Chapter 4: Menu reference
110
CDC4 Door Controller Installation and Programming Manual
In each LED field, enter an area number to select an area.
Alarm control tab
See “Alarm control” on page 59 for more information.
IN alarm control
This field determines whether the door’s IN readers can be used to control the
alarm system (arm/disarm) and if so, the way in which it can be controlled:
• No Alarm control: It is not possible to arm/disarm via the reader.
• Alarm control on 1st badge: Presentation of a valid card at the reader will
disarm the system on the first badge. (Three badges are still required to arm
system).
• Alarm control on 3rd badge: Presentation of a valid card three times at the
reader will arm/disarm system.
• Alarm control always (off = IN, on = OUT): Presentation of a valid card at the
IN reader will disarm the system and presentation of a valid card at the OUT
reader will arm the system.
• Alarm control via region count: The last user leaving the panel region
assigned to door automatically sets the area, and the first user entering the
region unsets it. This option is similar to option “Alarm control on 1st badge”,
but works only for the last and the first user in the region.
See “Regions” on
page 54 for more details.
Note:
Panel regions must be configured in Panel > Regions menu. See
Advisor Advanced ATSx500A(-IP) Installation and Programming Manual
for
more details on panel regions.
OUT alarm control
This field determines whether the door’s IN readers can be used to control the
alarm system (set/unset) and if so, the way in which it can be controlled. The
options are the same as for the IN alarm control field. See the “IN alarm control”
section above.
IN denied when set
When set to On, a valid card or PIN will not open a door if any of the areas
assigned to the door are set.
OUT denied when set
When set to On, a valid card or PIN will not open a door if any of the areas
assigned to the door are set.
Summary of Contents for CDC4
Page 1: ...CDC4 Door Controller Installation and Programming Manual P N 466 5478 REV D ISS 29OCT19 ...
Page 86: ...Chapter 3 Programming 80 CDC4 Door Controller Installation and Programming Manual ...
Page 120: ...Chapter 4 Menu reference 114 CDC4 Door Controller Installation and Programming Manual ...
Page 136: ...130 CDC4 Door Controller Installation and Programming Manual ...