5.7.2 Set Point - Enable limits on Control_ Setpoint obj
This parameter enables to define temperature limits for the
Control_ Setpoint Temperature
object.
o
If set to
“no”
the setpoint temperature limits for the
Control_ Setpoint Temperature
object will be the default:
16ºC for the lower limit and 32ºC for the upper limit.
o
If set to
“yes”
it is possible to define temperature limits for the
Control_ Setpoint Temperature
object.
➢
Control_ Set Temp Lower limit (ºC)
This parameter lets to define the lower limit for the setpoint temperature.
➢
Control_ Set Temp Upper limit (ºC)
This parameter lets to define the upper limit for the setpoint temperature.
Important: If a setpoint temperature above the upper defined limit (or below the lower defined limit) is sent
through the Control_ Setpoint Temperature object, it will be ALWAYS applied the limit defined.
Important: When limits are enabled, any setpoint temperature sent to the AC (even through scenes, special
modes, etc.) will be limited.
5.7.3 Set Point - Periodic sending time
This parameter lets you change the interval of time (in seconds, from 0 to 255) at the end of which the AC
setpoint temperature is sent to the KNX bus. For a
“0”
value, the AC setpoint temperature will ONLY be sent
on change. The AC setpoint temperature is sent through the communication object
Status_ AC Setpoint Temp.
5.7.4 Ambient -
Transmission of “Status_ AC Ret Temp”
This parameter lets to you choose if the AC return temperature will be sent
“only cyclically”
,
“only on change”
or
“cyclically and on change”
. The AC return temperature is sent through the communication object
Status_
AC Return Temp.
5.7.5 Ambient - Periodic sending time
This parameter will only be available for the
“only cylically”
and
“cyclically and on change”
options, and lets
you change the interval of time (in seconds, from 1 to 255) at the end of which the AC return temperature is
sent to the KNX bus.