3
Commercial Burglary and Home Navigator System
Special Installation Requirements
(60-783) for use with a listed printer.
q
SuperBus 2000 Dual Phone Line Module (60-768) for
expansion to primary and secondary phone line report-
ing.
System Setup and Programming
The system Feature Numbers shall be set as follows in
UL 1023 listed systems:
Central Station Burglar-Alarm System Units (UL 1610)
Basic system using Commercial Burglary (60-562-01 or
60-562-04) Control Panel, plus:
q
Hardwire Magnetic Contact (13-068 or 13-071).
The basic system may also include:
q
SuperBus 2000 Commercial RF Transceiver (60-821)
for use with listed wireless signaling devices.
q
Wireless Learn Mode Door/Window Sensor (60-362).
q
SuperBus 2000 Printer or Automation Module
(60-783) for use with a listed printer.
q
SuperBus 2000 Dual Phone Line Module (60-768) for
reporting to multiple phone lines.
System Setup and Programming
The system Feature Numbers shall be set as follows in
UL 1610 listed systems:
Digital Alarm Communicator System Units (UL 1635)
Same as UL 1610 plus:
q
A UL Listed Exterior Siren.
Central Station Reporting
The panel has been tested with the following central station
receivers using Contact ID reporting format:
q
ITI CS-5000 Central Station Receiver.
q
Sur-Gard Central Station Receiver with models
SG-DRL2A and SG-CPM2.
q
Radionics Model (D6600).
Table 4: UL 1023 Listed System Settings
Feature No.
Feature
Required Setting
xx002
Siren Sound Time
6 min. minimum
xx003
Entry Delay
45 sec. maximum
xx004
Exit Delay
60 sec. maximum
yy004
Communication Format
0 Contact ID
xx088
Report Partition Events
1-On
xx092
Auto Forced Arming
0-Off
xx097
Exterior Siren Arming Verifi-
cation
0-Off
xx102
Exit Delay Reset
0-Off
xx108
Local Trouble Annunciation
at LTIME.
1-On
17036
AC Stable Time
90 sec. maximum
17041
AC Report Delay
6-12 hours
17049
RF Supervisory Time
4 hours
17069
No Phone Line
0-Off
17072
Enable RF Jam Detect
1-On
17073
Automatic Panel Backup Bat-
tery Test Interval
1-4 hours
17076
Commercial/Residential
0-Off Residential
17078
Detect Receiver Failure
1-On
17079
Alarm Messages Play at High
Volume
1-On High
17096
Report System Events
1-On
47004
#2-Supervisory Time Zone
Attribute (all sensors)
#4-Hardwire Smoke Verify
Zone Attribute
A (set to 4 hrs. in
Feature 17049)
0-No
xx = Two digit partition number.
yy = Two digit non-pager phone number.
Table 5: UL 1610 Listed System Settings
Feature No.
Feature
Required Setting
xx002
Siren Sound Time
16 min., minimum
xx003
Entry Delay
45 sec., maximum
xx004
Exit Delay
60 sec., maximum
yy004
Communication Format
0 Contact ID
xx088
Report Partition Events
1-On
xx092
Auto Forced Arming
0-Off
xx097
Exterior Siren Arming Verifi-
cation
0-Off
xx098
Local Closing Report Verifi-
cation
1-On
xx102
Exit Delay Reset
0-Off
xx108
Local Trouble Annunciation
at LTIME.
1-On
17034
Auto Phone Test Frequency
1 Day
17036
AC Stable Time
90 sec. maximum
17041
AC Report Delay
6-12 hours
17049
RF Supervisory Time
4 hours
17069
No Phone Line
0-Off
17072
Enable RF Jam Detect
1-On
17073
Automatic Panel Backup Bat-
tery Test Interval
1-4 hours
17076
Commercial/Residential
1-Commercial
17078
Detect Receiver Failure
1-On
17079
Alarm Messages Play at High
Volume
1-On High
17096
Report System Events
1-On
47004
#2-Supervisory Time Zone
Attribute (all sensors)
#4-Hardwire Smoke Verify
Zone Attribute
A (set to 4 hrs. in
Feature 17049)
0-No
xx = Two digit partition number.
yy = Two digit non-pager phone number.