EQUIPMENT HEALTH MONITOR ROUTINE OPERATION
Measurement interval
The measurement interval for the condition monitor during normal and alarm operation is 5 minutes.
When the monitor measures a reading beyond the specified temperature and vibration limits, the appropriate red LED
flashes (after 2 consecutive readings). After the process or pump condition that causes the alarm is corrected, the condition
monitor returns to normal mode after one normal-level measurement.
Alarm mode
The condition monitor’s alarm mode is activated after two consecutive readings. When the alarm mode is on, you should
investigate the cause of the condition and make necessary corrections in a timely manner.
Magnetic device considerations
Be careful when you use magnetic devices in close proximity of the condition monitor, such as magnetic vibration-
monitoring probes or dial indicators. These magnetic devices can accidentally activate or deactivate the condition monitor
resulting in improper alarm levels or loss of monitoring.
Wireless Integration
A Bluetooth Low Energy Radio is utilized to communicate condition monitoring information to a mobile Smart device that
the operator can easily view and react to.
I-ALERT2
EQUIPMENT HEALTH MONITOR TROUBLESHOOTING
Figure 25: Troubleshooting
Summary of Contents for i-ALERT2
Page 1: ...Application Guide...
Page 2: ...i ALERT2 Application Guide 2 of 64...
Page 32: ...i ALERT2 Application Guide 32 of 64 Figure 27 Devices in range and out of range...
Page 58: ...i ALERT2 Application Guide 58 of 64 Figure 57 Route Report Trend Details Screen...
Page 63: ...i ALERT2 Application Guide 63 of 64...
Page 64: ...i ALERT2 Application Guide 64 of 64 G iALERT2AppGuide en US 2016 10...