Installation stage
The convector installations stages are:
- Apparatus choice location
- Tube installation
- Parallel tube kit Ø 32 mm or Ø 54 mm with unique
terminal (standard)
- Separated pip kit Ø 32 mm o Ø 54 mm with single
terminal (special)
- Convector installation
- Electrical collegaments
- Gas connection
TYPE OF INSTALLATION SECOND UNI CIG 7129
As we go on we are going to show you the types of
installation second by the Uni Cig 7129 rule.
INTAKE AND EXHAUST TUBE FUMES ASSEM-
BLAGE
The intake & exhaust tubes can be
embedded
insi-
de the wall, or in
sight
, they have to be protected to
avoid, risk condition. To have the apparatus in sight
it exist a spacing bar so that you can see the tubes,
we recommend that the unloaded tubes have to
have a good insulation using materials that have
also a resistant of more 200° C°
(ex. HT/-
Armaflex) of temperature. Realize the holes for
fastening the tubes, after establish the hangers
ʼ
length; insert it in the right position.
Before assembling the tubes kit verifying that the
Max tube length has been respected, even the
Max loaded loss provided
(See table).
50 MIN
A
B
RIGHT SIDE
L
h
C
D
b
a
in mm
A
Overall dimensions
50
450
70
600
90
750
B
204
204
204
C
312,5
312,5
312,5
D
267,5
267,5
267,5
h
580
580
580
L
658
808
958
30
300
204
312,5
267,5
580
508
15
INSTALLATION
¯ unloaded intake tubes
¯ Wall hole single terminal tubes
Max single terminal tube length
Min comprehensive tube length
Loaded loss tube L = 500mm
Loaded loss tube L = 1000mm
Loaded loss single terminal
Loaded max loss permissible (*)
30
80
80
Loaded loss tube curve 90¡ (die)
mm
mm
m
mm
Pa
Pa
Pa
Pa
Pa
54
110
15
0,5
0,7
4,4
2
20
54
110
15
0,6
1
9
4
20
32
65
1
6
11
-
9
50
32
65
5
3
5
-
5
50
80
54
110
15
0,8
1,6
0,3
4
30
50
70
90
80
54
110
10
1,2
2,25
4,3
6
25
30
50
70
90
MAX length tubes with separate terminal
m
15
15
3
10
15
10
Loaded loss tube curve 90¡
Pa
0,7
1,5
12,2
5,8
0,05
0,7