controlled: s= 1= PGX,  s=2=PGY 
or s=3=PGX & PGY. To use this function the 
PG output involved has to be programmed to 
the ON/OFF or pulse functions. 
If the reaction is triggered by: 

a code (card)

 – the PG output changes its 

state (ON,OFF,ON,OFF……) or a pulsed 
switching event is generated after a valid code 
or card is used. If a code or card is 
programmed this way, it cannot be used for 
setting (arming) control. Many different codes 
can be programmed to operate PG outputs, if 
desired. 

a keyfob

 – one button in a pair is used to 

switch a PG output ON, the second one to 
switch it off or each of them generates a pulsed 
switching event.  If a keyfob is programmed this 
way, it cannot be used for setting (arming) 
control.  Each PG output can have as many 
associated keyfobs as desired. If both buttons 
of the remote control are pressed 
simultaneously, they will trigger a panic alarm 

a detector

 – the PG output copies the status of 

the detector or it generates a pulsed switching 
event when the detector is triggered. The 
detector also effects the control panel which 
responds with a natural reaction. Only one 
detector should be programmed to a PG output 
ON/OFF reaction and should not be combined 
with keyfob or keypad control as the detector 
repeats its status every 9 minutes and it would 
override the signal from the keypad or keyfob. 

Set/unset 

Toggles the system status 
SET,UNSET,SET,UNSET etc 

12.41.  Code/card reactions and section assignment

  

The following sequence programs the features of access codes 

or cards:  

62 nn r s 

where: 

nn 

is the user position from 01 to 50  

r

 

is the reaction index from 0 to 9 – see 

Table 2

 

s

 

is  the  section  1  =  A,  2  =  B,  3  =  C  (only  has  an 
effect  in  a  split  system  –  except  for  the  PG 
output control reaction). 

 

Guidance on assigning codes or cards to sections: 

 

In partial setting (arming) mode 

assigning codes or cards to 

sections  has  no  effect  (except  for  the  PG  output  control 
reaction). If anything in the system is set and a card/code is 
used,  the  system  will  then  be  unset,  and  if  all  sections  are 
unset  then  the  whole  system  will  be  set  by  a  card/code. 
Partial  setting  keys  A  and  B  on  the  keypad  can  be 
programmed to be followed by a valid access code if required 
(see 12.13). 

 

For a split system, a code assigned to section

o

 

controls section A  

o

 

B

 controls section B 

o

 

controls section A, B and C. 

  If the system is not split then the assignment of codes/cards 

to  sections  has  no  effect,  but  the  s  parameter  must  be 
entered  in  the  programming  section.  Enter  s=3  if  splitting  is 
not desired.  

 

Guidance on code/card reactions: 

  If a code/card has a natural reaction, i.e. r=1, then its reaction 

is set,unset,set etc. (the same as reaction r=9 in table 2). 

  A code/card can also have an alarm reaction designated to it, 

similar to detectors. 

 

Factory  default  setting:

  all  codes/cards  from  01  to  50  have  a 

natural reaction (set/unset) and are assigned to section C. 

 

12.42.  Enrollment by keying in production codes 

This  sequence  allow  the  enrollment  of  devices  by  keying  in 

their production codes: 

60 nn xx..x 

where: 

nn 

is the address of the device from 01 to 50  

xx...x

   is  the  production  code  of  the  device  (the  last 

eight digits of the bar code, see the label on the 
PCB inside the device) 

Notes: 

  If  the  address  nn  is  already  occupied,  the  current  device  will  be 

erased, and the new device will then be enrolled instead. 

  If a device with production code xx…x has already been enrolled  to 

another  address  in  the  past,  and  if  the  device  is  now  enrolled  to  a 
new address, then it will be moved to the new address, releasing the 
old address. 

  If  you  enter  nn  =  01  or  02,  the  device  will  enroll  instead  of  the 

corresponding hard-wired input in the control panel (the terminal will 
be disabled). 

 

If  eight  zeros  are  entered  as  a  production  code,  the  device  already 
assigned to the address nn  will be erased 

 

 

12.43.  Automatic setting/unsetting schedule 

This  can  be  used  to  program  an  automatic  sequence  of  daily 

setting/unsetting  events.  Up  to  10  daily  events  can  be 
programmed. Events will occur every day of the week:  

64 n a hh mm 

where:   

n

  

is the event number from  0 to 9 

 

 

a

  

is the type of event from 0 to 6 (see the following 
table) 

hh

 

hours (time of event) 

mm

  

minutes (time of event) 

Erase the automatic schedule setting by:

 

 

64 n 0

 

 

 

*   the same event in an unsplit system 
** only possible if partial setting (arming) is programmed (see 12.24) 

 

Notes:  

  The  automatic  setting/unsetting  event  schedule  can  also  be 

programmed in maintenance mode.  

  If automatic event scheduling is not used for setting/unsetting control 

and  the  system is  not split, then  it 

can  be programmed  as  a  daily 

timer

 to switch equipment connected to the PGY output on and off at 

the desired daily times. To do this, split the system (see 12.24) but do 
not  enroll  any  detectors  to  section  B  (keeping  this  section  empty). 
Then program the PGY output to be triggered by the setting (arming) 
of  section  B  (see  12.5)  and  program  the  automatic  daily  event 
schedule (with a=4) to set/unset the empty section B which will then 
switch the PGY output on and off at the required times every day. 

 

Factory default setting:

 All automatic events switched off. 

 

12.44.  Changing the service code.   

To change the service code enter: 

5 NC NC 

where: 

NC

 

new  code  (4  digits),  the  new  code  has  to  be 
entered twice. 

  

Example: 

The  code  1276  can  be  programmed  by  entering:    5  

1276  1276 

 

Factory default setting:

 8080 

 

Unsplit system 

Split system 

No event 

No event 

Set all (ABC) 

Set all (ABC) 

Unset all (ABC) * 

Unset all (ABC) 

Set A** 

Set A 

Set AB** 

Set B

 

Unset all (ABC) * 

Unset A 

Unset all (ABC) * 

Unset B 

Summary of Contents for JA-82KRC-US

Page 1: ...OASiS security system JA 82KRC US 1 21 MKH51400 JA 82KRC US OASiS Control panel installation manual This manual is valid for control panel JA 82KRC US The control panel can be configured by a PC runn...

Page 2: ...ible alarms 13 12 21 Wireless siren alarm enabled IW and EW 13 12 22 Auto bypass user approval via the key 13 12 23 Final door detectors 13 12 24 Partial setting arming or system splitting 14 12 25 Au...

Page 3: ...01 to 50 for wireless inputs o The control panel does not allow for the simultaneous connection of both a wired and a wireless input to the same address Connecting to a wired input automatically disab...

Page 4: ...r Maintenance modes 1 2 Optional system configurations In the European Union region follow the valid standards and rules especially series EN 501 xx The Oasis control panel complies with grade 2 The c...

Page 5: ...allel resistors see the diagram below o For wiring examples see the below diagram TAMPER SIREN ACTIVATION TAMPER ACTIVATION TAMPER ACTIVATION TAMPER ACTIVATION ACTIVATION DOOR 1 DOOR 2 DETECTOR 1 DETE...

Page 6: ...control panel for 1 second e g using a screwdriver This will enter enrollment mode on the control panel 4 Install batteries into the keypad not far from the control panel 5 The keypad generates a bee...

Page 7: ...nection to the control panel possibly due to excessive distance or it could be too close to the control panel closer than 2 meters is not permitted To re enroll a device first disconnect its battery T...

Page 8: ...multiple control panels in one UC or AC receiver 12 Control panel programming The most convenient way to program the system is to use a PC running OLink software The system can however also be progra...

Page 9: ...g Entrance delay beeps 35x 351 YES 350 NO YES Setting arming confirmation by wired siren chirp 36x 361 YES 360 NO NO IW terminal only Siren always sounds during audible alarms 37x 371 YES 370 NO YES N...

Page 10: ...the effect or SET A or SET AB C has the effect or SET ABC or UNSET ABC In a split system a keyfob button pair assigned to section A SET UNSET A B SET UNSET B C SET UNSET ABC 61 nn r s Code card react...

Page 11: ...alarm PG on excluding Panic Panic A PGX on Panic B PGY on 6 AC dropout PG on Fire PGX on dropout PGY on 7 ON OFF 8 2 seconds pulse The ON OFF and 2 second pulse functions can be controlled from the ke...

Page 12: ...ter code has no effect on other codes and cards Resets are recorded in the control panel memory and sent to the ARC if used Alarm Receiving Centre previously called a central monitoring station 12 12...

Page 13: ...Wireless siren alarm enabled IW and EW This setting is for enabling and disabling wireless sirens in the system 3 8 1 wireless sirens enabled 3 8 0 wireless sirens disabled Note This setting has no e...

Page 14: ...nset immediately after the user sets unsets the system Assigning wireless devices access codes and keyfobs to various sections of the system has no effect in this mode Partial setting is especially su...

Page 15: ...r or a JA 80V version XA64005 or higher is installed 12 32 Annual check notification This sequence enables the user and installer to be notified of the necessary time for an annual technical check 690...

Page 16: ...hard wired input terminals in the control panel or enrolled wireless devices r is the reaction index from 0 to 9 see Table 2 s is the section 1 A 2 B 3 C only has an effect if partial setting or syst...

Page 17: ...rd has a natural reaction i e r 1 then its reaction is set unset set etc the same as reaction r 9 in table 2 A code card can also have an alarm reaction designated to it similar to detectors Factory d...

Page 18: ...is stored in the non volatile memory of keypads so power disconnection will not erase any stored text Convenient text editing is possible using a PC running OLink software Besides device names keypad...

Page 19: ...codes and cards from 01 to 50 are erased If a user has both a code and a card then it is possible to program whether both a code and card must be presented to the system for system access or whether o...

Page 20: ...can be scrolled through with the A indicator showing whether a code is programmed or not and the B indicator showing whether a card is programmed or not 4 To exit this code card display mode press th...

Page 21: ...st wake it up Install an ordinary magnetic sensor to the entrance door wiring it to the keypad input so that opening the door wakes up the keypad and reports to the control panel Alternatively power t...

Reviews: