5.2 Vertical Pipe Arrangement 

The ITABAR Sensor for flow measurement of 
steam and satured steam can be installed in vertical 
pipe runs at any location, however, the instrument 
connections have to be located in the same 
horizontal plain (see Figure 4). 
 

Fig. 4:  Installation in vertical pipe 

 

5.3 Horizontal Pipe Arrangement 

For flow measurements in a horizontal pipe the 
ITABAR Sensor must be installed in the lower half 
of the pipe circumference; the connections to the 
instruments have to be located below the pipe axis. 
 

 

Fig. 5:  Installation in horizontal pipe 

 

5.4 Misalignment 

The ITABAR Sensor operates on the basis of 
simple physical principles. 
The sensor is not affected by being slightly out of 
alignment. 
The influence on the accuracy of the measurements 
is negligible as long as the limits indicated in 
Figures 6, 7 and 8 are not exceeded. 
 
 

 

Fig. 6 side view 
 

 

Fig. 7 top view 

 

 

Fig. 8 front view

Summary of Contents for Analog Node

Page 1: ...Installation of the ITABAR Sensor 6 6 1 Installation of Type FTMD25 6 6 2 Installation of Type FTMD26 7 6 3 Insertion Procedure for FTMD 8 6 4 Retract Procedure for FTMD 8 7 Installation of the Attach...

Page 2: ...ept for drilling and welding equipment These instructions call for the use of a Mueller DH 5 drilling machine or equivalent which is rated for 80 bar at 35 C with a maximum temp erature of 120 C This...

Page 3: ...1 Determination of Pipe Arrangement For design reasons the pipe arrangement at the installation location has to be known before the sensor is manufactured For horizontal pipe arrangements the instrume...

Page 4: ...flow measurements in a horizontal pipe the ITABAR Sensor must be installed in the lower half of the pipe circumference the connections to the instruments have to be located below the pipe axis Fig 5...

Page 5: ...eous installation location As a general rule regulating valves throttle valves and gate type valves should be installed behind the sensor Note If the recommended straight pipe run lengths are not avai...

Page 6: ...l flanged nipple 8 Drill through the pipe wall in accordance with the instructions supplied with the drilling machine For type FTMD 25 35mm 9 Withdraw the drill past the Flo Tap unit isolating valve C...

Page 7: ...one end around the installed weld socket 4 Wrap the other end of the cord around the pipe so that it forms a loop around the pipe Mark the half way point of the pipe circumference on the pipe 5 Now dr...

Page 8: ...h temperature gland additional adjustment may be required at this time 8 6 10 3 4 Fig 13 retracted Flo Tap Sensor 5 Connect instrument lines to the instrument valves and to the appropriate meter recor...

Page 9: ...followed by a zero point error We recommend you to install the differential pressure lines close together connect hi and lo line heat conducting to maintain equal temperature Attention The differenti...

Page 10: ...ng signal The ITABAR sensors are head measuring devices and will not accurately measure two phase flow ITABAR Flow Sensors for low pressure steam have condensate pots in which the condensate water lin...

Reviews: