Goodrive10 Series Mini VFD
Function parameters
-39-
Function
code
Name
Description
Default
Modify
automatic torque boost.
Torque boost cut-off threshold: Below this
frequency threshold, the torque boost is valid,
exceeding this threshold will invalidate torque
boost.
Output voltage
Output
frequency
Cut-off
boost
b
f
f
v
v
Setting range of P04.01: 0.0% (automatic),
0.1%
–10.0%
Setting range of P04.02: 0.0%
–50.0%
P04.03
Motor V/F
frequency
point 1
When P04.00 =1, the user can set V//F curve
through P04.03
–P04.08.
V/F is generally set according to the load of the
motor.
Note:
V1 < V2 < V3, f1 < f2 < f3. Too high low
frequency voltage will heat the motor
excessively or damage. The VFD may occur
the
overcurrent
speed
or
overcurrent
protection.
Output voltage
Output
frequency
V1
V2
V3
f1
f2
f3
100.0%
b
f
b
V
Setting range of P04.03: 0.00Hz
–P04.05
Setting range of P04.04: 0.0%
–110.0% (rated
voltage of the motor)
Setting range of P04.05: P04.03
– P04.07
Setting range of P04.06: 0.0%
–110.0% (rated
voltage of the motor)
0.00Hz
○
P04.04
Motor V/F
voltage
point 1
00.0%
○
P04.05
Motor V/F
frequency
point 2
00.00Hz
○
P04.06
Motor V/F
voltage
point 2
00.0%
○
P04.07
Motor V/F
frequency
point 3
00.00Hz
○
P04.08
Motor V/F
voltage
point 3
00.0%
○