Planning the Installation
California State Fire Marshall Listed
Installations
The California State Fire Marshall listing has been
approved.
Planning the Installation
This section describes system capabilities to help you get
familiar with the system. “Appendix A” provides planning
sheets with tables that let you record the hardware and pro-
gramming configuration of the system. Fill in all necessary
information ahead of time to help prepare for the installa-
tion, and retain for your records.
Note
It is recommended that no more than 132 wireless sen-
sors be used in any individual Advent system.
If 2 or more Advent systems are in close proximity to
each other, the total number of wireless sensors for all
systems must not exceed 132.
Panel Types
To plan the installation, find your specific panel type below.
The panel type will help determine the system capabilities
(dependent upon devices used).
Panel Components
Before installing devices and making wiring connections,
familiarize yourself with the main panel components. Fig-
ure 1 shows the main component locations for the circuit
board.
Figure 1. Circuit Board Main Components
Panel Terminals
Table 7 describes each of the control panel terminals. Typi-
cal system wiring diagrams are provided on the last page of
this manual.
Note
A) Class 2, Class 3, and power-limited fire alarm circuits
must be installed using FPL, FPLR, FPLP, or substitute
cable permitted by the National Electrical Code ANSI/
NFPA 70. Wire that extends beyond the cable jacket
must be separated from all other conductors by a mini-
mum of 1/4-inch or by a nonconductive barrier.
OR
(B) Class 2, Class 3, and power-limited fire alarm circuit
conductors must be installed as Class 1 or higher cir-
cuits.
Table 6: Advent Panel Types
Part Number
Description
Partiti
ons/
A
re
as
U
ser
s
Inp
u
t Zon
es
250Z, 60-562-01
Commercial Burglary Panel.
UL Listings include 365,
609, 985, 1023, 1610 and
1635. Gray enclosure.
8
250 250
132Z, 60-562-04
4
100
132
250Z, 60-562-05
Home Nav Panel. UL List-
ings include 985, 1023 and
1635. White enclosure.
8
250 250
132Z, 60-562-02
4
100
132
CONTROL PANEL
CIRCUIT BOARD
TERMINAL STRIP
8543G05B.DSF
OPTIONAL
EXPANSION
SNAPCARD
CONNECT-
ORS
OPTIONAL
EXPANSION SNAPCARD
SUPERBUS
CONNECT-
ORS (2)
INCOMING PHONE LINE TEST
LUGS (TIP/RING)
PHONE JACK
(DB-8 CORD)
POWER
LED
+
–
BACKUP
BATTERY
LUGS
MEMORY
CLEAR
BUTTON
Table 7: Panel Terminal Strip Connections
Terminal
Name
Used for
1
24 VAC
24 VAC, 100 VA power transformer
connection.
2
24 VAC
24 VAC, 100 VA power transformer
connection.
3
GND
Common ground connection for sirens,
general purpose outputs 1-6, etc.
4
+12 VDC
Interior bell (+), and misc. DC power
supply, 12 VDC @ 5.0A maximum load
(includes Bus 1 and Bus 2 headers) Cur-
rent limited.
5
INT
BELL
Negative (-) side of bell connection. 12
VDC @ 150mA (sink) maximum. Posi-
tive (+) side to +12 VDC terminal 4.
Connect multiple interior bells in
parallel
1
.
6
EXT
SIREN
RTN
Negative (-) external siren drive return
connection
1
.
7
EXT
SIREN
OUT
Positive (+) external siren power output
connection. 30 VDC @ 2.5A maximum
load
1
. Or 70 VAC @ 500 mA maximum.
8
EXT
SIREN IN
Positive (+) external siren drive input
connection. 30 VDC @ 2.5A or 70 VAC
@ 500 mA maximum. Normally con-
nected to +12 VDC terminal 4 or other
siren voltage source
1
.
9
VOICE
SIREN
One side of voice siren (speaker) con-
nection. Other side to VOICE SIREN
terminal 10
2
.
10
VOICE
SIREN
One side of voice siren (speaker) con-
nection. Other side to VOICE SIREN
terminal 9
2
.
11
ZONE
COM
Common return connection for general
purpose inputs 1–7, sensors, etc.
12
GPI/O 1
General purpose hardwire input. GPI/Os
1–6 can be programmed for use as a
hardwire contact input (2.0K ohm EOL
resistor) or a control relay driver output
(200 mA sink at 12 VDC maximum).
13
GPI/O 2
14
GPI/O 3
15
GPI/O 4
16
GPI/O 5
17
GPI/O 6
18
INPUT 7
Hardwire input 7.
19
Unused