6.7.4. Drive Identity

Data is read from the Drive.
If the Drive does not support this functionality then the following data is required:

  

Vendor Name: ‘Unknown Modbus Device’

  

Product Code: Empty

  

Version Number: Empty.

6.8. Drive parameter access

6.8.1. Overview

The OPT-2-ETHEG-IN is a Modbus translator device. This means that all data accessible from the drives Modbus RTU interface may 
also be accessed via the Ethernet/IP interface.
For details of the relevant Modbus registers available for each drive, refer to the drive documentation.

6.8.2. Supported Ethernet/IP Classes

The OPT-2-ETHEG-IN supports the following Ethernet/IP classes to allow communication with a connected Drive:

  

0x01 Identity

  

0x02 Message Router

  

0x04 Assembly

  

0x06 Connection manager

  

0x0F Parameter

  

0x44 Modbus.

Drive parameters may be accessed using unconnected or Class 2/3 connection via following methods:

Status LED

Function

0x0F Parameter

0x0E Get_Attribute_Single

Individual parameter Read/Write 
Instance 1 = holding register 0

0x10 Set_Attribute_Single

0x44 Modbus Object

0x4E Read_Holding_Registers

Multiple parameter Read/Write 
Instance 1 = holding register 0

0x50 Write_Holding_Registers

0x04 Assembly Object

0x18 Get_Member
0x19 Set_Member

NOTE

 

All Optidrives support the following Modbus RTU Commands:

  

0x03 Read Multiple Holding Registers.

  

0x06 Write Single Holding Register.

Sequential blocks of available Modbus Registers may be read either by using multiple 0x0E Get_Attribute_Single commands or by 
using a single 0x4E Read_Holding_Registers to read multiple register values in a single command.
In order to write parameter values to the drive, each individual parameter must be written in a singularly, either using 0x10 Set_
Attribute_Single or 0x50 Write_Holding_Registers. It is not possible to write multiple parameters in a single command.

Operation

6

Summary of Contents for Eco Optidrive ODV-3-641100-3F12-MN

Page 1: ...3 4 5 6 7 User Guide OPT 2 ETHEG IN Ethernet IP Interface General Information Introduction Mechanical Installation Electrical Installation Drive Parameter Settings Operation Technical Data 2 1 3 4 5 6...

Page 2: ...ensions and Weight 8 4 Electrical Installation 9 4 1 Overview 9 4 2 Connection Diagram 9 4 3 Grounding 9 5 Drive Parameter Settings 10 5 1 Overview 10 5 2 Optidrive Communication Parameters Overview 1...

Page 3: ...ion or commissioning The manufacturer also accepts no liability for damage or consequences resulting from inappropriate negligent or incorrect installation incorrect adjustment of the operating parame...

Page 4: ...2006 42 EC Safety of Machinery In particular the machine manufacturer is responsible for ensuring that the electrical equipment complies with EN60204 1 and providing a disconnecting device which must...

Page 5: ...rt 2 Module Status LED Network Status LED Serial Port 1 Serial Port 2 Ethernet Port 1 COMM LED Indicator P1 Ethernet P2 D1 MS NS D2 2 2 Labelling The OPT 2 ETHEG IN has two labels as shown below Top L...

Page 6: ...tion Steady Off Not powered no IP address Steady Green Online one or more connections active Flashing Green Online no connections active Flashing Red Connection timeout Steady Red Duplicate IP Flashin...

Page 7: ...h TX RX P2 Speed Steady Yellow 100Mbps link active Steady Off 10Mbps or No link P2 Link Activity Steady Green Valid Link Steady Off No Link TX RX 2 5 Power up sequence At power up the following LED te...

Page 8: ...interface is intended for mounting inside a control cabinet adjacent to the drive The unit should be mounted in a vertical position only on a flat flame resistant vibration free mounting The unit mus...

Page 9: ...ich also supplies the power to the OPT 2 ETHEG IN from the 24 Volt output of the Optidrive 4 2 Connection Diagram COMM ERROR P1 Ethernet P2 D1 MS NS D2 GND Optional Drive Keypad OPT 2 OPORT IN OPT 2 O...

Page 10: ...al must still be provided at the control terminals digital input 1 P 14 Extended Menu Access code 0 65535 0 Enables access to Extended and Advanced Parameter Groups This parameter must be set to the v...

Page 11: ...Then Trip 2 Ramp to Stop Only No Trip 3 Run at Preset Speed 8 P5 07 Fieldbus Ramp Control 0 1 0 0 Disabled Ramps are control from internal drive parameters P1 03 and P1 04 1 Enabled Ramps are controll...

Page 12: ...ldbus In order for this option to be used P9 38 must be set to 1 and the PID User setpoint must not be utilised within the PLC function 2 User Register 3 The value received by the drive in PDI 3 is tr...

Page 13: ...s connection using one of the two methods shown below This allows process data to be cyclically exchanged between the Ethernet IP master and a connected Optidrive via the OPT 2 ETHEG IN 6 3 1 Method 1...

Page 14: ...ype Point to Point Length Fixed Transfer Format Pure data 6 4 Process Data Exchange All Optidrives support a 4 word input 4 word output process data exchange to allow control and monitoring of the dri...

Page 15: ...g commanded value 500 the drive torque setpoint will be 50 0 6 5 5 Drive Ramp Times When the drive parameters are configured to allow control of the drive ramp times through fieldbus this register sp...

Page 16: ...evant fault information for each code Refer to the relevant drive User Guide for further information on the cause and possible solutions for each fault No Fault Description 00 No fault 01 Brake channe...

Page 17: ...ixed function or configurable function depending on the drive in use The possible functions are described below 6 6 5 Output Current Output current data has one decimal place e g a returned value of 1...

Page 18: ...efer to the drive documentation for further information 6 7 OPT 2 ETHEG IN Web Server The OPT 2 ETHEG IN web server interface can be accessed at via the IP address or host name Default IP address 192...

Page 19: ...applied To commit values press Set Module will reboot if data is valid otherwise an error status will be displayed Status State Indication Data Submitted Data has been submitted to OPT 2 ETHEG IN awai...

Page 20: ...rameters may be accessed using unconnected or Class 2 3 connection via following methods Status LED Function 0x0F Parameter 0x0E Get_Attribute_Single Individual parameter Read Write Instance 1 holding...

Page 21: ...Tool 6 9 2 Configure the IP Address Configure the OPT 2 ETHEG IN IP address using either the OPT 2 ETHEG IN Web Server see section 6 7 3 Network Settings or using RSLinx as follows Launch RSWho from R...

Page 22: ...1 Environmental Ambient Temperature Storage and Transportation 40 60 C 40 140 F Operating 10 50 C 14 122 F UL approved 40 50 C 104 122 F Without UL approval Maximum Altitude Operating 1000m UL approv...

Page 23: ...Version 1 10 Optidrive ODP 2ETHEG IN 23 www invertekdrives com...

Page 24: ...82 EIPMN IN_V1 10b 82 EIPMN IN_V1 10 Invertek Drives Ltd Offa s Dyke Business Park Welshpool Powys SY21 8JF United Kingdom Tel 44 0 1938 556868 Fax 44 0 1938 556869 www invertekdrives com...

Reviews: