Specifications/Outer dimensions
■ Control unit
Operation
modes
MAN (Manual)
A flow rate is set with (Up) and (Down) keys.
EXT
Analogue preset 4-20/0-20/20-4/20-0mA (proportional control of a flow by current patterns)
Analogue variable 0-20mADC (proportional control of a flow by user-settable two points )
Pulse control*
1
0.01560mL/PLS - 300mL/PLS (D150)
0.03120mL/PLS - 600mL/PLS (D300)
Batch control*
1
15.6mL/PLS - 300L/PLS (D150)
31.2mL/PLS - 600L/PLS (D300)
Interval batch
control*
1
0-9day, 0-23hr, 1-59min
15.6mL - 300L/PLS (D150)
31.2mL - 600L/PLS (D300)
Profibus control Profibus-DP
Compliant to EN50170 (IEC61158)
Monitors
LCD
16×2 backlit LCD
LED
OPERATE
Lights in green colour during pump operation.
Lights in orange colour when a Pre-STOP signal is input.
Lights in red colour when the pump has stopped or flashes when pres
-
sure overload is detected.
ALARM
Lights in red colour when Alarm OUT 1 or 2 is activated.
Operation
Key-
pads
(Start/Stop), MENU, ESC, (Enter), (Up), (Down), (Left) and (Right) keys
Control
functions
STOP
Pump OFF at contact input*
2
PRIME
Max spm operation while the UP and DOWN keys are pressed.
Keypad lock
PIN number entry disables the function.
Interlock
Pump OFF at contact input*
2
AUX
Pump ON at AUX speed at contact input
Maximum flow rate setting The max flow rate can be set at each control mode.
Buffer
Accumulates the entered external pulse signal with buffer ON.
Current value indication An input current is displayed during operation in the ANA.V mode.
Input
Stop/ Pre-STOP
No-voltage contact or open collector*
3
AUX
No-voltage contact or open collector*
3
Interlock
No-voltage contact or open collector*
3
Analogue
0-20mADC (internal resistance is 200Ω.)
Pulse
No-voltage contact/open collector (max 100Hz, min ON time: 5msec)
Output
Alarm (OUT 1)
No voltage contact (mechanical relay) 250VAC 3A (resistive load)
Enable or disable the Batch Complete*
4
, STOP, Pre-STOP, Interlock,
Leak Detection (default: ON) and Motor Overload (/Drive Error).
Alarm (OUT 2)
No voltage contact (PhotoMOS relay) 24VAC/DC 0.1A (resistive load)
Enable or disable the Volume Prop. PLS*
5
, Batch Complete*
4
, STOP,
Pre-STOP, Interlock (default: ON), Leak Detection and Motor Overload (/
Drive Error).
Power supply
12VDC 30mA or below
Analogue
User-settable between 0-20mADC (allowable load resistance: 300Ω)
Power voltage*
6
100-240VAC 50/60Hz
*
1
For these control modes, the calibrated flow volume per shot is applied to the minimum settable flow volume per shot.
*
2
The setting can be changed to "pump ON at contact input".
*
3
The maximum applied voltage from the IX to an external contact is 12V at 5mA. When using a mechanical relay, its
minimum application load should be 5mA or below.
*
4
Once the Batch Complete output is set to enabled, other output functions turn disabled.
*
5
Once the Volume Prop. PLS output is set to enabled, other output functions turn disabled.
*
6
Observe the specified power voltage range. Otherwise failure may result. The allowable power voltage range is 90-
264VAC.