![Interlogix Advent Installation Instructions Manual Download Page 12](http://html.mh-extra.com/html/interlogix/advent/advent_installation-instructions-manual_2077278012.webp)
10
Commercial Burglary and Home Navigator System
Installing the System
Figure 12. Connecting a RS-232 Automation Module
Voice Siren 25/70 Volt Converter Card (60-773)
*
Mount the card in the panel cabinet in the area shown in
Figure 5, and as described in the specific Installation
Instructions. Wire the card to the panel and speakers as
shown in Figure 14.
Note
70 volt wiring and supervision is shown. For 25 volt wir-
ing, connect speakers to COMMON and 25V terminals,
then jump +SUPERVISION to 25V terminal.
Figure 13. Connecting the Voice Siren 25/70 Volt
Converter Card
Note
Separate in and out conductors must be used at each
speaker. Do not loop a single wire around each terminal.
Connecting Detection Devices to Panel
Zone Inputs
Connecting Intrusion Detection Devices
For information on programming and configuring detection
devices, please see “Zone Settings” on page 22. For infor-
mation on mounting and installing devices please see the
Installation Instructions included with the device.
General Inputs
Figure 15 shows the typical wiring for N/C and N/O door/
window intrusion detection.
Figure 14. Installing Intrusion Detection Devices
Connecting 2-Wire Smoke Detectors
Panel terminals 21 and 22 are set up to accept the following
12 VDC 2-wire smoke detectors.
q
System Sensor models 2100S, 2100TS, 2100D, 2100TD,
2400, or 2400TH.
q
Sentrol (ESL) models 429AT, 521B, or 521BXT.
Panel terminals 21 and 22 can handle up to 20 smoke detec-
tors with 120 uA maximum idle current per detector. Maxi-
mum total loop current allowed in alarm condition is
100 mA.
Connect one or more 2-wire smoke detectors to the panel as
shown in Figure 16.
* Not investigated by UL.
S U P E R B U S 2 0 0 0
A U T O M A T I O N M O D U L E
T E R M I N A L S T R I P
8 8 4 5 G 1 0 A . D S F
B L A C K ( G N D )
W H I T E ( B U S B )
G R E E N ( B U S A )
R E D ( + 1 2 V D C )
2
B U S
A
1
+ 1 2
V D C
3
B U S
B
4
G N D
P A N E L S U P E R B U S
W I R I N G H A R N E S S 4 9 - 4 6 2
9715g03d.dsf
UL-LISTED SPEAKERS
(PARALLEL)
PANEL
TERMINALS
COM-
MON
25V
70V
+
SUPER-
VISION
4 OHMS
10
9
VOICE
SIREN
VOICE
SIREN
VOICE SIREN CONVERTER
CARD TERMINALS
2K OHM 5 WATT
EOL RESISTOR
ASSEMBLY 49-482
(LOCATE AT
LAST DEVICE)
+
-
10
11
12
11
16
17
PANEL TERMINALS
I/O
C
O
M
ZO
NE 1*
I/O
C
O
M
ZO
NE 5*
*
ZO
NE 6*
*
NORMALLY
OPEN
(N/O)
CONTACTS
IN PARALLEL
2k OHM
EOL RESISTOR
49-467
(LOCATE AT
LAST DEVICE)
NORMALLY
CLOSED
(N/C)
CONTACTS
IN SERIES
*OR TO ANY GP I/O PROGRAMMED AS A NORMALLY
CLOSED INPUT.
Summary of Contents for Advent