-  If the mA- signal have big bounce, the valves A 
 

and B must be closed and the system must be 

 vented 

again. 

 

10. Preventive 

Maintenance 

ITABAR sensors are intensive to dirt and soil 
build-up and therefore nearly maintenance-free. 
However, if cleaning is required: 
- remove the sensor 
- flush completely 
- hand clean with a soft wire brush 
 
 

11. Trouble 

shooting 

If, after start-up of the ITABAR sensor, any 
measuring errors accur, they may possibly be 
corrected quite easily: 
 

Error: 

No differential pressure indication. 
 

Correction: 

Check whether all instrument valves to the 

p-transmitter are opened. 

The valve E must be closed (only for zero). 
Check the alignment of the sensor with the pipe. 
The arrow on the sensor must point exactly in the 
flow direction (downstream). 
 

Note:

 

Two-Phase flow or alternating phase flow will 
cause an erratic spiking signal. The ITABAR 
sensors are head-measuring devices and will not 
accurately measure two-phase flow. 
 
ITABAR-Flow-Sensors for low pressure steam 
have condensate pots in which  the condensate 
water line is 25mm higher than the flange 
connection of the sensor is installed precise 
horizontal. 
That means that water column of static and 
dynamic pressure side must have the same high to 
guarantee zero differential pressure when steam is 
not flowing. 
The arrangment of higher condensate line than 
sensor connection has been done to secure the exact 
water column onto the d.p. transmitter. 
During steam flow the steam will move into the 
condensate pots and will condensate to water. The 
water level above line 1 will flow back into the 
sensor and change again into steam. The steam 
pressure from dynamic and static connection is 
pressing onto the water level and the difference at 
these pressures will be transmitted into mA-signal 
through the differential pressure transmitter. 
Please note that 25mm deviation in the line of 1 
will give 25mm WG differential pressure. 
 

 
 

10 

Summary of Contents for Analog Node

Page 1: ...Installation of the ITABAR Sensor 6 6 1 Installation of Type FTMD25 6 6 2 Installation of Type FTMD26 7 6 3 Insertion Procedure for FTMD 8 6 4 Retract Procedure for FTMD 8 7 Installation of the Attach...

Page 2: ...ept for drilling and welding equipment These instructions call for the use of a Mueller DH 5 drilling machine or equivalent which is rated for 80 bar at 35 C with a maximum temp erature of 120 C This...

Page 3: ...1 Determination of Pipe Arrangement For design reasons the pipe arrangement at the installation location has to be known before the sensor is manufactured For horizontal pipe arrangements the instrume...

Page 4: ...flow measurements in a horizontal pipe the ITABAR Sensor must be installed in the lower half of the pipe circumference the connections to the instruments have to be located below the pipe axis Fig 5...

Page 5: ...eous installation location As a general rule regulating valves throttle valves and gate type valves should be installed behind the sensor Note If the recommended straight pipe run lengths are not avai...

Page 6: ...l flanged nipple 8 Drill through the pipe wall in accordance with the instructions supplied with the drilling machine For type FTMD 25 35mm 9 Withdraw the drill past the Flo Tap unit isolating valve C...

Page 7: ...one end around the installed weld socket 4 Wrap the other end of the cord around the pipe so that it forms a loop around the pipe Mark the half way point of the pipe circumference on the pipe 5 Now dr...

Page 8: ...h temperature gland additional adjustment may be required at this time 8 6 10 3 4 Fig 13 retracted Flo Tap Sensor 5 Connect instrument lines to the instrument valves and to the appropriate meter recor...

Page 9: ...followed by a zero point error We recommend you to install the differential pressure lines close together connect hi and lo line heat conducting to maintain equal temperature Attention The differenti...

Page 10: ...ng signal The ITABAR sensors are head measuring devices and will not accurately measure two phase flow ITABAR Flow Sensors for low pressure steam have condensate pots in which the condensate water lin...

Reviews: