background image

Installation manual: OASiS security system JA-82KRC-US   

14 / 21 

MKH51400

 

  After  entering  a  request  to  set  the  system,  an  exit  delay  of 

between 30 to 270 seconds will begin and be indicated.  

  If  a  final-door  detector  is  triggered  during  the  exit  delay,  the 

exit delay will be extended by the time in which the detector is 
still triggered. So, if for example, the door is left continuously 
open, the exit delay will never end. 

  If a final-door detector is de-triggered, the system will wait five 

more  seconds  during  which  beeping  gets  faster,  and  if  the 
door  is  not  opened  again  during  this  short  period,  the  exit 
delay will terminate and the system will be set immediately. 

  The duration of the exit delay therefore depends on the time 

the  final  door  stays  open.  For  instance,  in  winter  if  the 
driveway  in  front  of  a  garage  needs  to  be  cleared  of  snow 
there  will  be  plenty  of  time  to  do  it,  and  in  summer  when 
garages  can  be  exited  easily  and  therefore  quickly,  the  exit 
delay  can be  rather  shorter.  The  exit  delay  only  depends  on 
the length of time  the garage door is left open. 

  If  no  final-door  detectors  are  triggered  during  the  exit  delay, 

the system will provide an exit delay and then set.  

  If  the  final  door  detector  stays  continuously  triggered,  an 

endless exit delay will result with the system never being set. 
This means all delayed and next-delayed detectors will not be 
set (armed). 

  If there are multiple final-door detectors in the system, the exit 

delay is extended if any of them is triggered and ends after all 
final-door detectors have been de-triggered. 

 

Unsetting (disarming) the system with a final door detector: 

  If a final-door detector gets triggered in a set (armed) system, 

an  entrance  delay  will  begin  with  a  duration  of  between  30 
and 270 seconds. 

  If  a  normal  delayed  detector  gets  triggered  while  the  user 

enters  a  building,  the  system  starts  an  ordinary  entrance 
delay of between 5 and 45 seconds.  

  If  a  final-door  detector  is  triggered  first,  a  longer  entrance 

delay  will  begin.  If  during  this  delay  an  ordinary  delayed 
detector  is  then  triggered,  the  remaining  entrance  delay  will 
then  be  shortened  to  the  delay  associated  with  detectors  of 
this kind. 

Note: 

Only  use  status-reporting  detectors  such  as  the  JA-80M 

or JA-82M, or the hard-wired inputs of wireless keypads, or the 
hard-wired inputs of a control panel as final-door detectors.  This 
mode  is  unsuitable  for  pulse  detectors  such  as  JA-80P  motion 
detectors,  or  the  hard-wired  inputs  of  JA-80E  hard-wired 
keypads which also have a pulse reaction. 

Factory default setting:

 No final-door detectors in the system. 

12.24.  Partial setting (arming) or system splitting  

The control panel can be configured in three ways as follows: 

  the entire system sets and unsets together or, 

  the  system  partially  sets  and  unsets  to  protect  only 

certain parts of a house during the day, while people are 
still present in the unset parts or, 

  the  system  can  be  split  into  two  independently  set/unset 

sections for two separate users and also with a common 
section if desired. 

 

Program as follows to configure the system as desired: 

66x 

where 

x = 0 

unsplit  system 

(setting/unsetting  as  an  entire 

system)

   

x = 1 

partial  setting 

(for  setting  sections  A,  AB,  or 

ABC) 

x = 2 

split system 

(sections A and B can be set/unset 

independently by separate users, with section C 
only being automatically set when both A and B 
are manually set) 

Notes: 

 

For  an  unsplit  system, 

all  intruder  detectors  are  set/unset 

immediately after the user sets/unsets the system. Assigning wireless 

devices, access codes and keyfobs to various sections of the system 
has no effect in this mode. 

 

Partial  setting 

is  especially  suitable

 

for  homes  and  apartments 

where  the  user  wishes  to  protect  different  parts  of  the  premises 
during the day. Detectors can be assigned to three sections, A, B and 
C.  Using setting  (arming)  key A  on  the  system  keypad, you can  set 
section A, e.g. setting the garage area in the afternoon. Using setting 
key  B  you  can  set  sections  A  and  B  simultaneously  e.g.  in  the 
evening before going to sleep  to protect the garage (section A) and 
the  ground  floor  of  the  house  (section  B).  The  ABC  total-setting 
button is used when leaving the home to set all sections, A,B and C. 
If you then use a valid access code or card for unsetting (disarming), 
all  sections  will  be  unset.  The  assignment  of  codes  or  cards  to 
sections has no effect in this mode.   

 

A keyfob can also be used for partial setting control. Buttons 

 and 

  can  be  programmed  to  set  and  unset  the  entire  system,  and 

buttons 

+

  can  be  programmed  for  setting  (arming)  sections  A 

and AB respectively to partially set the system. (see 12.40 for details 
on partial setting by keyfob). 

 

Split system mode

 is especially suitable where two families (A and 

B)  live  in  a  single  house  or  two  companies  (A  and  B)  share  one 
building.  The  system  behaves  as  two  independent  systems,  one 
being  section  A  and  the  other,  section  B.  There  is  also  a  common 
section C which is only set if section A and section B are set at the 
same  time.  and  is  commonly  used  for  shared  entrances,  doors  etc. 
Detectors can be assigned to sections A, B or C. Access codes and 
cards can be assigned to operate either section A or B (not both), or 
alternatively to  section  C  to  access the  entire  building.  The same  is 
true for keyfob access. 

 

Partial setting only has an effect on intruder detectors, i.e. detectors 
with  instant,  delayed  or  next-delayed    reactions.  Detectors  with  fire, 
tamper,  panic  and  24-hour  reactions  are  always  able to  trigger their 
kind of alarm immediately, whether their section is set (armed) or not.

 

 

Factory default setting:

 Unsplit system. 

 

12.25.  Automatic  summer  time  (daylight  saving 

time) 

If enabled, this feature automatically offsets the system time to 

that of summer time, or daylight saving time as it is also known:   

 

6801

 

automatic summer time enabled 

6800

 

automatic summer time disabled 

 

Note: 

If  automatic  summer  time  is  enabled,  the control  panel’s  internal 

clock is automatically offset by +1 hour on March 31

st

 at midnight.  The 

offset  is  then  removed  on  October  31

st

  at  midnight  to  return  to  winter 

time. 

 

Factory default setting:

 automatic summer time disabled  

 

12.26.  Tamper  alarm  in  response  to  an  increase  in 

the number of triggered tamper sensors 

This feature allows permanently triggered tamper sensors to be 

ignored:  

 

6811

 

ignore  permanently  triggered  tamper  sensors, 
i.e.  only  react  to  an  increase  in  the  number  of 
triggered tamper sensors. 

6810

 

react with a tamper alarm to all triggered tamper 
sensors 

 

Note: 

Ignoring  permanently  triggered  tamper  sensors  is  useful  for 

example  when  carrying  a  detached    wireless  keypad  around  with  you 
during installation as this avoids unnecessary tamper indication.  

 

Factory  default  setting:

  react  with  a  tamper  alarm  to  all 

triggered tamper sensors 

 

12.27.  Operating the PG outputs using 

8 and 

Using this feature the PGX and PGY outputs can be controlled 

from the keypad by pressing the 

8 and 

9 keys (or keys 

 

and

 

). 

6821

 

control enabled 

6820

 

control disabled  

Notes: 

 

The  PG  outputs  can  only  be  operated  from  the  keypad  if they  have 
their ON/OFF or pulse functions enabled. 

Summary of Contents for JA-82KRC-US

Page 1: ...OASiS security system JA 82KRC US 1 21 MKH51400 JA 82KRC US OASiS Control panel installation manual This manual is valid for control panel JA 82KRC US The control panel can be configured by a PC runn...

Page 2: ...ible alarms 13 12 21 Wireless siren alarm enabled IW and EW 13 12 22 Auto bypass user approval via the key 13 12 23 Final door detectors 13 12 24 Partial setting arming or system splitting 14 12 25 Au...

Page 3: ...01 to 50 for wireless inputs o The control panel does not allow for the simultaneous connection of both a wired and a wireless input to the same address Connecting to a wired input automatically disab...

Page 4: ...r Maintenance modes 1 2 Optional system configurations In the European Union region follow the valid standards and rules especially series EN 501 xx The Oasis control panel complies with grade 2 The c...

Page 5: ...allel resistors see the diagram below o For wiring examples see the below diagram TAMPER SIREN ACTIVATION TAMPER ACTIVATION TAMPER ACTIVATION TAMPER ACTIVATION ACTIVATION DOOR 1 DOOR 2 DETECTOR 1 DETE...

Page 6: ...control panel for 1 second e g using a screwdriver This will enter enrollment mode on the control panel 4 Install batteries into the keypad not far from the control panel 5 The keypad generates a bee...

Page 7: ...nection to the control panel possibly due to excessive distance or it could be too close to the control panel closer than 2 meters is not permitted To re enroll a device first disconnect its battery T...

Page 8: ...multiple control panels in one UC or AC receiver 12 Control panel programming The most convenient way to program the system is to use a PC running OLink software The system can however also be progra...

Page 9: ...g Entrance delay beeps 35x 351 YES 350 NO YES Setting arming confirmation by wired siren chirp 36x 361 YES 360 NO NO IW terminal only Siren always sounds during audible alarms 37x 371 YES 370 NO YES N...

Page 10: ...the effect or SET A or SET AB C has the effect or SET ABC or UNSET ABC In a split system a keyfob button pair assigned to section A SET UNSET A B SET UNSET B C SET UNSET ABC 61 nn r s Code card react...

Page 11: ...alarm PG on excluding Panic Panic A PGX on Panic B PGY on 6 AC dropout PG on Fire PGX on dropout PGY on 7 ON OFF 8 2 seconds pulse The ON OFF and 2 second pulse functions can be controlled from the ke...

Page 12: ...ter code has no effect on other codes and cards Resets are recorded in the control panel memory and sent to the ARC if used Alarm Receiving Centre previously called a central monitoring station 12 12...

Page 13: ...Wireless siren alarm enabled IW and EW This setting is for enabling and disabling wireless sirens in the system 3 8 1 wireless sirens enabled 3 8 0 wireless sirens disabled Note This setting has no e...

Page 14: ...nset immediately after the user sets unsets the system Assigning wireless devices access codes and keyfobs to various sections of the system has no effect in this mode Partial setting is especially su...

Page 15: ...r or a JA 80V version XA64005 or higher is installed 12 32 Annual check notification This sequence enables the user and installer to be notified of the necessary time for an annual technical check 690...

Page 16: ...hard wired input terminals in the control panel or enrolled wireless devices r is the reaction index from 0 to 9 see Table 2 s is the section 1 A 2 B 3 C only has an effect if partial setting or syst...

Page 17: ...rd has a natural reaction i e r 1 then its reaction is set unset set etc the same as reaction r 9 in table 2 A code card can also have an alarm reaction designated to it similar to detectors Factory d...

Page 18: ...is stored in the non volatile memory of keypads so power disconnection will not erase any stored text Convenient text editing is possible using a PC running OLink software Besides device names keypad...

Page 19: ...codes and cards from 01 to 50 are erased If a user has both a code and a card then it is possible to program whether both a code and card must be presented to the system for system access or whether o...

Page 20: ...can be scrolled through with the A indicator showing whether a code is programmed or not and the B indicator showing whether a card is programmed or not 4 To exit this code card display mode press th...

Page 21: ...st wake it up Install an ordinary magnetic sensor to the entrance door wiring it to the keypad input so that opening the door wakes up the keypad and reports to the control panel Alternatively power t...

Reviews: