8.4.9.5. DPÜ/B menu
Activating the DPÜ/B icon opens the corres-
ponding dialogue window.
The DPÜ/B modules are directly installed
into the sub-distribution boards to monitor the supply
voltage of the general lighting. The modules are commu-
nicating by the intern BUS. Up to 31 pieces can be con-
nected to the BUS. If a phase fails, this will be indicated
at the controller. All three LEDs glow green, if all three
phases are available at the DPÜ/B inputs.
If one or more phases fail, the corresponding LED
changes to yellow. The component icon is shown in yel-
low in the main menu and the message “sub-DB failure”
appears in the status display.
8.4.9.5. Menü DPÜ/B
Durch Betätigen des Symbols DPÜ/B öffnet
sich der entsprechende Dialog.
Zur Überwachung der Netzspannung an
den Unterverteilern der Allgemeinbeleuch-
tung werden die DPÜ/B-Module direkt in den Unter-
verteiler eingebaut. Die Abfrage der Module erfolgt
über den internen Bus. Es können bis zu 31 busfähige
Dreiphasenüberwachungen angeschlossen werden. Bei
Ausfall einer Phase wird diese im Steuerteil angezeigt.
Sofern alle drei Phasen spannungsführend an den Ein-
gängen der DPÜ/B anliegen, leuchten alle drei LED‘s
grün.
Bei Ausfall einer oder mehrerer Phasen ändert sich die
jeweilige LED. Im Display des Hauptmenüs erscheint das
Komponentensymbol in Gelb, in der Statusanzeige wird
die Information „Netzausfall UV“ angezeigt.