Goodrive10 Series Mini VFD
Function parameters
-68-
Function
code
Name
Description
Default Modify
Termin
al 2
OFF OFF ON ON
OF
F
OF
F
ON ON
Termin
al 3
OFF OFF OFF
OF
F
ON ON ON ON
Termin
al 4
ON ON ON ON ON ON ON ON
step
8
9
10
11 12 13 14 15
Setting
range
of
P10.(2n,1<n<17):
-100.0
–100.0%
P11 group Protection parameters
Function
code
Name
Description
Default Modify
P11.01
Frequency
drop at
transient
power-off
0: Disable
1: Enable
0
○
P11.02
Frequency
drop ratio
at transient
power-off
Setting range: 0.00Hz/s
–P00.03 (max. output
frequency)
After the grid powers off, the bus voltage drops
to the frequency drop point at transient
power-off, the VFD begins to decrease the
running frequency based on P11.02, to make
the motor generate power again. The returning
power can maintain the bus voltage to ensure a
rated running of the VFD until the VFD is
powered on again.
Voltage class
220V
380V
Frequency drop
point at transient
power-off
260V
460V
Note:
1. Adjust the parameter properly to avoid the
stopping caused by VFD protection during the
switching of the grid.
2. Disable input phase loss protection to enable
this function.
10.00Hz/
s
○