Goodrive10 Series Mini VFD
Optional peripheral accessories
-112-
VFD model
Fuse (A)
Breaker (A)
Rated current of the
contactor (A)
GD10-2R2G-2-B
32
25
16
GD10-0R7G-4-B
10
6
10
GD10-1R5G-4-B
10
10
10
GD10-2R2G-4-B
16
16
10
C.5 Reactors
When the voltage of the grid is high, the transient large current that flows into the input
power circuit may damage rectifier components. You need to configure an AC reactor on the
input side, which can also improve the current adjustment coefficient on the input side.
When the distance between the VFD and motor is longer than 50 m, the parasitic
capacitance between the long cable and ground may cause large leakage current, and
overcurrent protection of the VFD may be frequently triggered. To prevent this from
happening and avoid damage to the motor insulator, compensation must be made by
adding an output reactor. When a VFD is used to drive multiple motors, take the total length
of the motor cables (that is, sum of the lengths of the motor cables) into account. When the
total length is longer than 50 m, an output reactor must be added on the output side of the
VFD. If the distance between the VFD and motor is 50 m to 100 m, select the reactor
according to the following table. If the distance is longer than 100 m, contact INVT's
technical support technicians.
Input reactor
Output reactor
VFD model
Input reactor
Output reactor
GD10-0R2G-S2-B
-
-
GD10-0R4G-S2-B
-
-
GD10-0R7G-S2-B
-
-
GD10-1R5G-S2-B
-
-