Communication protocol
-94-
instructions should be paid attention to when modifying the function code parameters.
EEPROM is stocked frequently, which may shorten the usage time of EEPROM. For
users, some functions are not necessary to be stocked on the communication mode.
The needs can be met on by changing the value in RAM. Changing the MSB of the
function code form 0 to 1 can also realize the function. For example, the function code
P00.07 is not stocked into EEPROM. Only by changing the value in RAM can set the
address to 8007H. This address can only be used in writing RAM other than reading. If
it is used to read, it is an invalid address.
7.3.4.2 Description of other function addresses in Modbus
BIn addition to modifying the parameters of the VFD, the master can also control the VFD,
such as start and stop it, and monitor the operation state of the VFD. The following table
describes other function parameters.
Function instruction
Address
definition
Data meaning instruction
R/W
characteristics
Communication-based
control command
2000H
0001H: Forward running
R/W
0002H: Reverse running
0003H: Forward jogging
0004H: Reverse jogging
0005H: Stop
0006H: Coast to stop
0007H: Fault reset
0008H: Jogging stop
Communication-based
value setting
2001H
Communication setting
frequency (0
–Fmax (unit:
0.01Hz))
R/W
2002H
PID reference, range (0
–1000,
1000 corresponds to100.0% )
2003H
PID feedback, range (0
–1000,
1000 corresponds to100.0% )
R/W
200AH
Virtual input terminal command ,
range: 0x000
–0x1FF
R/W
200BH
Virtual input terminal command ,
range: 0x00
–0x0F
R/W
200DH
AO output setting 1
(-1000
–1000, 1000 corresponds
to 100.0%)
R/W
VFD state word 1
2100H
0001H: Forward running
R
0002H: Forward running
0003H: Stop
0004H: Fault