Ofs 1 to Of 5 for the offset values.
The Pnt values must be entered in ascending order.
Set a Pnt to a value lower than the previous point to disable it.
The indicator would be programmed with the following data:
Pnt 1 100
Ofs 1 0.8
Pnt 2 300
Ofs 2 1.1
Pnt 3 500
Ofs 3 2.1
Pnt 4 -999
Ofs 4 0
Pnt 5 -999
Ofs 5 0