background image

Version 1.10

  |   Optidrive ODP-2ETHEG-IN   |   

15

www.invertekdrives.com

6.5. Process Data PDI

6.5.1. PDI Word 1: Drive Control Word

The drive control word can be used to control the drive as follows:

Port

Function

0

0: Stop 
1: Run

1

0: Normal Operation 
1: Fast Stop

2

0: No Function 
1: Fault Reset Request

3

0: Normal Operation 
1: Coast Stop

4

No function

5
6
7

6.5.2. PDI Word 2: Drive Speed Reference

The drive speed reference value has one decimal place, e.g. commanded value = 500, the drive setpoint frequency will be 50.0Hz.

6.5.3. PDI Words 3 and 4

As described in section 6.4.1. Process Data Exchange Overview, process data words 3 and 4 may be fixed function or configurable 
function depending on the drive in use. The possible functions are described below.

6.5.4. Drive Torque Reference

Where supported by the drive and correctly configured in the drive parameters, the torque limit or reference may also be sent to 
the drive using the fieldbus PDI. In this case, the value is sent with 1 decimal place, e.g. commanded value = 500, the drive torque 
setpoint will be 50.0%.

6.5.5. Drive Ramp Times

When the drive parameters are configured to allow control of the drive ramp times through fieldbus, this register specifies the drive 
acceleration and deceleration ramp times.

  

For P2 and Eco drives, when Fieldbus Ramp Control is selected (P5-08 = 1).

  

For E3 drives, setting P-12 = 4.

The input data range is from 0 to 60000 (0.00s to 600.00s for P2, 0.0 – 6000.0s for Eco).

6.5.6. User Registers

For P2 and Eco drives, which have internal function block programming capability, data may be written to the User Registers. This 
allows control functions to be achieved within the drive by linking to the Group 9 parameters. The values may also be used within the 
function block program.

6.6. Process Data PDO

PDO data is returned from the drive to the master PLC. The available data for each word is described below.

6.6.1. PDO Word 1: Drive Status Word

The function of PDO Word 1 is fixed for all drive models, and returns the drive Status Word. The individual bits within the drive status 
word indicates the status of the drive as follows. Some functions are applicable to specific drive types, as indicated below.

Operation

6

Summary of Contents for Eco Optidrive ODV-3-641100-3F12-MN

Page 1: ...3 4 5 6 7 User Guide OPT 2 ETHEG IN Ethernet IP Interface General Information Introduction Mechanical Installation Electrical Installation Drive Parameter Settings Operation Technical Data 2 1 3 4 5 6...

Page 2: ...ensions and Weight 8 4 Electrical Installation 9 4 1 Overview 9 4 2 Connection Diagram 9 4 3 Grounding 9 5 Drive Parameter Settings 10 5 1 Overview 10 5 2 Optidrive Communication Parameters Overview 1...

Page 3: ...ion or commissioning The manufacturer also accepts no liability for damage or consequences resulting from inappropriate negligent or incorrect installation incorrect adjustment of the operating parame...

Page 4: ...2006 42 EC Safety of Machinery In particular the machine manufacturer is responsible for ensuring that the electrical equipment complies with EN60204 1 and providing a disconnecting device which must...

Page 5: ...rt 2 Module Status LED Network Status LED Serial Port 1 Serial Port 2 Ethernet Port 1 COMM LED Indicator P1 Ethernet P2 D1 MS NS D2 2 2 Labelling The OPT 2 ETHEG IN has two labels as shown below Top L...

Page 6: ...tion Steady Off Not powered no IP address Steady Green Online one or more connections active Flashing Green Online no connections active Flashing Red Connection timeout Steady Red Duplicate IP Flashin...

Page 7: ...h TX RX P2 Speed Steady Yellow 100Mbps link active Steady Off 10Mbps or No link P2 Link Activity Steady Green Valid Link Steady Off No Link TX RX 2 5 Power up sequence At power up the following LED te...

Page 8: ...interface is intended for mounting inside a control cabinet adjacent to the drive The unit should be mounted in a vertical position only on a flat flame resistant vibration free mounting The unit mus...

Page 9: ...ich also supplies the power to the OPT 2 ETHEG IN from the 24 Volt output of the Optidrive 4 2 Connection Diagram COMM ERROR P1 Ethernet P2 D1 MS NS D2 GND Optional Drive Keypad OPT 2 OPORT IN OPT 2 O...

Page 10: ...al must still be provided at the control terminals digital input 1 P 14 Extended Menu Access code 0 65535 0 Enables access to Extended and Advanced Parameter Groups This parameter must be set to the v...

Page 11: ...Then Trip 2 Ramp to Stop Only No Trip 3 Run at Preset Speed 8 P5 07 Fieldbus Ramp Control 0 1 0 0 Disabled Ramps are control from internal drive parameters P1 03 and P1 04 1 Enabled Ramps are controll...

Page 12: ...ldbus In order for this option to be used P9 38 must be set to 1 and the PID User setpoint must not be utilised within the PLC function 2 User Register 3 The value received by the drive in PDI 3 is tr...

Page 13: ...s connection using one of the two methods shown below This allows process data to be cyclically exchanged between the Ethernet IP master and a connected Optidrive via the OPT 2 ETHEG IN 6 3 1 Method 1...

Page 14: ...ype Point to Point Length Fixed Transfer Format Pure data 6 4 Process Data Exchange All Optidrives support a 4 word input 4 word output process data exchange to allow control and monitoring of the dri...

Page 15: ...g commanded value 500 the drive torque setpoint will be 50 0 6 5 5 Drive Ramp Times When the drive parameters are configured to allow control of the drive ramp times through fieldbus this register sp...

Page 16: ...evant fault information for each code Refer to the relevant drive User Guide for further information on the cause and possible solutions for each fault No Fault Description 00 No fault 01 Brake channe...

Page 17: ...ixed function or configurable function depending on the drive in use The possible functions are described below 6 6 5 Output Current Output current data has one decimal place e g a returned value of 1...

Page 18: ...efer to the drive documentation for further information 6 7 OPT 2 ETHEG IN Web Server The OPT 2 ETHEG IN web server interface can be accessed at via the IP address or host name Default IP address 192...

Page 19: ...applied To commit values press Set Module will reboot if data is valid otherwise an error status will be displayed Status State Indication Data Submitted Data has been submitted to OPT 2 ETHEG IN awai...

Page 20: ...rameters may be accessed using unconnected or Class 2 3 connection via following methods Status LED Function 0x0F Parameter 0x0E Get_Attribute_Single Individual parameter Read Write Instance 1 holding...

Page 21: ...Tool 6 9 2 Configure the IP Address Configure the OPT 2 ETHEG IN IP address using either the OPT 2 ETHEG IN Web Server see section 6 7 3 Network Settings or using RSLinx as follows Launch RSWho from R...

Page 22: ...1 Environmental Ambient Temperature Storage and Transportation 40 60 C 40 140 F Operating 10 50 C 14 122 F UL approved 40 50 C 104 122 F Without UL approval Maximum Altitude Operating 1000m UL approv...

Page 23: ...Version 1 10 Optidrive ODP 2ETHEG IN 23 www invertekdrives com...

Page 24: ...82 EIPMN IN_V1 10b 82 EIPMN IN_V1 10 Invertek Drives Ltd Offa s Dyke Business Park Welshpool Powys SY21 8JF United Kingdom Tel 44 0 1938 556868 Fax 44 0 1938 556869 www invertekdrives com...

Reviews: