background image

Installation manual: OASiS security system JA-82KRC-US   

8 / 21 

MKH51400

 

11.5.  Erasing enrolled devices  

1.  The control panel must be in Service Mode. If it is not, then 

enter 

0  service  code  (factory  default:  8080).  The  control 

panel must be unset (disarmed) to enter Service Mode. 

2.  Key  in  “1”  to  enter  enrollment  mode  and  using  the  arrow 

keys  select  the  desired  address  of  the  device  you  wish  to 
erase. 

3.  Press and hold the “2” key until a beep is heard and the A 

indicator turns off. 

4.  After all the desired devices have been erased, press 

#.

   

Notes: 

  To erase all wireless devices, press and hold the “4” key in 

enrollment mode.  

  If  a  wireless  keypad  is  erased,    it  will  stop  communicating 

with the control panel and must be re-enrolled before being 
used again. (see 7.1).  

11.6. 

 

Enrolling  the  control  panel  to  UC  and  AC 

modules 

If  you  wish  to  use  UC  and  AC  modules  to  output  PGX  and 

PGY  signals,  you  must  enroll  the  control  panel  to  these 
modules as follows:  

1.  The control panel must be in Service Mode. If it is not, then 

enter 

0 service code (factory default: 8080). 

2.  On  the  UC  or  AC  module,  enter  the  desired  enrollment 

mode  (see the manual of the particular module) 

3.  Key in 

299

  on the control panel keypad and check that all 

LEDs on the module flash a few times to confirm successful 
enrollment. 

Notes: 

  Because  the  UC  and  AC  modules  have  rather  short 

enrollment-period  timeouts,  we  recommend  locating  the 
module  close  to  the  control  panel  during  enrollment. 

Alternatively  you  could  carry  the  wireless  keypad  close  to 
the module to perform enrollment. 

  The control panel can be enrolled to the desired number of 

UC/AC  modules  to  control  multiple  PG  outputs  in  an 
installation. 

  Each UC and AC module has 2 relays, X and Y which have 

to  go  through  enrollment  separately.  The  X  relay  reacts  to 
PGX signals from an enrolled control panel and the Y relay 
reacts  to  PGY  signals  from  an  enrolled  control  panel.  The 
control  panel’s  PGX  signal  can  be  enrolled  to  the  X  relay 
and the control panel’s PGY signal can be enrolled to the Y 
relay.  Therefore,  the  enrollment  procedure  has  to  be  done 
twice  if  both  relays  are  to  be  controlled  by  the  control 
panel’s PG signals. 

  Only  one  control  panel  can  be  enrolled  to  a  UC  or  AC 

receiver  because  a  control  panel  repeats  its  PG  signals 
every  9  minutes  so  it  is  impossible  to  combine  multiple 
control panels in one UC or AC receiver. 

12.  Control panel programming 

The most convenient way to program the system is to use 

a  PC  running  OLink  software.  The  system  can  however  also 
be programmed by keying in the sequences in section 12.1.  

  The  system  should  be  in  Service  mode  (if  not,  enter  the 

following  with  the  system  unset:  “

0  Service  code”  –  the  

factory default is 8080). 

  Enter  the  appropriate  programming  sequences  –  see  the 

following  description  (an  unfinished  sequence  can  be 
escaped from by pressing the # key). 

 

To exit Service

 

Mode

 press the # key. 

12.1.  Control panel programming sequences 

Function 

Sequence 

Options 

Factory 

default 

Notes 

Entering enrollment mode  

One wireless device (detector, keypad, key fob, siren or sub 

control panel) can be enrolled to each 

address from 01 to 50

The system offers vacant addresses one by one, if all 

addresses are occupied no devices can be enrolled. 

A  device  enrolled  to  address  01  to  04  (or  01  to  14) 

disables the corresponding hard-wired input 01 to 04 (or 01 to 
14, respectively).  

In addition to enrollment mode, devices can also be enrolled 

by keying in their production codes (see 12.42). 

Keys:  
up/down arrows

 = address 

scrolling

  

holding 

2

erases the displayed

 

address 

holding 

4

 = 

erases all

 addresses 

#

 = 

exiting

 enrollment mode  

 
 

  

nothing 

 devices enroll by 

connecting their 
power (battery) except 
keyfobs which enroll 
by pressing & holding 
a pair of their buttons  

 an occupied address 

is indicated by the A 
indicator being lit 

 enrolling a device to 

a new address will 
move it there 

Exit delay time 

20x 

x

 = 1 to 9 (x10 s =10 to 90 s) 

30s 

Entrance delay time 

21x 

x

 = 1 to 9 (x 5 s = 5 to 45 s) 

20s 

if a final door detector 
is used, then x is 
multiplied by 30s 
instead (i.e. from 30 
to 270s) 

Alarm duration time 

22x 

= 1 to 8 (min.), 9=15min  

4 min. 

0=10s (for testing) 

PGX function 

23x 

 

 

on/off 

(∗

80/

81) 

PGY function 

24x 

x in an unsplit system: 

0 - whole system set (ABC)  = 

PG on 

1 - any system part set = PG on 
2 - AB set (not C) = PG on 
3 - Fire alarm = PG on 
4 - Panic alarm = PG on 
5 - Any alarm = PG on 
   

(excluding Panic) 

6 - AC dropout = PG on 
7 - PG on/off (by 

80 /

81 for 

PGX and   

90/

91 for PGY) 

8 – Single 2 s pulse (keys 

8=X, 

9=Y) 

any 

system 

part set 

x in a split system

 

0 - alarm A = PG on 
1 - alarm B = PG on 
2 - entrance delay A = 
= PG on 
3 - entrance delay B = 
PG on 
4 - A set = X on, B set 
= Y on 
5 - A panic = X on, B 
panic = Y on 
6 - Fire = X on, AC 
dropout = Y on. 
7 - PG on/off (by 

80 

/

81for PGX and   

90/

91 for PGY) 

8 – Single 2 s pulse 
(keys 

8=X, 

9=Y)

 

Enablement  of  telephone  number  changes  in 
maintenance mode 

25x 

251 = YES      250 = NO 

NO 

see communicator 

Summary of Contents for JA-82KRC-US

Page 1: ...OASiS security system JA 82KRC US 1 21 MKH51400 JA 82KRC US OASiS Control panel installation manual This manual is valid for control panel JA 82KRC US The control panel can be configured by a PC runn...

Page 2: ...ible alarms 13 12 21 Wireless siren alarm enabled IW and EW 13 12 22 Auto bypass user approval via the key 13 12 23 Final door detectors 13 12 24 Partial setting arming or system splitting 14 12 25 Au...

Page 3: ...01 to 50 for wireless inputs o The control panel does not allow for the simultaneous connection of both a wired and a wireless input to the same address Connecting to a wired input automatically disab...

Page 4: ...r Maintenance modes 1 2 Optional system configurations In the European Union region follow the valid standards and rules especially series EN 501 xx The Oasis control panel complies with grade 2 The c...

Page 5: ...allel resistors see the diagram below o For wiring examples see the below diagram TAMPER SIREN ACTIVATION TAMPER ACTIVATION TAMPER ACTIVATION TAMPER ACTIVATION ACTIVATION DOOR 1 DOOR 2 DETECTOR 1 DETE...

Page 6: ...control panel for 1 second e g using a screwdriver This will enter enrollment mode on the control panel 4 Install batteries into the keypad not far from the control panel 5 The keypad generates a bee...

Page 7: ...nection to the control panel possibly due to excessive distance or it could be too close to the control panel closer than 2 meters is not permitted To re enroll a device first disconnect its battery T...

Page 8: ...multiple control panels in one UC or AC receiver 12 Control panel programming The most convenient way to program the system is to use a PC running OLink software The system can however also be progra...

Page 9: ...g Entrance delay beeps 35x 351 YES 350 NO YES Setting arming confirmation by wired siren chirp 36x 361 YES 360 NO NO IW terminal only Siren always sounds during audible alarms 37x 371 YES 370 NO YES N...

Page 10: ...the effect or SET A or SET AB C has the effect or SET ABC or UNSET ABC In a split system a keyfob button pair assigned to section A SET UNSET A B SET UNSET B C SET UNSET ABC 61 nn r s Code card react...

Page 11: ...alarm PG on excluding Panic Panic A PGX on Panic B PGY on 6 AC dropout PG on Fire PGX on dropout PGY on 7 ON OFF 8 2 seconds pulse The ON OFF and 2 second pulse functions can be controlled from the ke...

Page 12: ...ter code has no effect on other codes and cards Resets are recorded in the control panel memory and sent to the ARC if used Alarm Receiving Centre previously called a central monitoring station 12 12...

Page 13: ...Wireless siren alarm enabled IW and EW This setting is for enabling and disabling wireless sirens in the system 3 8 1 wireless sirens enabled 3 8 0 wireless sirens disabled Note This setting has no e...

Page 14: ...nset immediately after the user sets unsets the system Assigning wireless devices access codes and keyfobs to various sections of the system has no effect in this mode Partial setting is especially su...

Page 15: ...r or a JA 80V version XA64005 or higher is installed 12 32 Annual check notification This sequence enables the user and installer to be notified of the necessary time for an annual technical check 690...

Page 16: ...hard wired input terminals in the control panel or enrolled wireless devices r is the reaction index from 0 to 9 see Table 2 s is the section 1 A 2 B 3 C only has an effect if partial setting or syst...

Page 17: ...rd has a natural reaction i e r 1 then its reaction is set unset set etc the same as reaction r 9 in table 2 A code card can also have an alarm reaction designated to it similar to detectors Factory d...

Page 18: ...is stored in the non volatile memory of keypads so power disconnection will not erase any stored text Convenient text editing is possible using a PC running OLink software Besides device names keypad...

Page 19: ...codes and cards from 01 to 50 are erased If a user has both a code and a card then it is possible to program whether both a code and card must be presented to the system for system access or whether o...

Page 20: ...can be scrolled through with the A indicator showing whether a code is programmed or not and the B indicator showing whether a card is programmed or not 4 To exit this code card display mode press th...

Page 21: ...st wake it up Install an ordinary magnetic sensor to the entrance door wiring it to the keypad input so that opening the door wakes up the keypad and reports to the control panel Alternatively power t...

Reviews: