42
Commercial Burglary and Home Navigator System
Programming the Panel
Miscellaneous Settings
AC Stable Time
17036
Default = 8 Seconds
This setting allows you to specify the time (in seconds) that AC
power must be lost or restored before a trouble, or trouble restoral
is generated. These events are not reported immediately (see
17041).
To Set AC Stable Time:
1. Once in program mode enter the item number.
2. Enter the desired time (0–200) and press #.
AC Frequency
17123
Default = 0 (60 Hz)
This setting allows you to choose the AC frequency that is power-
ing the panel.
To Set the AC Frequency:
1. Once in program mode enter the item number.
2. Enter 1 for 50 Hz (off), or 0 for 60 Hz (on).
3. Press # to apply the new setting.
Latitude Adjustment
17110
Default = 0 Degrees
This setting allows you to specify the latitude (in degrees) where
the panel is located. This information is then used by the panel
when automatically adjusting sunrise/sunset schedules.
To Set the Latitude:
1. Once in program mode enter the item number.
2. Enter the desired latitude (0–65) and press #.
On Premises Pager ID 1
17060
On Premises Pager ID 2
17061
Defaults = 0000000
This setting allows you to specify 7-digit pager IDs that will iden-
tify the 2 different pager groups in a local paging network.
To Specify On Premises Pager IDs:
1. Once in program mode enter the item number.
2. Enter the desired 7-digit (0–9) pager ID and press #.
Downloader Account Number
17109
Default = 00000000
The Downloader Account Number is used to identify the panel to
Advent Downloader.
To Enter a Downloader Account Number:
1. Once the desired item number has been entered the current
account number will be displayed.
2. Enter an 8-digit number (0–9) and press #.
Reset Panel
50001
Default = NA
This setting allows you to clear any errors the panel may have by
“rebooting” the system. All settings will remain unchanged.
To Reset the Panel:
1. Enter the installer code.
2. Enter
50001
.
3. Press
99
and then #. Wait about a minute for the panel to reset.
Software/Hardware Version
50003
Default = NA
This setting allows you to view and identify panel hardware and
software version.
To View System Version:
1. Enter the installer code.
2. Enter
50003
. The panel displays
SYSTEM
ID
nnnnnnnn
VERSION
n.nn nnn.nnn
PANEL
TYPE
n
SNAPCARD
n n.
Panel Type Formats:
0—Commercial Burg-250
5—not used
1—Home Navigator-132
6—not used
2—Commercial Fire-250
7—Commercial Burg-132
3—Home Navigator-250
8—Commercial Fire-132
4—not used
SnapCard Type Formats:
0—none
5—quad smoke loop
1—not used
6—not used
2—NAC
7—not used)
3—8Z input
8—4z input, 2 relay output
4—4 relay output
Clear History Buffer
50004
Default = NA
This setting allows you to clear the history buffer.
To Clear History Buffer:
1. Enter the installer code.
2. Enter
50004
. The display shows
HISTORY
BUFFER
CLEARED
.