Important: If any preset value is configured as
“(unchanged)”, the execution of this scene will not
change current status of this feature in the AC unit.
Important: When a scene is executed, Status_ Current Scene object shows the number of this scene.
Any change in previous items does Status_ Current Scene show
“No Scene”. Only changes on items
marked as
“(unchanged)” will not disable current scene.
Enable use of Open Window
This parameter shows/hides the
Control_ Window Contact Input
communication object which lets you Start/Stop
a timeout to switch off the indoor unit.
o
If set to
“no”
the object will not be shown.
o
If set to
“yes”
the
Control_ Window Contact Input
object will appear. If a
“1”
value is sent to this object,
and the indoor unit is already turned on, the switch-off timeout will begin. If a
“0”
value is sent to this object,
the switch-off timeout will stop.
➢
Input Object
This parameter lets you choose between the datapoints
0-Open / 1-Closed Window [DPT_1.009]
and
0-Stop / 1-Start Timeout [DPT_1.010]
for the
Control_ Switch Off Timeout
.
➢
Timeout (min)
This parameter lets you select how much time (in minutes) to wait before switching off the indoor unit.
➢
Reload last Value
If set to
“no”
, once the switch-off timeout is stopped, any value will be reloaded.
If set to
“yes”
, once the switch-off timeout is stopped, the last On/Off value sent will be reloaded.
•
If a
“1”
value is sent to
the
Control_ Window Contact Input
object after the timeout period, the
indoor unit will
turn on
.