C.3 Cable
C.3.1 Power cable
The sizes of the input power cables and motor cables must meet the local regulation.
Note:
If the conductivity of the shielding layer of the motor cables cannot meet the
requirements, separate PE conductors must be used.
C.3.2 Control cable
All analog control cables and cables used for frequency input must be shielded cables.
Relay cables need to be those with metal braided shield layers.
Keypads need to be connected by using network cables. In complicated electromagnetic
environments, shielded network cables are recommended.
Note:
Analog signals and digital signals cannot use the same cables, and their cables must be
arranged separately.
Check the insulation conditions of the input power cable of a VFD according to the local
regulations before connecting it.
VFD model
Recommended
cable size(mm
2
)
Size of connectable cable
(mm
2
)
Terminal
screw
Tightening
torque
(Nm)
RST
UVW
PE
RST
UVW
P1 and
(+)
PB
(+) and
(-)
PE
GD10-0R2G-S2-B
1.5
1.5
1.5
1.5
1.5
1.5
M3
0.56
GD10-0R4G-S2-B
1.5
1.5
1.5
1.5
1.5
1.5
M3
0.56
GD10-0R7G-S2-B
1.5
1.5
1.5
1.5
1.5
1.5
M3
0.56
GD10-1R5G-S2-B
2.5
2.5
2.5
2.5
2.5
2.5
M3
0.8
GD10-2R2G-S2-B
2.5
2.5
2.5
2.5
2.5
2.5
M3
0.8
GD10-0R2G-2-B
1.5
1.5
1.5
1.5
1.5
1.5
M3
0.56
GD10-0R4G-2-B
1.5
1.5
1.5
1.5
1.5
1.5
M3
0.56
GD10-0R7G-2-B
1.5
1.5
1.5
1.5
1.5
1.5
M3
0.56
GD10-1R5G-2-B
2.5
2.5
2.5
2.5
2.5
2.5
M3
0.8
GD10-2R2G-2-B
2.5
2.5
2.5
2.5
2.5
2.5
M3
0.8
GD10-0R7G-4-B
1.5
1.5
1.5
1.5
1.5
1.5
M3
0.8
GD10-1R5G-4-B
2.5
2.5
2.5
2.5
2.5
2.5
M3
0.8
GD10-2R2G-4-B
2.5
2.5
2.5
2.5
2.5
2.5
M3
0.8
Summary of Contents for GD10-0R2G-2-B