CUSTOMER SERVICE
The convector is furnished with (G20) gas function
following the Technical label, and the constructor
already regulates it. If you make a new regulation,
like exchanging the gas valve, or a gas transforma-
tion from Methane to GPL or reversed, this regula-
tion has to be done from a Technical service
Assistance or by the manufacture
Gas methane G 20(20mbr); nominal & minimum
pressure regulation.
- Open the gas tap put the electrical plug under the
convector then pushes the start button and put to the
max power.
Alimentation pressure
- Loosen the pressure screw (1) connect the mano-
meter and verified the pressure value is included
between 17/25mbar (like indicated in the table) then
close the screw after that the manometer tube is pul-
led away.
- Loosen the pressure screw (2) connect the mano-
meter verified the nominal and minimum pressure
values are as specified in the table.
Nominal pressure
With the convector in function at a max power veri-
fied that the values of the nominal pressure are as
specified in the table. To make a regulation operate
on the pressure regulator that is at the edge of the
valve gas, then take off the protection cap. If you
rotate the regulator (3) screw clockwise the pressure
increase, rotating counter clockwise the pressure
decrease. After that, check that all the regulation are
done, fasten the cap then close with cover.
Regulation GPL butane G30 (29mbar) and
Propane G31 (37mbar). Minimum and nominal
pressure.
- Open the gas taps put the electrical plug under the
convector then push the start button and put to the
max power.
Alimentation pressure
- Loosen the pressure screw (1) connect the mano-
meter and verified the pressure value is included
between 29 mbar with the Butane and 37 mbar with
Propane then close the screw. In the case that the
net pressure is low, operate on the low-pressure
regulator that is put on the Gas tank.
- Verified that the establishment GPL vaporization
capacity is sufficient.
Nominal pressure
With the convector in function at a max power loosen
the outlet pressure screw (2) then connect the mano-
meter and verified that the nominal pressure values
are as specified in the table (Nozzle Pressure). In the
GPL function, only for the 3+ categories the regulator
has to be out of service fastening clockwise the adju-
stment screw (1) at an immediately inferior value to
the alimentation max pressure.
At verification done, take away the manometer and
fasten the screw.
3
2
1
REGOLATION
MODELLO
30
50
G 2 0
1 2
1 2
G 3 0
2 8 , 8
2 8 , 8
G 3 1
3 6 , 7
3 6 , 6
mbar
mbar
70
1 2
2 8 , 8
3 6 , 5
mbar
nom.
nom.
nom.
90
1 0
2 7 , 4
3 4 , 5
mbar