Intesis
Box
®
KNX
– IR Universal AC
User's manual r1.0 eng
© Intesis Software S.L.U. - All rights reserved
This information is subject to change without notice
IntesisBox
®
is a registered trademark of Intesis Software SLU
URL
Email
tel
http://www.intesisbox.com
[email protected]
+34 938047134
21 / 48
Fan Speed
All the parameters in this section are related with the Fan Speed properties and communication objects.
Figure 5.9
Fan Speed parameters
5.4.1 DPT object type for fan speed
With this parameter is possible to change de DPT for the
Control_ Fan Speed
and
Status_ Fan Speed
byte-
type
communication objects. Datapoints Scaling (DPT_5.001) and Enumerated (DPT_5.010) can be selected.
o
When
“Enumerated [DPT 5.010]”
is selected,
Control_ Fan Speed
and
Status_ Fan Speed
communication
objects
for this DPT will appear. Also, depending on the number of fan speeds selected, these objects will
be different.
The first fan speed will be selected if a
“1”
is sent to the
Control_
object. The second fan speed will be
selected sending a
“2”
and so on.
The
Status_
object will always return the value for the fan speed selected.
Important: In both cases if a
“0” value is sent to the Control_ object, the minimum fan speed will be
selected. If a value bigger than
“2” (in case of 2 speeds) or bigger than “3” (in case of 3 fan speeds)
is sent to the Control_ object, then the maximum fan speed will be selected.
o
When
“Scaling [DPT 5.001]”
is selected,
Control_ Fan Speed
and
Status_ Fan Speed
communication
objects
for this DPT will appear. Also, depending on the number of fan speeds selected, these objects will
be different.