Goodrive10 Series Mini VFD
Fault tracking
-83-
Fault code
Fault type
Possible cause
Solution
EF
[17] External fault
SI external fault input
terminals acts.
Check the external
device input.
CE
[18] RS485
communication
fault
Baud rate is set
improperly.
Communication line
fault.
Communication address
error.
Communication suffers
from strong interference.
Set proper baud rate.
Check the wiring of
communication
interfaces.
Set proper
communication
address.
Replace or change the
wiring to enhance
anti-interference
capacity.
EEP
[21] EEPROM
operation fault
R/W error occurred to
the control parameters.
EEPROM is damaged.
Press STOP/RST to
reset.
Replace the main
control board.
PIDE
[22] PID feedback
offline fault
PID feedback offline
PID feedback source
disappears.
Check PID feedback
signal wires.
Check PID feedback
source.
END
[24] Running time
reached
The actual running time
of the VFD is larger than
the set running time.
Ask help from the
supplier, and adjust
the set running time
OL3
[25] Electronic
overload fault
The VFD releases
overload pre-alarm
based on the set value.
Check the load and
overload
pre-alarm
threshold.
LL
[36] Electronic
underload fault
The VFD releases
underload pre-alarm
based on the set value.
Check the load and
underload
pre-alarm
threshold.
6.2.4 Fault instruction and solution
Fault code
Fault type
Possible cause
Solution
PoFF
System power
failure
The system is powered
off or the bus voltage is
too low.
Check the grid
conditions.